5.9.2 Update USB downloaded content Manual Acquisition This manual is only available in PDF format. Users can log into the Kinco official website (https://en.kinco.cn/) and going to "Services -> Download" to search for keywords and download the document. Programming Software Acquisition PLC programming software ——...
Kinco will not be liable for any legal responsibility arising from personal safety accidents or property losses caused by non-compliance with the content of this manual To ensure the safe use of the product, this manual uses the following symbols and graphics to indicate precautions and highlights safety-related important content.
Page 4
MK series integrated(PLC+HMI) user manual When Power is Supplied During power supply, do not touch any terminals or terminal blocks, and do not attempt to disassemble any units. Especially during power supply or just after power is turned off, capacitors need time to discharge, which may cause electric shock or other personal or equipment hazards.
Page 5
MK series integrated(PLC+HMI) user manual due to electromagnetic noise. For applications with severe interference, use special shielded cables for high-frequency signal input or output to improve the system's anti-interference capability. During System Design When applying, it is essential to design a safety circuit to ensure that the control system remains safe even in the event of a power failure or controller malfunction.
2.2.12 MK series product wiring summary ....................34 2.2.13 MK series product dimension ......................39 3 Installation guideline ..............................41 3.1 MK series product connect expansion module ....................41 3.2 Dis/Assembly of terminal blocks ........................42 3.2.1 Disassembly of terminal blocks ......................42 3.2.2 Assembly of terminal blocks .........................
Page 7
4.5.1 Compiler ..............................51 4.5.2 Simulator ..............................52 4.6 Connection and program up/download ......................54 4.6.1 MK series PLC communicate with PC via USB-Slave ................ 54 4.6.2 Program upload/download ........................55 4.7 Error message and solution ..........................57 4.7.1 Error Message in KincoBulider ......................57 4.7.2 Common Error ............................57...
Page 8
MK series integrated(PLC+HMI) user manual 7.1 Fast selection list ...............................93...
Module type + Number of channels + function identification , as shown in figure: In the MK series, except the MK070E-32DX body has no analog,other models body have analog input / output. In addition, the MK043E-27DT body has a 4-channel DIO, which can be used as a drain type DI input or...
MK series integrated(PLC+HMI) user manual According to the above principles, MK070E - 33DT stands for the DC 24 V power supply, the total input/output channels is 33 (16*DI , 14*DO , 2*AI , 1*AO) of 7 inch integrated machine; MK043E-20DT stands for the DC 24 V power supply, the total input/output channels is20 (9*DI , 9*DO , 2*AI) of 4.3 inch integrated machine.
MK series integrated(PLC+HMI) user manual 1.3 Operating and Storage Conditions The MK series products complies with the GB/T 15969.3-2007 (equivalent to IEC61131-2:2007) standard and testing specifications. Transportation and Storage Temperature -40℃~+70℃ Relative humidity 10%~95%,non-condensing Environmental conditions Atmospheric pressure Altitude of 0~3000 meters above sea level...
MK series integrated(PLC+HMI) user manual 1.4 Product List Standard product MK070E-33DT MK070E-32DX MK043E-20DT Power supply DC24V(Range:DC 20.4V-DC 28.8V) 16*DC24V(PNP/NPN) 16*DC24V(PNP/NPN) 9*DC24V(PNP/NPN) 4*DC24V(PNP) DI/DO 14*DC24V(PNP) 9*DC24V(PNP) 12*Relay 2*AI 2*AI Support 0-10V signal AI/AO 1*AO Programmatic USB-Slave/RS485(Port1) interface Interface 1*CAN,support CAN free communication...
Page 13
MK series integrated(PLC+HMI) user manual Standard product MK070E-27DRT MK043E-20DTC MK043E-27DT Power supply DC24V(Range:DC 20.4V-DC 28.8V) 12*DC24V(PNP/NPN) 9*DC24V(PNP/NPN) 10*DC24V(PNP/NPN) 12*Relay 9*DC24V(PNP) 10*DC24V(PNP) DI/DO 4*DC24V Change the input/output function of each channel according to the wiring, can be mixed 3*RD Support Pt100 thermal...
