Copyright This document and parts thereof must not be reproduced or copied without written permission from ABB, and the contents thereof must not be imparted to a third party, nor used for any unauthorized purpose. The software or hardware described in this document is furnished under a license and may be used, copied, or disclosed only in accordance with the terms of such license.
Page 5
In case any errors are detected, the reader is kindly requested to notify the manufacturer. Other than under explicit contractual commitments, in no event shall ABB be responsible or liable for any loss or damage resulting from the use of this manual or the application of the equipment.
Page 6
(EMC Directive 2004/108/EC) and concerning electrical equipment for use within specified voltage limits (Low-voltage directive 2006/95/EC). This conformity is the result of tests conducted by ABB in accordance with the product standards EN 50263 and EN 60255-26 for the EMC directive, and with the product standards EN 60255-1 and EN 60255-27 for the low voltage directive.
Page 10
LD0.MAPGAPC7 Multipurpose analog protection function (7)................47 LD0.MAPGAPC8 Multipurpose analog protection function (8)................47 LD0.MAPGAPC9 Multipurpose analog protection function (9)................48 LD0.MAPGAPC10 Multipurpose analog protection function (10)................48 LD0.MAPGAPC11 Multipurpose analog protection function (11)................48 LD0.MAPGAPC12 Multipurpose analog protection function (12)................48 REF620 Point List Manual...
Page 11
Sensors and monitoring functions..........58 LD0.SSCBR1 Reset signals of CB condition monitoring..58 LD0.SSCBR2 Reset signals of CB condition monitoring..59 Metering and measurand functions..........59 LD0.PEMMXU1 Reset accumulated energy values....59 Protection functions..............59 LD0.LSHDPFRQ1 Loadshedding controls (1)......59 LD0.LSHDPFRQ2 Loadshedding controls (2)......59 REF620 Point List Manual...
Page 12
CTRL.DCXSWI2 Controllable disconnector 2, 4-pole (2 bit) position values..............68 CTRL.DCXSWI3 Controllable disconnector 3, 4-pole (2 bit) position values..............68 CTRL.DCXSWI4 Controllable disconnector 4, 4-pole (2 bit) position values..............68 CTRL.ESSXSWI1 Earth switch 1, 4-pole (2 bit) position values..................68 REF620 Point List Manual...
Page 13
LD0.DARREC1 Autoreclosing values........73 LD0.DARREC2 Autoreclosing values........73 DR.RDRE1 Disturbance recorder values.......73 LD0.SECRSYN1 Synchrocheck line and bus state....74 Physical and raw I/O data............74 LD0.XRGGIO105 RTD inputs..........74 Section 3 DNP3 protocol implementation........75 DNP3 device profile................75 DNP3 implementation table..............77 Section 4 Glossary.................81 REF620 Point List Manual...
The engineering manual contains instructions on how to engineer the IEDs using the different tools in PCM600. The manual provides instructions on how to set up a PCM600 project and insert IEDs to the project structure. The manual also REF620 Point List Manual...
1.3.2 Document revision history Document revision/date Product version History A/2013-05-07 First release Download the latest documents from the ABB Website http://www.abb.com/substationautomation. 1.3.3 Related documentation Name of the document Document ID DNP3 Communication Protocol Manual 1MRS757646 Symbols and conventions 1.4.1...
Parameter values are indicated with quotation marks. The corresponding parameter values are "On" and "Off". • IED input/output messages and monitored data names are shown in Courier font. When the function starts, the START output is set to TRUE. REF620 Point List Manual...
Section 1 1MRS757652 A Introduction 1.4.3 Functions, codes and symbols Table 1: REF620 functions, codes and symbols Function IEC 61850 IEC 60617 IEC-ANSI Protection Three-phase non-directional overcurrent protection, low stage, PHLPTOC1 3I> (1) 51P-1 (1) instance 1 Three-phase non-directional overcurrent protection, high stage, PHHPTOC1 3I>>...
Page 19
Frequency protection, instance 5 FRPFRQ5 f>/f<,df/dt (5) 81 (5) Frequency protection, instance 6 FRPFRQ6 f>/f<,df/dt (6) 81 (6) Three-phase thermal protection for feeders, cables and distribution T1PTTR1 3Ith>F (1) 49F (1) transformers Table continues on next page REF620 Point List Manual...
Page 20
I <-> O ESC (1) Disconnector control, instance 3 DCXSWI3 I <-> O DCC (3) I <-> O DCC (3) Disconnector control, instance 4 DCXSWI4 I <-> O DCC (4) I <-> O DCC (4) Table continues on next page REF620 Point List Manual...
