A Specifications; Power Requirements - HP D5970A - NetServer - LCII Installation Manual

Hp netserver lxr 8000 installation guide
Hide thumbs Also See for D5970A - NetServer - LCII:
Table of Contents

Advertisement

A Specifications

Power Requirements

Table A-1. Power Requirements
Voltage and frequency
Maximum continuous power
input
Maximum inrush current
Delayed action circuit breaker
recommended
Power availability
NOTE
Some local codes do now allow a 16-amp device to be
connected to a 16-amp service. Consult a qualified electrician
or local regulatory authority before beginning electrical site
preparation.
200-240 VAC; 50/60 Hz
1100 W for a four-CPU configuration; 5.6 A at 200/208
V, 4.9 A at 230/240 V.
150 A for 4 ms
North America: a 20 A minimum circuit is to be used
with one NEMA AB1 class 14B breaker for each 16 A
power distribution unit (PDU) that is connected to an HP
NetServer LXr 8000.
Europe (single server in a rack): use a 16 A-minimum
circuit with one IEC MCB C-type breaker for each 16-
amp PDU.
Europe (multiple servers in a rack): use a 16-amp-
minimum circuit with one IEC MCB D-type breaker for
each 16 A PDU.
1500 DC watts continuous
133