MK series integrated(PLC+HMI) user manual Economy product MK070C-33DT MK043C-20DT Power supply DC24V(Range:DC 20.4V-DC 28.8V) 16*DC24V(PNP/NPN) 9*DC24V(PNP/NPN) DI/DO 14*DC24V(PNP) 9*DC24V(PNP) 2*AI 2*AI Support 0-10V signal AI/AO 1*AO Programmatic USB-Slave/RS485(Port1) interface Interface Not supported Serial 1*RS485(Port1) communication Expansion module Not supported Screen size 7"TFT...
Page 15
An RS232 serial port has been added to the display section for direct data exchange with external devices MK series support a variety of expansion modules, standard product can expand 8 KS expansion modules, meeting users' various application needs and offering higher cost-effectiveness.
MK series integrated(PLC+HMI) user manual 2.2 Component and interface description 2.2.1 MK070E component description Note: MK070E-33DT/MK070E-32DX/MK070E-27DRT components are the same, only the total number of input and output points are different Name Function ① Display and touch LCD screen Display and touch area ②...
MK series integrated(PLC+HMI) user manual HMI expansion interface for peripheral devices such as storage ⑨ USB Host interface devices, keyboards, or mouse ⑩ PLC program clears physical key CLR button For Ethernet communication connection, can connect to PC to ⑪...
MK series integrated(PLC+HMI) user manual HMI expansion interface for peripheral devices such as storage USB Host interface ⑦ devices, keyboards, or mouse ⑧ CLR button PLC program clears physical key For Ethernet communication connection, can connect to PC to ⑨...
MK series integrated(PLC+HMI) user manual Used for connecting analog input signal, the wiring is fastened ⑦ Analog input channel terminal with screws, and the terminals are detachable ⑧ Supports 2*RS485 (Port1, Port2) and KS extension DB9 interface HMI expansion interface for peripheral devices such as storage ⑨...
According to the user's usage and feedback, the panel indicator light has been updated twice, and the differences before and after the update will be explained below. There are three types of indicator lights on the MK series panel: PWR, RUN, and STA, which are used to indicate the current operation status of MK.
Page 21
MK series integrated(PLC+HMI) user manual Error type Err. Description When a fatal error occurs, the PLC will immediately exit the normal scanning state, and according to the value of the special register SM2.0 to determine whether to directly reset the PLC or enter the independent security subsystem operation: If the SM2.0 = 0, the PLC will enter the independent...
Page 22
MK series integrated(PLC+HMI) user manual The CPU has two main states:Run and Stop. In the running state, the CPU module executes the main scanning task and various interrupt tasks in a normal cycle. In the stopped state, the CPU module only processes some...
MK series integrated(PLC+HMI) user manual 2.2.6 MK back interface and pin description 2.2.6.1 DB9 interface The DB9 interface behind the MK provides 2*RS485 (Port1, Port2) communication, both support ModbusRTU master/slave station, free communication function, of which Port1 can be connected to download programs. EX.
Page 24
Ground 2.2.6.3 EtherNet interface The MK series CPU modul is equipped with a 10/100M Ethernet port (in accordance with the IEEE802.3 standard specification), in the form of RJ45. Users can access the external network or other Ethernet device, the interface supports programming protocols, can download the HMI configuration program...
Page 25
MK series integrated(PLC+HMI) user manual 2.2.6.4 USB-Slave (USB-B&Type-C) USB-Slave is the PLC, HMI general program download interface, in the MK series only MK043E-27DT USB-Slave uses the Type-C interface, the use of mobile phone data cable can be connected to download programs, other MK models use USB-B interface.
2.2.6.5 Anti-demolition warranty label There is an anti-demolition warranty label on the side of the MK series plc, which is the main basis for users and maintenance personnel to confirm whether the product is dismantled. If the user destroys the anti-demolition warranty label, it will be regarded as artificial damage, so it is not within the scope of warranty.
Page 27
MK series integrated(PLC+HMI) user manual Figure 2.2.7-1 Data maintain setting Permanent storage refers to a designated area in the CPU's non-volatile memory (E2PROM) .The data stored in this area will not be lost even when power is disconnected. However,the E2PROM has limitations in terms of lifespan and write speed, so frequent or rapid writesshould be avoided.
Page 28
MK series integrated(PLC+HMI) user manual 2.2.7.2 Real-time clock The MK series PLC integrates a real-time clock (RTC), providing real-time time/calendardisplay. The format of the real-time clock/calendar (year/month/day, hour/minute/second) is encoded in BCD format, automatically adjusting for leap years. When the CPU is powered off, the real-time clock relies on backup battery power to maintain operation.
