Lansrl100 Connection - Honeywell NSEK Configuration Manual

Configuration guide
Hide thumbs

Advertisement

NS2 Configuration Guide

LANSRL100 Connection

Thirty-one NS2 panels for each drop line, Maximum sixty-four IP connections.
NStar Server
RS-485
NS2 Panel
Red/White
TB9-1 (RS485+)
Black/Green
TB9-2 (RS485-)
RS-485 COM
TB9-3 (RS485 COM)
4,000 ft. (1,200 m) max, 24 AWG, 2 twisted pairs with
shield, 120 ohm, 23 pf (NCI part no. NCP2441-TN)
10
100BaseT (CAT 5) 328 Ft. Max.
NIC
RS-485 Cable
NS2 Panel
TB9-1 (RS485+)
TB9-2 (RS485-)
TB9-3 (RS485 COM)
Refer to
LANSRL100
documentation
for programmig.
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: ON (485 EOL)
NS2
Panel
EG
It is recommended to earth ground (EG) each
HUB
100BaseT (CAT 5)
328 Ft. Max.
DIP Switch Settings
S1: ON
S2: ON
S3: ON
S4: ON
S5: ON
S6: OFF (Ack/Nak on)
S7: ON
LANSRL100
S8: OFF (19,200 Baud Rate)
RJ-45
RS-232 (50 Ft.)
DIP Switch Settings
S1-S5: Panel Address
S6: ON (RS-485 Enable)
S7: N/A (Baud Rate)
S8-S9: OFF (Bias)
S10: OFF (485 EOL)
NS2
Panel
EG
Only Earth Ground
(EG) one side of
EG
cable.
NS2 enclosure individually.
Honeywell Access Systems
Refer to
485-PCI /
NS2 Panel
N-485-PCI-2L
Connection
Detail
diagram.
See RS-485
Cable note.
EG
7-101004-01