ANSI / SIA CP-01 REQUIREMENTS

To meet SIA CP-01 requirements –
Minimum System Requirements: 1 control panel; 2 keypads (or 1 keypad per partition for multi-partitioned systems)
Remote arming shall NOT be enabled in SIA classified installations.
Off-premise transmission must be in the SIA format.
The Abort window and Entry Delay must not exceed 1 minute.
CAUTION – A call waiting cancel on a non-call waiting line will prevent successful connection to the central station.
CP-01 Feature
Description
Exit Time
Progress Annuncation / Disable
– for Silent Exit
Exit Time Restart
Auto Stay Arm on Unvacated Premises
Exit Time and Progress
Annunciation / Disable
– for Remote Arm
Entry Delay(s)
Abort Window
– for Non-Fire Zones
Abort Window Time
– for Non-Fire Zones
Abort Annunciation
Cancel Annunciation
Duress Feature
Cross Zoning
Programmable Cross Zoning Time
Swinger Shutdown
Swinger Shutdown Disable
Fire Alarm Verification
Call Waiting Cancel
Default Changes (from prior versions):
IMPORTANT NOTE: UL requirements take priority over SIA requirements.
Feature Description
as shown in manual
Exit 1 Delay
Exit 2 Delay
Silent Keypad Option
This feature is non-programmable in the panel.
Auto Bypass
This feature is non-programmable in the panel.
Entry 1 Delay
Entry 2 Delay
Dialer Delay
Dialer Delay
This feature is non-programmable in the panel.
Cancel
Duress
2 Trips on Cross Zone
Keypad sounds on Cross Zone trip
Zone Type Characteristic
Cross Zone Time
Swinger Shutdown Count
Swinger Shutdown Count
Fire Alarm Verification Time
Must be programmed as part of the
phone number
Recent Closing
Exit Error
Power Up Delay
Program
Seg / Opt
Loc
24
2
24
4
9 3
2
All annunciators enabled
23
1 / 3
-- Exit time and progress are always enabled.
24
1
24
3
40
8
40
8
-- Flashing Cancel LED goes off when disarming.
23
3 / 6
44
37
5 / 4
39
5
111
3 / 4
40
6
38
n/a
Enabled for 1 trip
38
n/a
Enabled for 1 trip
40
9
0
n/a
23
3 / 7
23
3 / 8
40
3
Factory
Default
45 – 240 sec.
60
45 – 240 sec.
60
Allowed
(individual keypads may be disabled)
Enabled
Enabled
Enabled
Enabled (may be disabled for remote arming)
30
30 – 240 sec.
30
30 – 240 sec.
30
Enabled
(may be disabled by zone/ zone type)
30
15 – 45 sec.
Enabled
Enabled
Enabled
Disabled
Disabled
Disabled
Required
Disabled
Disabled
5 minutes
Allowed
For all non-fire zones, shut down at 1–2 trips
Allowed
Disabled
Required (depends on panel & sensors)
n/a
Required (depends on user phone line)
Enabled
Enabled
60 sec.
CP-01 Required
Setting
NOTE:
Combined
Abort window
and Entry
Delay must
not exceed 1
minute.