Page 29
Backup battery The MK series CPU uses a specific specification lithium battery as the backup battery. When CPU is power off, the backup battery is used to power the real-time clock to maintain its operation and also powers the RAM to retain data.
Page 30
Please follow local waste disposal and recycling regulations for proper disposal of the old lithium battery. 2.2.7.3 High speed counting function The MK series CPU support 4 high-speed pulse counters.numbered HSC0 to HSC3, covering single-phase /two-phase (UP/Down)/AB (1 multiple frequency and 4 multiple frequency) equal counting modes. The maximum...
Page 31
2.2.7.4 High pulse speed output function MK series PLC supports 4 high-speed pulse output channels, namely Q0.0, Q0.1, Q0.4, Q0.5, all channels support PTO (pulse string, pulse + direction) and PWM output. At the same time, the software provides PLS (PWM or PTO), positioning control instruction group, PFLO_F (follow instruction), etc., which is convenient for users to...
2.2.7.5 Interrupt function MK series PLC body input point I0.0 ~ I0.3 support edge interrupt function, can use the input signal rising edge and falling edge to generate interrupt. This feature is fast enough to capture the rising or falling edge of the input, and to achieve a fast response to some input signals whose pulse width is less than the CPU scan cycle.
Page 33
MK series integrated(PLC+HMI) user manual 2.2.8.3 DO( Transistor ) Input type Rated output voltage DC24V,allowance range: DC20.4V~DC28.8V Output current / channel Rated 200mA@24VDC Inrush transient current/channel 1A,≤1s Output leakage current Max: 0.5μA Output impedance Max: 0.2Ω Turn-on delay: common channel 15μs, high-speed channel 10μs (50K) Output delay time Turn-off delay: common channel 35μs, high speed channel 6μs (50K)
Page 34
MK series integrated(PLC+HMI) user manual 2.2.8.7 Communication interface 1 channel, support HMI configuration program up/download, connect KDManager Ethernet firmware upgrade 2 channel RS485,isolation Baud rate range:1200bps~115200bps PORT1 supports programming protocol, Modbus RTU master/slave station, and free communication 1 channel CAN,8 KS expansion modules can be connected 2.2.8.8 Program storage and RTC...
1M , it is referred to as NPN input; when the signal flows out from the (1M), it is referred to as PNP input. In the diagram, solid lines represent external wiring for PNP input, while dashed lines represent external wiring for NPN input.This wiring diagram applies to all MK series input wiring Meaning Meaning 24V DC +(Source type)...
Page 36
L- is connected to the DC 24V-,L+ is connected to the DC 24V+, and the signal is connected to the external load. This diagram applies to all MK series transistor type output wiring except MK070E-32DX and MK070E-27DRT.
MK series integrated(PLC+HMI) user manual 2.2.10.4 DIO wiring diagram Figure 2.2.10-4 DIO wiring diagram The figure above is DIO wiring diagram. Only the MK043E-27DT provides 4 channels of DIO, and each channel can be used independently as DI or DO according to the connection method. The dashed line is the NPN drain output and the solid line is the PNP source input.
MK series integrated(PLC+HMI) user manual 4-wire / 2-wire current input 2 wire 4 wire transmitter transmitter Figure 2.2.11-1 2-wire / 4-wire current input wiring diagram Current signal corresponding to access pin * + and R * (* indicate channel name: A/B/C/D), Taking the 2-wire current input A group as an example, signal + end of the transmitter needs to be connected to the sampling resistance "B+"...
Page 39
MK series integrated(PLC+HMI) user manual Figure 2.2.11-3 voltage input wiring diagram MK043E-20DT Thermal resistance input The MK070E-27DRT has 3 thermal resistance input channels (3*RD), each input channel consists of 3 terminals, named X1, X2, X3, (X is the channel name: A/B/C/D, take channel A as an example, the three terminals are A1, A2, A3), support Pt100 thermal resistor, 2-wire and 3-wire heating resistor.
Page 40
MK series integrated(PLC+HMI) user manual the module will automatically send a fault message to the CPU module through the expansion bus. The following table is the measurement range and measurement value format. I : input current value V : input voltage value.
Page 41
MK series integrated(PLC+HMI) user manual -100~400℃ T×10(-1000~4000) 2.2.11.2 AO wiring diagram Current/Voltage output The MK070E-33DT and MK043E-27DT have 1 current/voltage output channel, and each channel consists of I, V, and M. For the configuration method, see 4.3.2 KincoBuilder configuration extension module.
