NS2 Configuration Guide

Lease Line Modem Connection

Thirty-one NS2 panels for each drop line.
NStar Server
Refer to
485-PCI /
N-485-PCI-2
NS2 Panel
Connection
Detail
diagram.
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
DB 9 / DB 25 Connectors
Female
12
Straight Thru Cable (9-25 Pin)
Female 9 Pin
Male 25 Pin
(RX)
2
3
(TX)
3
2
(Comm) 5
COM Port
RS-232 (50 Ft.)
Null Modem Cable Cable (9-25 Pin)
Male 9 Pin
Female 25 Pin
(RX)
2
(TX)
3
3
(Comm) 5
RS-232 (50 Ft.)
RS-485 (4,000 Ft.)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
Panel
EG
Male
(RX)
(TX)
7 (Comm)
M-9600-LO
2
(TX)
(RX)
7 (Comm)
M-9600-LA
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
NS2
EG
Only Earth Ground (EG)
one side of cable.
EG
It is recommended to earth ground (EG) each
NS2 enclosure individually.
RS-485 Cable
RS-485
NS2 Panel
Red/White
TB9-1 (RS485+)
Black/Green
TB9-2 (RS485-)
RS-485 COM
TB9-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
Honeywell Access Systems
Lease
Line
Phone
Line
NS2
See RS-485
Panel
Cable note.
EG
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
7-101004-01