Samsung SMH1927B/XAA Installation Instructions Manual page 5

Over the range microwave oven
Hide thumbs Also See for SMH1927B/XAA:
Table of Contents

Advertisement

NOTE: If you need to install ducts, note that the total
duct length of 3 ¼˝ x 10˝ rectangular or 6˝ diameter
round duct should not exceed 140 equivalent feet.
Outside ventilation requires a HOOD EXHAUST DUCT.
Read the following carefully.
NOTE: It is important that venting be installed using
the most direct route and with as few elbows as
possible. This ensures clear venting of exhaust and
helps prevent blockages. Also, make sure dampers
swing freely and nothing is blocking the ducts.
Exhaust connection:
The hood exhaust has been designed to mate with a
standard 3 ¼˝ x 10˝ rectangular duct.
If a round duct is required, a rectangular-to-round
transition adaptor must be used. Do not use less
than a 6˝ diameter duct.
e
d
.
SMH1927_XAA_DE68-04108A-01_EN_120725.indd 5
DUCT PIECES
Rectangular-to-Round
Transition Adaptor*
Wall Cap
90 ° Elbow
45 ° Elbow
90 ° Elbow
45 ° Elbow
Roof Cap
Straight Duct 6˝ Round or 3 ¼˝
x 10˝ Rectangular
*
IMPORTANT: If a rectangular-to-round
transition adaptor is used, the bottom
corners of the damper will have to be cut
to fit, using tin snips, in order to allow free
movement of the damper.
General information
maximum duct length:
For satisfactory air movement, the total duct length of
3 ¼˝ x 10˝ rectangular or 6˝ diameter round duct should
not exceed 140 equivalent feet.
Elbows, transitions, wall and roof
caps, etc.,
and are equivalent to a section of straight duct which is
longer than their actual physical size. When calculating
the total duct length, add the equivalent lengths of all
transitions and adaptors plus the length of all straight
duct sections. The chart below shows you how to
calculate total equivalent ductwork length using the
equivalent length in feet of some typical ducts.
EQUIVALENT
NUMBER
x
LENGTH
5 ft.
x
40 ft.
x
10 ft.
x
5 ft.
x
25 ft.
x
5 ft.
x
24 ft.
x
1 ft.
x
Total Ductwork
Equivalent lengths of duct pieces
are based on actual tests and reflect
the requirements for good venting
performance with any vent hood.
5
present additional resistance to airflow
EQUIVALENT
=
USED
LENGTH
(
)
=
(
)
=
(
)
=
(
)
=
(
)
=
(
)
=
(
)
=
(
)
=
=
2012-07-25
ft.
ft.
ft.
ft.
ft.
ft.
ft.
ft.
ft.
7:54:28