NS2 Configuration Guide

M-56K Dial-up Modem, RS-485 Connection

Thirty-one NS2 panels for each drop line.
NStar Server
Refer to
485-PCI/
N-485-HUB-2
NS2 Panel
Connection
Detail
diagram.
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
DB 9 / DB 25 Connectors
Female
16
COM Port
Straight Thru Cable
Female 9 Pin
Male 25 Pin
(RX)
2
3
(TX)
3
2
(Comm) 5
7 (Comm)
RS-232 (50 Ft.)
RS-485 (4,000 Ft.)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
NS2
Panel
EG
It is recommended to earth ground (EG)
Male
M-56K
FAX/MODEM
Local DIP Switch Settings
(1, 3, 5, 8 ON) (2, 4, 6, 7 OFF)
(RX)
(TX)
M-56K
FAX/MODEM
Remote DIP Switch Settings
(1, 3, 8 ON) (2, 4, 5, 6, 7 OFF)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
NS2
Panel
EG
Only Earth Ground (EG)
one side of cable.
EG
each NS2 Enclosure individually.
RS-485 Cable
RS-485
NS2 Panel
Red/White
TB9-1 (RS485+)
Black/Green
TB9-2 (RS485-)
RS-485 COM
TB9-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
Honeywell Access Systems
Analog Phone Line
Dedicated analog phone
line recommended
See RS-485
Cable note.
EG
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
7-101004-01