Vertical Vent Through Roof; Vertical Vent Restrictions - Kenmore 33205 - Power Vent, 50 Gallon Owner's Manual

Power vented gas models with hot surface ignition, for potable water heating only, not suitable for space heating, not for use in mobile homes, 40/50 gallon natural
Table of Contents

Advertisement

Minimum 3 ft. (91 cm)
Minimum 3 ft. (91 cm) within a
height of 15 ft. (4.6 m) above
a12o_/_ (30_n) r
meter/regulator assembly
Minimum
expected snowfall J
12 in. (30 cm)
r'_
to side or
_
Minimum 3 ft. ( 91 cm ) clearance
from soffit'_---_L ' _
12 in. (30 cm)
_ _
,
/to service regulator vent outlet
l-k_
ibovedoor
_\_,,._
/
__7_
/_
Minimum\
_
_
/ li
imul ,
[_.
_....._
Minimum 12 in. (30 cm)
7 ft. (2.3 m) _.
_ I
_
_k,_
/2 ft. (61 cml
["--
I
I under veranda, porch,
above "
_"_' I
L J._
//from outsiae
__XI
/
I
I
I
.deck or balcony
public sidewalk
I I
r_r "Ix _
/
corner
___
kX_k_
/
I
I
_
(seefootnote 1)
orpaved
_
N \1 \ \\
/
/ __
_
_._X,"t /
_
I
(seder_Vetn way
2)
_
i
/
N
_
_
_
_/
_
_'_
Mi'n9r_Umm
ab(_vea )
\
\\
I
I /
Jt
/ L_ 1 CLW_
/
_-[X]
_
_.\X_-_--'_
I%
_/
mechanical air
_XI_.--_
1
/
_,
_E
/ _
_)\
_'_'_
_
_
_
supply inlet
"_'-_.
I
i
__
/
_
L_,
I-
\
_J..._'X_
/
_..--------'-"F-
./I
within l0 ft. (3 m)
i-
"_
/_..__
I..,,..'_--"1
horizontally
12Mi/?lfl_m)
Minimum
4_.
(1.2
m)_'_
_
I--
_
\
_
Minimum 4 ft. (1.2 m)
_°mm_idenSt_yffr_h_¢imdey°bfeWop
d°w
__
Minimum 4 ft. (1.2 m)
MiTAmum4_t_il"2m w) bela_W°rSiode°_J2a_Gc_OCm)
closed window
below a window that
o
s ae o
ao
supply inlet into building
Minimum 12 in. (30 cm) above
may be open
that may be open
or combustion air inlet
window or door that may be open
to another appliance
[] VENT TERMINAL
(_) AIR SUPPLY INLET
[]
AREA WHERE TERMINAL IS NOT PERMITTED
1. Permitted
only if veranda, porch, deck or balcony is fully opened on a minimum of two sides beneath the floor.
2. A vent shall not terminate
above a sidewalk or paved driveway
that is located between two single family dwellings
and serves both dwellings.
FIGURE
23.
This unit can vent through 2", 3" or 4" nonmetallic pipe and fittings.
The vent pipe installation
can be started
from either
the blower
discharge or the termination
wall.
Keep in mind the total vent system
(pipe and elbows) when installing the vent system, see VENTING AND
INSTALLATION AND MAXIMUM VENT LENGTHS, page 17.
MORTAR
OR
SILICONE
CAULK
FROM
WATER
HEATER
PVC
COUPLING
_;t.
i
_; 4.!
'_
°
_
°.
i
WALL
PLATE
(OPTIONAL)
J
PVC VENT
TERMINAL
WITH
MESH
PROTECTIVE
_N
INSIDE
12" MIN.(30.5 cm)
OUTSIDE
OF
L
_1_
BUILDING
WALL
FIGURE 24.
The vent terminal should be kept as close as possible to the outside wall,
but you need to allow at least 1.5" (3.8 cm) of pipe past the wall, for the
wall flange and vent terminal to mount on the pipe.
Before the vent terminal is installed,
caulk (not supplied)
around the
pipe on the exterior wall and install the optional wall flange. The flange
can be held to the outside wall by placing some of the caulking on the
back of the flange. The wall flange is supplied for decorative purposes
only and is not a requirement
for the vent termination
(if not needed by
the installer).
VERTICAL VENT THROUGH ROOF
This unit is approved
for venting through the roof with the type vent
terminal that is included with the unit. A proper flashing or "BOOT" should
be used to seal the pipe where it exits the roof.
The total vent system should not exceed that which is specified,
see
VENTING AND INSTALLATION,
page 17.
VERTICAL
VENT
TERMINATION
RESTRICTIONS
1. Minimum
of twelve 12" (30.5 cm) above the roof or twelve
12"
(30.5 cm) above the anticipated snow level. Provide proper support
for all pipe protruding through the roof.
VENT
TERMINAL
/--ROOF
_0.5
C_R) ABOVEROOF
/
II
MIN°OF 12"(30.5cm)ABOVE
I I
ANTICIPATED
SNOW L EVEL
*ALL
PIPE PROTRUDING
THROUGH
THE ROOF
SHOULD
BE PROPERLY
SUPPORTED.
FIGURE 25.
2. 4' (1.2 m) from or 1' (0.3 m) above any gable, dormer, or other roof
structure with access to interior of building (i.e.-vent, window etc.).
3. 3' (0.9 m) above any forced air inlet located within 10' (3.0 m).
All of the pipe should be secured as per the instructions in the instructions
in the VENTING AND INSTALLATION,
page 17.
20