LANSRLU1 Connection

Thirty-one panels for each drop line, Maximum sixty-four IP connections.
NStar Server
RS-485
NS2 Panel
Red/White
TB9-1 (RS485+)
Black/Green
TB9-2 (RS485-)
RS-485 COM
TB9-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
7-101004-01
NIC
100BaseT (CAT 5) 328 Ft. Max.
RS-485 Cable
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
LANSRLU1
documentation
for programmig.
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
NS2
Panel
EG
It is recommended to earth ground (EG) each
HUB
LANSRLU1
Refer to
RJ-45
RS-232 (50 Ft.)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
NS2
Panel
EG
Only Earth Ground (EG)
one side of cable.
EG
NS2 enclosure individually.
NS2 Configuration Guide
100BaseT (CAT 5)
328 Ft. Max.
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
S8: OFF (19,200 Baud Rate)
NS2 Panel
N-485-PCI-2L
Connection
See RS-485
Cable note.
EG
Refer to
485-PCI /
Detail
diagram.