M-9600 Dial-up Modem, RS-485 Connection

Thirty-one NS2 panels for each drop line.
NStar Server
Refer to
N-485-HUB-2
485-PCI /
NS2 Panel
Connection
Detail
diagram.
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
Female
7-101004-01
Straight Thru Cable (9-25 Pin)
Female 9 Pin
(RX)
(TX)
(Comm) 5
RS-232 (50 Ft.)
DB 9 / DB 25 Connectors
Male
Male 25 Pin
2
3
(RX)
3
2
(TX)
7 (Comm)
RS-485 (4,000 Ft.)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
NS2
Panel
EG
EG
It is recommended to earth ground (EG) each
NS2 enclosure individually.
RS-485
Red/White
Black/Green
RS-485 COM
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
NS2 Configuration Guide
M-9600-2
Analog Phone Line
Dedicated analog phone
line recommended
M-9600-2
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
NS2
Panel
EG
Only Earth Ground (EG)
one side of cable.
EG
RS-485 Cable
NS2 Panel
NS2 Panel
TB9-1 (RS485+)
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
TB9-3 (RS485 COM)
See RS-485
Cable note.