I : actual current value V : actual voltage value. Signal type Output range Output value specified in the user program 4~20mA 3.92~20.4mA I×1000(3920~20400) 0~20mA 0~20.4mA I×1000(0~20400) 1~5V 0.96~5.1V V×1000(960~5100) 0~10V 0~10.2V V×1000(0~10200) 2.2.12 MK series product wiring summary Figure 2.2.12-1 MK043E-20DTC wiring diagram Figure 2.2.12-2 MK043E-20DT wiring diagram...
Page 43
MK series integrated(PLC+HMI) user manual Figure 2.2.12-3 MK043E-27DT wiring diagram...
Page 44
MK series integrated(PLC+HMI) user manual Figure 2.2.12-4 MK070E-27DRT wiring diagram Figure 2.2.12-5 MK070E-32DX wiring diagram...
Page 45
MK series integrated(PLC+HMI) user manual Figure 2.2.12-6 MK070E-33DT wiring diagram...
Page 46
MK series integrated(PLC+HMI) user manual Figure 2.2.12-7 MK070C-33DT wiring diagram...
3.1 MK series product connect expansion module The standard MK series product support up to 8 KS expansion modules. CAN communication protocol is used between the MK and the expansion module. However, the CAN communication physical interface and two RS485 communication physical interfaces of the MK are placed in the DB9 connector.
MK series integrated(PLC+HMI) user manual 3.2 Dis/Assembly of terminal blocks 3.2.1 Disassembly of terminal blocks Hold the protruding parts on both sides of the top of the terminal block, and apply vertical force to pull out the terminal block. Figure 3.2.1-1 MK terminal block Figure 3.2.1-2 MK terminal block disassembly operation diagram...
3.3 Installation method The packaging box of the MK series product contains a sealed pocket with fixed accessories, which contains 4 installation buckles and screws. The MK070E has square mounting slots on the upper, lower, left and right sides. In the KincoDTools software, MK supports editing the configuration screen in a vertical or horizontal posture.
Page 52
MK series integrated(PLC+HMI) user manual Figure 3.3-4 Install the fixed accessories on the upper and lower sides Figure 3.3-5 Install the fixed accessories on the left and right sides The installation steps are as follows: Place the MK into the installation holes on the device control panel, and clamp the installation buckle hook into the square installation slots on the upper and lower sides or left and right sides as needed.
MK series integrated(PLC+HMI) user manual 4 Getting started with Kinco Builder KincoBuilder is a programming software for Kinco K-series PLC, compliant with the lEC61131-3 standard, enabling users to carry out efficient program development. Here is a brief getting started guide to assist users in quickly getting acquainted with KincoBuilder.
MK series integrated(PLC+HMI) user manual KincoBuilder has organized some commonly used functions into sections on the toolbar for user convenience. Hovering the mouse pointer over the corresponding icons allows to view brief descriptions of the functions and their corresponding shortcut key operations. For more detailed information, please refer to the relevant application manual.
MK series integrated(PLC+HMI) user manual 4.3 Hardware configuration 4.3.1 Configure the CPU After a new project is created, the program will set the CPU to K606-24DT by default. The user needs to modify the CPU according to the actual hardware model. The default configuration model of the new project can also be opened by [Tools]→[Options] on the menu bar.
MK series integrated(PLC+HMI) user manual I/O , Comm,Reten, CANop , and more can be performed on the Hardware interface. For more detailed configuration tutorials, please refer to the software user manual. Figure 4.3.1-4 MK070E-33DT configuration interface 4.3.2 Configure the expansion module After the correct connection of the expansion module , its expansion function needs to be configured through KincoBuilder software before it can be really used.
MK series integrated(PLC+HMI) user manual If you need to set the expansion module, click the corresponding module model to open the related setting interface. Figure 4.3.2-2 Enpansion module configuration Note: In KincoBuilder, the configuration order of expansion modules must match the actual hardware connection sequence.
MK series integrated(PLC+HMI) user manual Figure 4.4.1-2 KincoBuilder help interface 4.4.2 Programming language KincoBuilder supports programming using IL (Instruction List) language and LD (Ladder Diagram) language. You can switch between these languages in the software by accessing the toolbar and selecting [Project].