Page 21
I1, I2, I0 (1) instance 1 Residual current measurement, RESCMMXU1 Io (1) In (1) instance 1 Three-phase voltage measurement VMMXU1 3U (1) 3V (1) Residual voltage measurement RESVMMXU1 Uo (1) Vn (1) Table continues on next page REF620 Point List Manual...
Page 22
SR (4) Move (8 pcs), instance 1 MVGAPC1 MV (1) MV (1) Move (8 pcs), instance 2 MVGAPC2 MV (2) MV (2) Move (8 pcs), instance 3 MVGAPC3 MV (3) MV (3) Table continues on next page REF620 Point List Manual...
Page 23
FKEYGGIO1 FKEY (1) FKEY (1) Logging functions Disturbance recorder RDRE1 DR (1) DFR (1) Fault recorder FLTMSTA1 FR (1) FR (1) Sequence event recorder SER1 SER (1) SER (1) Load profile LDPMSTA1 LOADPROF (1) LOADPROF (1) REF620 Point List Manual...
This list represents the superset of DNP3 points. The actual set of available points, meaning the actual set of available applications, is determined by the IED's order code. Supported functions Table 2: Supported functions in REF620 Function block FE201 FE202 PHLPTOC1 ●...
IEC 61850 name SA name Description Values CTRL.LLN0 .Loc.stVal Remote/Local state 0/1=Rem/Loc 2.3.1.2 LD0.LLN0 Settings supervision Table 5: LD0.LLN0 Settings supervision IEC 61850 name SA name Description Values LD0.LLN0 .SetChg.stVal Settings changed 1=Changed .SetSeld.stVal Settings reserved 1=Reserved REF620 Point List Manual...
.LoWrn.stVal LOW_WARN Low warning 1=Warning 2.3.4.4 LD0.RESVMMXU1 Residual voltage limit supervision Table 24: LD0.RESVMMXU1 Residual voltage limit supervision IEC 61850 name SA name Description Values LD0.RESVMMXU1 .HiAlm.stVal HIGH_ALARM High alarm 1=Alarm .HiWrn.stVal HIGH_WARN High warning 1=Warning REF620 Point List Manual...
1=Start 2.3.7 Protection related functions 2.3.7.1 LD0.CCRDIF1 Current circuit failure protection Table 88: LD0.CCRDIF1 Current circuit failure protection IEC 61850 name SA name Description Values LD0.CCRDIF1 .Alm.stVal FAIL Fail Alarm 1=Alarm .Op.general ALARM Fail Operate 1=Operate REF620 Point List Manual...
1=Open CB .UnsCBCls.stVal UNSUC_CB CB closing failed 1=Failed .WtMstr.stVal CMD_WAIT Master signal to follower 1=Signal 2.3.7.5 DR.RDRE1 Disturbance recorder Table 92: DR.RDRE1 Disturbance recorder IEC 61850 name SA name Description Values DR.RDRE1 .RcdMade.stVal DR recording made 1=Made REF620 Point List Manual...
LD0.MAPGAPC3 Multipurpose analog protection function (3) Table 96: LD0.MAPGAPC3 Multipurpose analog protection function (3) IEC 61850 name SA name Description Values LD0.MAPGAPC3 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REF620 Point List Manual...
LD0.MAPGAPC8 Multipurpose analog protection function (8) Table 101: LD0.MAPGAPC8 Multipurpose analog protection function (8) IEC 61850 name SA name Description Values LD0.MAPGAPC8 .Op.general OPERATE Stage operate 1 = Operate .Str.general START Stage start 1 = Start REF620 Point List Manual...
LD0.MVGAPC1 Multipurpose binary inputs (1) Table 106: LD0.MVGAPC1 Multipurpose binary inputs (1) IEC 61850 name SA name Description Values LD0.MVGAPC1 .Q1.stVal Input 1 signal 0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On Table continues on next page REF620 Point List Manual...
0/1=Off/On .Q2.stVal Input 2 signal 0/1=Off/On .Q3.stVal Input 3 signal 0/1=Off/On .Q4.stVal Input 4 signal 0/1=Off/On .Q5.stVal Input 5 signal 0/1=Off/On .Q6.stVal Input 6 signal 0/1=Off/On .Q7.stVal Input 7 signal 0/1=Off/On .Q8.stVal Input 8 signal 0/1=Off/On REF620 Point List Manual...
