Roger MCT80M Installation Manual

Access control system
Hide thumbs Also See for MCT80M:

Advertisement

Quick Links

Roger Access Control System
MCT80M / MCT82M /
MCT84M Reader
Installation Manual
Firmware version: x.1.30.266 and newer
Document version: Rev. F
This document contains minimum information that is necessary for
initial setup and installation of the device. The detailed description of
configuration parameters and functionalities is specified in respective
Operating Manual available at www.roger.pl.
1. I
NTRODUCTION
The reader is designed for operation with MC16 access controller
(RACS 5 system). Factory new reader is configured with default
settings including ID=100 address.
2. D
C
EVICE
ONFIGURATION
The reader can be configured in regard of various parameters
(including address) in order to adapt it to the requirements of specific
installation. Device can be configured from VISO v2 management
software or RogerVDM utility software.
Note: Remote configuration of device from VISO v2 software is possible
only if jumper is placed on MEM contacts (fig. 4). If the jumper is
removed then such configuration is blocked. In case of factory new
device, jumper is placed on MEM contacts.
C
ONFIGURATION WITH
In RACS 5 v2 system the reader can be installed at site without
previous configuration. According to AN006 application note, its
address and other settings can be configured from VISO v2
management software and during such configuration the access to its
service contacts (fig. 4) is not required.
C
ONFIGURATION WITH
Fig. 1 Connection of MCT reader to RUD-1 interface (configuration)
Programming procedure:
1. Connect the device to RUD-1 interface (fig. 1) and connect the RUD-
1 to computer's USB port.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST
contacts for a moment) and orange LED SYSTEM will pulsate. Then
within 5 seconds place jumper on MEM contacts.
4. Start RogerVDM program, select MCT device, firmware version,
RS485 communication channel and serial port with RUD-1 interface.
5. Click Connect, the program will establish connection and will
automatically display Configuration tab.
6. Enter unoccupied RS485 address in range of 100-115 and other
settings according to requirements of specific installation.
7. Click Send to Device to update the configuration of device.
8. Optionally make a backup by clicking Send to File... and saving
settings to file on disk.
9. Disconnect from RUD-1 interface and leave jumper on MEM contacts
to enable further configuration of device from VISO v2 software or
Roger sp. z o.o. sp. k.
V
2 P
ISO V
ROGRAM
R
VDM P
OGER
ROGRAM
remove
jumper
from
MEM
configuration.
Note: Do not read any cards nor press reader keypad when reader is configured
with RogerVDM.
M
ANUAL ADDRESSING
Manual addressing procedure enables configuration of new RS485
address with all other settings unchanged.
Manual addressing procedure:
1. Remove all connections from A and B lines.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST
contacts for a moment) and orange LED SYSTEM will pulsate. Then
within 5 seconds place jumper on MEM contacts.
4. Enter 3 digits of RS485 address in range of 100-115 with keypad or
with any MIFARE card.
5. Leave jumper on MEM contacts to enable further configuration of
device from VISO v2 software or remove jumper from MEM contacts
to block such remote configuration.
6. Restart the device.
Readers without keypad can be addressed with multiple card readings
where the N number of readings emulates digit of the address. Three
series of readings with any MIFARE proximity card are necessary to set
the address. After each series wait for two beeps and proceed with the
next digit. Zero digit is emulated with 10 readings.
Example:
Programming of ID=101 address with card readings:
1. Read card 1 time and wait for two beeps.
2. Read card 10 times and wait for two beeps.
3. Read card 1 time and wait for two beeps.
4. Wait till reader is restarted with the new address.
M
EMORY RESET
Memory reset procedure resets all settings to factory default ones
including ID=100 address.
Memory reset procedure:
1. Remove all connections from A and B lines.
2. Remove jumper from MEM contacts (fig. 4) if it is placed there.
3. Restart the device (switch power supply off and on or short RST
contacts for a moment) and orange LED SYSTEM will pulsate. Then
within 5 seconds place jumper on MEM contacts.
4. Press [*] or read any MIFARE card 11 times.
5. Wait till device confirms reset with long acoustic signal.
6. Leave jumper on MEM contacts to enable further configuration of
device from VISO v2 software or remove jumper from MEM contacts
to block such remote configuration.
7. Restart the device.
F
U
IRMWARE
PDATE
The firmware of device can be changed to newer or older version. The
update requires connection to computer with RUD-1 interface (fig. 2)
and starting RogerVDM software. The latest firmware file is available
at www.roger.pl.
Firmware update procedure:
1. Connect the device to RUD-1 interface (fig. 2) and connect the RUD-
1 to computer's USB port.
2. Place jumper on FDM contacts (fig. 4).
3. Restart the device (switch power supply off and on or short RST
contacts for a moment).
4. Start RogerVDM program and in the top menu select Tools and then
Update firmware.
5. In the opened window select device type, serial port with RUD-1
interface and path to main firmware file (*.hex) and in case of device
with keypad also path to additional firmware file (*.cyacd).
6. Click Update to start firmware upload with progress bar in the
bottom.
7. When the update is finished, disconnect from RUD-1 interface and
remove jumper from FDM contacts. Additionally it is recommended
to start memory reset procedure.
contacts
to
block
such
remote
Strona 1 z 4

Advertisement

loading
Need help?

Need help?

Do you have a question about the MCT80M and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Roger MCT80M

  • Page 1 8. Optionally make a backup by clicking Send to File… and saving settings to file on disk. 9. Disconnect from RUD-1 interface and leave jumper on MEM contacts to enable further configuration of device from VISO v2 software or Roger sp. z o.o. sp. k. Strona 1 z 4...
  • Page 2 Installation guideliness • The terminal should be mounted on a vertical structure (wall) away from sources of heat and moisture. Roger sp. z o.o. sp. k. Strona 2 z 4...
  • Page 3 MCT80M: ~100g MCT82M series: ~100g MCT84M series: ~100g Certificates CE, RoHS Manufacturer's warranty 36 months Fig. 8 Connection of readers and expanders to MC16 access controller Fig. 7 MCT84M installation Roger sp. z o.o. sp. k. Strona 3 z 4...
  • Page 4 MCT84M published on the website www.roger.pl Portable USB-RS485 communication interface RUD-1 dedicated to ROGER access control devices Contact: Roger Sp. z o. o. sp. k. 82-400 Sztum Table 9. Product history Gościszewo 59 Date Description Version Tel.: +48 55 272 0132...