Complete Installation - Kenmore 6965 - 600 5.9 cu. Ft. Capacity Electric Flatback Dryer Installation Instructions Manual

29" (73.7cm) electric dryer
Hide thumbs Also See for 6965 - 600 5.9 cu. Ft. Capacity Electric Flatback Dryer:
Table of Contents

Advertisement

Available languages

Available languages

Style 2:Direct w irestrainrelief
Unscrew the removable conduit connector and any
screws from a 3/4" (19 mm) UL listed strain relief (UL
marking on strain relief). Put the threaded section of the
strain relief through the hole below the terminal block
opening. Reaching inside the terminal block opening,
screw the removable conduit connector onto the strain
relief threads.
4.
A. Removable
conduit connector
B. Hole below terminal block opening
C. Strain relief threads
Put direct wire cable through the strain relief. The strain
relief should have a tight fit with the dryer cabinet and be
in a horizontal position. Tighten strain relief screw against
the direct wire cable.
Now complete installation following instructions
for your
type of electrical connection:
4-wire (recommended)
3-wire (if 4-wire is not available)
Electrical Connection Options
If your home has:
And you will be
Go to Section
connecting to:
4-wire receptacle
A UL listed,
4-wire connection:
(NEMA Type 14-30R)
120/240-volt
Power supply cord
(_)
minimum,
30-amp, dryer
power supply
cord*
4-wire direct
A fused
4-wire connection:
disconnect
or
Direct Wire
circuit breaker
box*
3-wire receptacle
A UL listed,
(NEMA type 10-30R)
120/240-volt
(_
minimum,
30-amp, dryer
power supply
cord*
3-wire connection:
Power supply cord
3-wire direct
A fused
disconnect
or
circuit breaker
box*
(89 mm_
3-wire connection:
Direct Wire
* If local codes do not permit the connection of a
cabinet-ground
conductor to the neutral wire, go to
"Optional 3-wire connection"
section.
4-wire connection:
Power Supply
Cord
IMPORTANT: A 4-wire connection
is required for mobile
homes and where local codes do not permit the use of
3-wire connections.
A
B
F
C
D
E
G
A. 4-wire receptacle
(NEMA type 14-30R)
B. 4-prong plug
C. Ground prong
D. Neutral prong
E. Spade terminals with upturned ends
F. 3/4" (19 mm) UL listed strain relief
G. Ring terminals
1. Remove center terminal block screw.