0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On .SPCS14.stVal Output 14 state 0/1=Off/On .SPCS15.stVal Output 15 state 0/1=Off/On .SPCS16.stVal Output 16 state 0/1=Off/On REF620 Point List Manual...
0/1=Off/On .SPCS08.stVal Output 8 state 0/1=Off/On .SPCS09.stVal Output 9 state 0/1=Off/On .SPCS10.stVal Output 10 state 0/1=Off/On .SPCS11.stVal Output 11 state 0/1=Off/On .SPCS12.stVal Output 12 state 0/1=Off/On .SPCS13.stVal Output 13 state 0/1=Off/On Table continues on next page REF620 Point List Manual...
0/1=Off/On .SPCS03.stVal LED 3 state 0/1=Off/On .SPCS04.stVal LED 4 state 0/1=Off/On .SPCS05.stVal LED 5 state 0/1=Off/On .SPCS06.stVal LED 6 state 0/1=Off/On .SPCS07.stVal LED 7 state 0/1=Off/On .SPCS08.stVal LED 8 state 0/1=Off/On Table continues on next page REF620 Point List Manual...
LD0.DNPGGIO1 Parameter setting group control Table 125: LD0.DNPGGIO1 Parameter setting group control IEC 61850 name SA name Description Type LD0.DNPGGIO1 .ActSG1.ctlVal Setting group 1 .ActSG2.ctlVal Setting group 2 .ActSG3.ctlVal Setting group 3 Table continues on next page REF620 Point List Manual...
IEC 61850 name SA name Description Type CTRL.DCCSWI1 .Pos.Oper.ctlVal Disconnector control On/Off 2.4.2.4 CTRL.DCCSWI2 Controllable disconnector (2) control Table 129: CTRL.DCCSWI2 Controllable disconnector (2) control IEC 61850 name SA name Description Type CTRL.DCCSWI2 .Pos.Oper.ctlVal Disconnector control On/Off REF620 Point List Manual...
LD0.SSCBR1 Reset signals of CB condition monitoring IEC 61850 name SA name Description Type LD0.SSCBR1 .RsAccAPwr.Oper.ctlVal RST_IPOW Reset accum. energy .RsCBWear.Oper.ctlVal RST_CB_WEAR Reset CB life and op. counter .RsSprChaTm.Oper.ctlVal RST_SPR_T Reset spring charge alarm .RsTrvTm.Oper.ctlVal RST_TRV_T Reset travel time alarm REF620 Point List Manual...
Manual restore .BlkRest.Oper.ctlVal BLK_REST Cancel restore 2.4.6 Protection related functions 2.4.6.1 LD0.DARREC1 Autoreclosing reset signals Table 143: LD0.DARREC1 Autoreclosing reset signals IEC 61850 name SA name Description Type LD0.DARREC1 .RsCnt.Oper.ctlVal AR reset all counters .RsRec.Oper.ctlVal AR reset REF620 Point List Manual...
On/Off .SPCS08.ctlVal Output 8 control On/Off .SPCS09.ctlVal Output 9 control On/Off .SPCS10.ctlVal Output 10 control On/Off .SPCS11.ctlVal Output 11 control On/Off .SPCS12.ctlVal Output 12 control On/Off .SPCS13.ctlVal Output 13 control On/Off Table continues on next page REF620 Point List Manual...
The binary outputs can be configured either as pulse- or persistent-type outputs. Pulse- type outputs are triggered with the write value "1". Persistent-type outputs can be written with both values "1" and "0". The setting mode "toggled" for local operation corresponds to "persistent" for remote operation. REF620 Point List Manual...
On/Off .SPCS06.ctlVal Output 6 control On/Off .SPCS07.ctlVal Output 7 control On/Off .SPCS08.ctlVal Output 8 control On/Off .SPCS09.ctlVal Output 9 control On/Off .SPCS10.ctlVal Output 10 control On/Off .SPCS11.ctlVal Output 11 control On/Off Table continues on next page REF620 Point List Manual...
Switchgear functions 2.5.2.1 CTRL.CBCSWI1 CB 4-pole (2 bit) position value Table 157: CTRL.CBCSWI1 CB 4-pole (2 bit) position value IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.CBCSWI1 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REF620 Point List Manual...
CTRL.DCSXSWI4 Disconnector 4, 4-pole (2 bit) position values Table 162: CTRL.DCSXSWI4 Disconnector 4, 4-pole (2 bit) position values IEC 61850 name SA name Description Values Arg 1,2,3,4 CTRL.DCSXSWI4 Intermediate=0; Off=1; On=2; .Pos.stVal POSITION Bad=3 0…3 0,3,0,3 REF620 Point List Manual...