Steps website. Product version iterations may lead to some lag in both the software and its user manual. Please ensure to download the latest version of the software and the corresponding user manual from the official website promptly. (https://en.kinco.cn/download/plc87.html) 4.5 Compiler and Simulator 4.5.1 Compiler...
MK series integrated(PLC+HMI) user manual Figure 4.5.1-1 Compile path 4.5.2 Simulator In KincoBuilder, an offline simulator for KPLC is provided, supporting simulation of actual program execution and debugging of user programs while offline. The simulator offers practical debugging features such as breakpoints, single-step execution, single-network execution, pause/resume operation, and serial communication simulation.
Page 61
MK series integrated(PLC+HMI) user manual Figure 4.5.2-2 Simulator interface Item Description Toggle monitoring mode Click to enter or exit monitoring mode ① Click to enter offline simulation mode. Enter/Exit simulation mode ② Click to exit offline simulation mode. Restart the simulation.
MK series integrated(PLC+HMI) user manual 4.6 Connection and program up/download 4.6.1 MK series PLC communicate with PC via USB-Slave User need to use a USB-B programming cable to connect the PC and MK . The DB9 port on the back of the MK has two RS485 ports, and only Port1 supports the programming protocol and power on the PLC.
MK series integrated(PLC+HMI) user manual 4.6.2 Program upload/download KincoBuilder provides two ways to upload the program: [Upload] and [Upload (breakpoint resume)...]. Breakpoint transfer refers to the ability to resume transmission from the point where it was interrupted or failed during the file transfer process. This way allows file transfers to be completed efficiently even if the network is unstable or the transfer process is interrupted.
Page 64
MK series integrated(PLC+HMI) user manual KincoBuilder offers two methods of program downloading: [Download] and [Download (breakpoint resume)...]. Similarly(refer to Program Upload), when the program download process is frequently interrupted, the network is busy, long-distance transmission is required, or for large project sizes, it is recommended to use [Download (breakpoint resume)...] for downloading programs.
MK series integrated(PLC+HMI) user manual Option Description Enabling this option will encrypt and store all user programs in the PLC, and "Upload program" Set the CPU to “ Upload Disabled” will not be supported. Please be careful when enabling this option and take care of program backup...
Kinco website, while PLC firmware can be obtained by contacting Kinco's technical support or local service centers. If you need more detailed explanations of error codes, please open the Online Help or download the "Kinco-K Series Application Manual" from the official website.
Page 67
Figure 4.8-3 Help document description The steps for updating the firmware of MK series PLC using the USB-Slave are as follows: 1. Use the USB-B cable to connect the PLC to the PC via USB port and power up the PLC.
Page 68
PLC can be connected but cannot enter the update mode, try power off the PLC for a while before update again. If firmware update still cannot be performed, please check the [Run] light, battery level, and firmware version, and then contact Kinco Technology Support or local agents for assistance...
5 Getting started with KincoDTools KincoDTools configuration editing software is a special human-machine interface configuration editing software developed by Kinco for Green series and Future HMI. The software installation process and configuration requirements are omitted here. This document only provides brief operations to get you started. For details about how to use KincoDTools, see 5.4.2 KincoDTools User Manual.
Component library window ④ HMI page:Contains all HMI models of Kinco PLC page:Support other manufacturers PLC equipment except Kinco Details of the relevant connection settings can be found in [Communication Connection Help (C)] in the menu bar [Help (H)]. Device topology window Display the topology connection screen of the added devices.
Page 71
MK series integrated(PLC+HMI) user manual by directly clicking the [New Project] button on the toolbar Figure 5.1-3 Create new file Then in the pop-up [New project] dialog box set the project name, select the project save location, HMI series and HMI model, here to create a project name of "Test_1" MK070E project as an example.
Page 72
MK series integrated(PLC+HMI) user manual Figure 5.1-5 Set the project name “Test_1” Figure 5.1-6 Change the project path In the KincoDTools software, the MKseries can edit the configuration screen in a vertical or horizontal attitude. User can select horizontal or vertical in the Display mode. If this parameter is incorrect, you can modify it after the project is created.
MK series integrated(PLC+HMI) user manual Figure 5.1-8 Set HMI model After setting, click [Next >>] to complete the project creation. 5.2 KincoDTools system parameters set After the project is created, the system parameters set page is displayed. On the page, you can change the HMI...
IP Address: The modification here is the IP address of the HMI device which selected for the Device NO. Comm Protocol:The default is Kinco communication protocol. If users need to connect other devices, they can select the protocol of the corresponding manufacturer from the list called by the [▼]...
