16

Product Specifications

Rated Maximum Load Current* (at 25°C/77°F) . . . . . . . . 200 Amps
Rated AC Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 250 Volts
Poles. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
Frequency . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60 Hz
Fault Current Rating . . . . . . . . . 25,000 RMS Symmetrical Amperes
Supervisory Contacts Rating:
A-A Terminals . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24 Volt AC
B-B Terminals . . . . . . . . . . . . . . . . 1 Amp, 125 Volt AC, Pilot Duty
Normal Operating Range . . . . . . . . -20°F (-28.8°C) to 104°F (40°C)
Weight . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .63 lbs. (29 kg)
*This transfer switch is certified in accordance with UL (Underwriters Laboratories)
1008 (transfer switch equipment).