This appendix contains the following topics:

Site Requirements for the Switch

Power Requirements
Safety Information
Preinstallation Information
Site Requirements for the Switch
This section describes the following site requirements
for setting up your CoreBuilder
Switch (7-slot chassis, 8-slot chassis, and 16-slot
chassis):

Location Requirements

Precautionary Guidelines
Ventilation Requirements
Location Requirements
Install a CoreBuilder 9000 Enterprise Switch in an
area that meets the following requirements:
Ambient (room) temperature: 0 °C to 50 °C (32 °F
to 122 °F). The default internal operating
temperature threshold for the CoreBuilder 9000
Switch is approximately 60 °C (140 °F).
Relative humidity: between 10 and 90 percent,
noncondensing.
R
EQUIREMENTS
®
9000 Enterprise
, S
,
AFETY
I
NFORMATION
The table or rack on which you mount the chassis
supports at least three times the weight of a fully
loaded chassis.
The recommended minimum space that is required
between the front of the chassis and another
vertical surface (such as a rack door) is 8 cm (3 in.).
There is a sufficient amount of space on each side
of the 7-slot chassis to accommodate any cables
along the side of the chassis.
There is at least 7 cm (2.76 in.) on each side of the
7-slot chassis to ensure proper cooling in the
chassis.
There is at least 91.4 cm (36 in.) in back of the
chassis to:
Remove and replace power supplies in the
7-slot chassis.
Remove and replace the fan trays in the 8-slot
chassis and 16-slot chassis.
Maintain proper cooling.
If the chassis is the first device in your rack, then
mount it about 10.2 cm (4 in.) up from the floor.
The power source is within approximately 2 meters
(6.6 feet) of the location where you plan to install
the CoreBuilder 9000 chassis.