Venting; Vent Terminal Installation - Kenmore 33205 - Power Vent, 50 Gallon Owner's Manual

Power vented gas models with hot surface ignition, for potable water heating only, not suitable for space heating, not for use in mobile homes, 40/50 gallon natural
Table of Contents

Advertisement

VENTINg;
Breathing
Hazard
- Carbon
Monoxide
Gas
• Install vent system in accordance
with
codes.
• Do not operate water heater if flood
damaged.
• High altitude orifice must be installed for
operation above7,700
feet (2,347 m).
• Do not operate if soot buildup.
• Do not obstruct water heater air intake
with insulating jacket.
• Do not place chemical
vapor emitting
products near water heater.
• Gas and carbon
monoxide
detectors
are available.
• Never operate the heater unless it is
vented to the outdoors and has adequate
air supply to avoid risks of improper
operation, fire, explosion, or asphyxiation.
• Make sure the flue baffle and flue restrictor
ring are properly aligned and inserted on
top of the flue. This can be checked
through the dilution air inlet of the blower
assembly. For viewing, the Air Intake screen
of the blower assembly will have to be
removed. Replace after the check is made.
Breathing carbon monoxide can cause brain damage or death.
Always read and understand instruction manual.
The vent system must terminate so that proper clearances are maintained
as cited in local codes or the current edition of the National Fuel Gas
Code, ANSI Z223.1/NFPA
54, 7.3.4e and 7.8a,b, as follows:
1. The exit terminals
of a mechanical
vent system shall be not less
than 7 feet (2.13 m) above grade when located adjacent to public
walkways, see Figure 23.
2. A venting system shall terminate at least 3 feet (91 cm) above any
forced air inlet located within 10 feet (3.1 m), see Figure 23.
3. The venting system shall terminate at least 4 feet (1.2 m) below, 4 feet
(1.2 m) horizontally from or, 12 in. (30 cm) above any door, window
or gravity air inlet into any building.
The manufacturer
also recommends
that the vent termination
should
not be installed closer than 3 feet (91 cm) from an inside corner of
an L shaped structure and not be less than 12 in. (30 cm) above
grade.
The vent shall terminate a minimum of 12" (30.5 cm) above expected
snowfall level to prevent blockage of vent termination,
see Figure
23.
4. In cold climates,
it is recommended
that vent termination
not be
mounted directly above or within 3 feet (91 cm) horizontally from an oil
tank vent or gas meter to avoid potential freeze-up from condensation,
see Figure 23.
Plan the vent system layout so that proper clearances are maintained
from plumbing
and wiring.
Vent pipes serving power vented appliances
are classified by building
codes as "vent connectors".
Required clearances
from combustible
materials
must be provided
in accordance
with information
in this
manual under FACTS TO CONSIDER
ABOUT THE LOCATION and
VENT TERMINAL
INSTALLATIONS,
and with the National Fuel Gas
Code and local codes.
VENT
TERMINAL
INSTALLATION
1.
After the point of termination
has been determined,
use the cover
plate as a template to mark the hole for the vent pipe to insert through
the wall. BEWARE OF CONCEALED
WIRING AND PIPING INSIDE
OF WALL.
2.
3.
If the Vent Terminal is being installed on the outside of a finished wall,
it may be easier to mark both the inside and outside wall. Align the
holes by drilling a hole through the center of the template from the
inside through to the outside.
The template can now be positioned
on the outside wall using the drilled hole as a centering point for the
template.
A) MASONRY
SIDE WALLS
Chisel an opening approximately
one half inch larger than the marked
circle.
4.
B) WOODEN SIDE WALLS
Drill a pilot hole approximately
one quarter inch outside of the marked
circle. This pilot hole is used as a starting point for a saws-all or sabre
saw blade. Cut around the marked circle staying approximately
one
quarter inch outside of the line. (This will allow the vent pipe to easily
slide through the opening.
The resulting gap will be covered up by
the vent
terminal cover plates.)
Repeat this step on inside wall if
necessary.
When the vent piping cannot pass through an outside wall at a
height greater than or equal to 12" above the ground (or above snow
accumulation
level), then the installation can be modified as shown
below.
///
///
///
///
///
///
ABOVE
I I
GROUND ORSNOW
_
ACCUMULATIONLEVEL
FIGURE 22.
19

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Economizer 6153.332040153.332050

Table of Contents