En.06 Unrecoverable Condition-No Blowers Installed; Temperature Conditions; En.01 Noncritical Condition-High Temperature - HP 6100 User Manual

Enterprise virtual array
Hide thumbs Also See for 6100:
Table of Contents

Advertisement

0.3.en.06 UNRECOVERABLE condition—No blowers installed
NOTE:
IMPORTANT
When this condition exists there will be two error messages.
The first message will be 0.3.en.05 and will identify the first blower.
The second message will be 0.3.en.06 and will identify the second blower.
The EMU cannot detect any installed blowers. Shutdown is imminent! The EMU will shut down the
enclosure in seven minutes unless you correct the problem. This condition report remains active
until you correct the problem or the EMU shuts down the power supplies, whichever occurs first.
Complete the following procedure to correct this problem.
1.
Record all six characters of the condition report.
2.
Use the controller shutdown procedure to shut down the controllers.
3.
Contact your authorized service representative.
CAUTION:
removed before a replacement is available.

Temperature conditions

The format of a temperature condition report is 0.4.en.ec, where:
0.4. is the temperature sensor element type
en. is the two-character temperature sensor element
ec is the error code
See
Table 43 (page 128)
Table 43 Temperature sensor element numbering
Sensor
01.
02.
03.
04.
05.
06.
07.
08.
09.
The following sections list the temperature condition reports and the default temperature thresholds.
Use HP Command View EVA to view the temperature sensor ranges for the disk drives, EMU, and
power supplies.
0.4.en.01 NONCRITICAL condition—High temperature
This condition report indicates that an element temperature is approaching, but has not reached,
the high temperature CRITICAL threshold. Continued operation under these conditions may result
in a CRITICAL condition. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1.
Record all six characters of the condition report.
2.
Ensure that all elements are properly installed to maintain proper air flow.
128 EMU-generated condition reports
An automatic shutdown and possible data corruption may result if the
to determine the location of each temperature sensor.
Sensor location
Power Supply 1 Exhaust
Power Supply 2 Exhaust
EMU
Drive Bay 1
Drive Bay 2
Drive Bay 3
Drive Bay 4
Drive Bay 5
Drive Bay 6
Sensor
Sensor location
10.
Drive Bay 7
1 1.
Drive Bay 8
12.
Drive Bay 9
13.
Drive Bay 10
14.
Drive Bay 1 1
15.
Drive Bay 12
16.
Drive Bay 13
17.
Drive Bay 14
blower