Rack-mounting
Switch 5500 (non
S
WITCH
Water or moisture cannot enter the case of the Switch.
■
Air flow is not restricted around the Switch or through the vents in the
■
side of the Switch. 3Com recommends that you provide a minimum of
25 mm (1 in.) clearance.
Air temperature around the Switch does not exceed 40 °C (104
■
If the Switch is installed in a 19-inch rack or closed assembly its local air
temperature may be greater than room ambient temperature.
The air is as free from dust as possible.
■
The Switch is situated away from sources of conductive (electrical)
■
dust, for example laser printers.
The unit is installed in a clean, air conditioned environment.
■
The AC supply used by the Switch is separate to that used by units
■
that generate high levels of AC noise, for example air conditioning
units.
No more than four Switch units are placed on top of one another, if
■
the units are free-standing.
The Switch 5500 is 1U high and will fit in most standard 19-inch racks.
CAUTION: Disconnect all cables from the Switch before continuing.
Remove all self adhesive pads from the underside of the Switch if they
have been fitted.
CAUTION: If you use a shelf or support ensure that it will not obstruct
the air flow through the side panels of the Switch.
To rack-mount your Switch 5500 (non PoE):
PoE)
1 Place the Switch the right way up on a hard flat surface, with the front
facing towards you.
2 Locate a securing bracket over the mounting holes on one side of the
front of the Switch, as shown in
Figure
12.
F).
°