Page 75
Figure 5.2-4 IP adress setting Serial port setting Serial port 0 parameter setting is an important action to connect the MK series PLC and HMI . Click [COM0], select the manufacturer [Kinco], select the communication protocol [Kinco PLC Series], click [Add] after selecting,...
MK series integrated(PLC+HMI) user manual 5.3 Startup menu Hold pressing on the touch panel when you power on HMI, then HMI will enter operation mode selection window, select the operation mode according to your application.The following function buttons are displayed on the startup menu: System setup:Press this button to enter system setup window.
MK series integrated(PLC+HMI) user manual After successfully entering the HMI Edit window, you will see the following interface: Figure 5.4-2 HMI Edit interface Num. Project Description Toolbar The Toolbar contains some frequently used operational commands. ① There are three pages of PLC Parts, Functional Parts and Project database.
MK series integrated(PLC+HMI) user manual Figure 5.4-3 Open user manual 5.4.3 Add component KincoDTools has two ways to add components: (1) Click [Components(I)] on the menu bar, hover the mouse over the component category to find the desired component, and click Add;...
Page 80
MK series integrated(PLC+HMI) user manual Figure 5.4-5 Add library method After adding the component, a component property setting window will pop up. There are multiple subpages in the component property setting window for setting. We take the example of creating a startup button with address M0.0.
Page 81
MK series integrated(PLC+HMI) user manual Figure 5.4-6 Set element adress type Figure 5.4-7 Set Switch type and Tag Figure 5.4-8 Set Graphics After the setting is complete, click [OK] to complete the button creation. If you want to modify the setting after...
MK series integrated(PLC+HMI) user manual Figure 5.4-9 Successfully created bit state switch 5.4.4 Add frame KincoDTools allows to create up to 32768 frame, which are numbered from 0 to 32767 and displayed as [Window number: Window name] in the project tree view. Users can click the menu bar [Screen (P)], click [Add Frame (N)], set the window information in the new window property page to add.
MK series integrated(PLC+HMI) user manual Figure 5.4-11 Add new frame successfully 5.5 Macro 5.5.1 Create macro file If the components provided by the component window attribute cannot meet the specific needs of users, it can be realized by creating macro code in C language. Click [Macromode... (M)] in the menu bar [Lib (L)], set the macro file name and corresponding group number to create macro file.
MK series integrated(PLC+HMI) user manual 5.5.2 Add variable Click the right mouse button in the [Parameters] window, click [Add Variable], set the variable name, data type, variable address and R/W properties, click [OK] to create a variable. Figure 5.5-3 Create variable Figure 5.5-4 Add variable successfully...
Page 85
MK series integrated(PLC+HMI) user manual Figure 5.5-5 Add variable successfully Users can choose to use timer or function key buttons to execute macro code, and can find them on the [Function Parts] page in the [Graph element window].The difference between the two is that the timer element is triggered without button, and the macro code is executed when the execution conditions are met.
MK series integrated(PLC+HMI) user manual Figure 5.5-7 Set Function key 5.6 Offline Simulation After completing the editing of the engineering configuration, it needs to be compiled before it can be downloaded and simulated. "Offline Simulation" function can simulate the effect of the engineering configuration runningand without connecting to the MK, eliminating download the engineering to the MK for verification every time changes are made, greatly improving programming efficiency.
MK series integrated(PLC+HMI) user manual Figure 5.6-1 Creat simulation Figure 5.6-2 Simulation button Figure 5.6-3 Offline simulation operation effect 5.7 Special register function HMI provides special registers to complete specific functions, tick [System Register] on the component attribute page, then click [▼] at the end of the address type , open the address detailed Info page to view, select and...
Figure 5.7-1 Set the system register 5.8 IOT function MK series supports the IOT function, users can see the current supported IOT implementation method in the menu bar [IOT (I)]. For detail , see KincoDTools user manual Chapter 17 .
Page 89
MK series integrated(PLC+HMI) user manual [Compile All (R)] on the menu bar, the Meaaage window displays the editing result is complete, click [Download (D)], in the pop-up download setting dialog box to confirm whether the current communication mode is correct, user can click [Set] to modify the communication mode.