0,99999,0,99999 .InaTmdCnt.stVal INA_DAYS CB inactive days 0…9999 .RmnLifPhA.stVal CB_LIFE_A Remaining life, phase A -9999…9999 -9999,9999,-9999,9999 .RmnLifPhB.stVal CB_LIFE_B Remaining life, phase B -9999…9999 -9999,9999,-9999,9999 .RmnLifPhC.stVal CB_LIFE_C Remaining life, phase C -9999…9999 -9999,9999,-9999,9999 Table continues on next page REF620 Point List Manual...
0,40,0,4000 .A.phsC.instCVal.mag I_INST_C -phsC magnitude 0.00..40.0 [xIn] 0,40,0,4000 2.5.4.2 LD0.RESCMMXU1 Residual current (1) Table 174: LD0.RESCMMXU1 Residual current (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESCMMXU1 .A.res.instCVal.mag I0_INST Residual current 0.00..40.0 [xIn] 0,40,0,4000 REF620 Point List Manual...
0,4,0,400 0.00…4.00 .phsCA.cVal.mag U_DB_CA -phsCA magnitude [xUn] 0,4,0,400 2.5.4.5 LD0.RESVMMXU1 Residual voltage (1) Table 177: LD0.RESVMMXU1 Residual voltage (1) IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.RESVMMXU1 0.00..4.00 .PhV.res.instCVal.mag U0_INST Residual voltage [xUn] 0,4,0,400 REF620 Point List Manual...
Description Values Arg 1,2,3,4 LD0.FMMXU1 .Hz.mag Frequency value 35…75 [Hz] 35,75,3500,7500 2.5.4.9 LD0.HAEFMHAI1 Current harmonics Table 181: LD0.HAEFMHAI1 Current harmonics IEC 61850 name SA name Description Values Arg 1,2,3,4 LD0.HAEFMHAI .HRmsA.res.cVal.mag Current harmonics 0…250 [A] 0,250,0,250 REF620 Point List Manual...
0…65535 0,65535,0,65535 2.5.6.3 DR.RDRE1 Disturbance recorder values Table 185: DR.RDRE1 Disturbance recorder values IEC 61850 name SA name Description Values Arg 1,2,3,4 DR.RDRE1 .FltNum.stVal Number of recordings 0…65535 0,65535,0,65535 .MemUsed.stVal Rec. memory used 0…100 [%] 0,100,0,100 REF620 Point List Manual...
Implementation table and the point list tables, provides a complete configuration/interoperability guide for communicating with a device. Table 188: Device profile document DNP3 device profile document Vendor name: ABB Oy Device name: REF620 Highest DNP level supported: Device function: For requests: Level 2+ ○...
Page 82
Only non-time-tagged ○ Binary input change with relative time ● Configurable to send one or the other ● Configurable Sends unsolicited responses: Sends static data in unsolicited responses: ● Never ● Never Table continues on next page REF620 Point List Manual...
(non-change-event) objects, requests sent with qualifiers 00, 01, 06, 07 or 08 are responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 are responded with qualifiers 17 or 28. For change-event objects, qualifiers 17 or 28 are always responded. REF620 Point List Manual...
Page 84
17, 28 (index) 32-bit 1 (read) 00, 01 (start-stop) 129 (response) 00, 01 (start-stop) analog 06 (no range, or all) 17, 28 (index) input 07, 08 (limited qty) 17, 28 (index) Table continues on next page REF620 Point List Manual...
Page 85
Time and 129 (response) 07 (limited qty) date CTO 130 (unsol. resp) (qty = 1) Unsynchro 129 (response) 07 (limited qty) nized time 130 (unsol. resp) (qty = 1) and date Table continues on next page REF620 Point List Manual...
Page 86
17 or 28 are always responded.) 3) Writes of internal indications are only supported for index 7 (Restart IIN1-7) 4) Cold and warm restarts return an application layer acknowledge, but no restart action is taken. REF620 Point List Manual...
International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling Intelligent electronic device IET600 Integrated Engineering Toolbox in PCM600 LHMI Local human-machine interface PCM600 Protection and Control IED Manager Select-before-operate WHMI Web human-machine interface REF620 Point List Manual...
Page 92
Contact us ABB Oy Medium Voltage Products, Distribution Automation P.O. Box 699 FI-65101 VAASA, Finland Phone +358 10 22 11 +358 10 22 41094 www.abb.com/substationautomation...