Page 90
MK series integrated(PLC+HMI) user manual Figure 5.9-3 Compiler result Figure 5.9-4 Communication Set Figure 5.9-5 Select Section Name Description Data file Download project files in .pkg , .pkgx format Recipe file Download recipe files in .rep fommat Logo file Download Initial Start Window in *.bmp/*.jpg/*.gif/*.logo format...
MK series integrated(PLC+HMI) user manual Clear history event data Clear the record in [Event Display】/ [Historical Event Display】 parts Clear history record data Clear the record in [Historical Event Display】 / 【 Trend Curve】 / 【 Tend Curve】 parts Clear data report Clear data saved in 【Data Report】...
Page 92
MK series integrated(PLC+HMI) user manual Project Description After this option is checked, all user programs stored by the PLC will The currenty downloaded user project is be encrypted and stored in ciphertext, and the "upload" operation is not prohibited from uploading supported.
MK series integrated(PLC+HMI) user manual Figure 5.9-9 Input password 5.10 KDManger KDManager is an auxiliary software for HMI project upload, download and decompile, HMI firmware update, and obtain HMI system information. It contains 8 processing modules: [Download Operate], [Upload Operate],...
MK series integrated(PLC+HMI) user manual Figure 5.10-2 Communication Set interface 5.10.1 Download/Upload Operate After saving the configuration screen edited by KincoDTools,. dpj format file is generated. After compilation, the. pkg , .pkgx file required for HMI is generated . Click[Download User Data] and find the.pkg or . pkgx files in the project file saving path, and click [Open] to enter the download page.
MK series integrated(PLC+HMI) user manual Figure 5.10-4 Download Operate step2 5.10.2 System Operate Figure 5.10-5 System Operate interface Name Description GetHMI IP/PORT information Obtain the IP address and port number of the current HMI WiFi, LAN0, and LAN1 Scan out the currently available WiFl, and set to select the network to be...
MK series integrated(PLC+HMI) user manual Return Set Application Status HMI changes to the embedded SETUP interface To update the HMI kernel and file system,user need to use this function under the guidance of the manufacturer. Before updating the firmware, Write Firmware...
MK series integrated(PLC+HMI) user manual 5.10.4 Decompile Operate Decompile operate can reverse compile the.pkgx file in the MK to generate a project folder and save it on the computer, and then open KincoDTools for editing. Operation steps: 1. Select the target .pkg , .pkgx files to be decompiled 2.
MK series integrated(PLC+HMI) user manual Figure 5.10-10 Decompiler successfully 5.10.5 Decrypt Operation KincoDTools supports data encryption components: trend chart components, XY chart components, and historical data display components. These components continuously collect data during operation, and the collected data (historical data) can be optionally generated into CSV format files and saved to the recipe data area or external storage devices.
MK series integrated(PLC+HMI) user manual 1. If the encrypted file is changed manually, KDManager [Decrypte Historic Data File] will prompt an error, informing the user that the source file is damaged 2. After [Decrypte Historic Data File] is performed by KDManager, you can only open and view, but cannot modify and edit CSV files or PDF files 5.10.6 Through communication method...
If you have any questions about the products described in this manual, please contact the local offices and agents of Kinco. For information regarding user training and other matters, please visit the company's website or contact local agents for training plans.
MK series integrated(PLC+HMI) user manual 7 Appendix 7.1 Fast selection list Standard type MK070E-33DT MK070E-32DX MK043E-20DT 16*DC24V 16*DC24V 9*DC24V 4*DC24V Switch value 14*DC24V 9*DC24V 12*Relay 2*A I(support 0-10V 2*AI signal) Analog value 1*AO USB-B √ √ √ Download Type-C ×...
Page 102
MK series integrated(PLC+HMI) user manual Standard type MK070E-27DRT MK043E-20DTC MK043E-27DT 12*DC24V 9*DC24V 10*DC24V Switch value 12*Relay 9*DC24V 10*DC24V 4*DC24V 3*RD Support Pt100 2*TC thermoelectric Support J/K/E/T 2*AI Analog value resistance, temperature thermocouples range -40℃ ~ 240 ℃ 1*AO USB-B √...
Page 103
MK series integrated(PLC+HMI) user manual Economic type MK070C-33DT MK043C-20DT 16*DC24V 9*DC24V Switch value 14*Relay 9*DC24V 2*AI 2*AI Support 0-10V signal Analog value 1*AO USB-B √ √ Download interface Type-C × × RS485(Port1) √ √ × × Communication RS485 RS232 ×...