Refer to our repair and calibration section at www.aemc.com/calibration. Serial #: Catalog #: 2137.69 / 2137.71 Model #: PEL 52 Please fill in the appropriate date as indicated: Date Received: Date Calibration Due: Chauvin Arnoux , Inc.
Example: hardwired equipment in fixed installation and circuit breakers. CAT II: Corresponds to measurements performed on circuits directly connected to the electrical distribution system. Example: measurements on household appliances and portable tools. Power & Energy Logger Model PEL 52 - User Manual...
Save the damaged packing container to substantiate your claim. Power & Energy Logger Model PEL 52 - User Manual...
Page 9
(1) Safety Sheet for the PEL (1) Safety Sheet for the MiniFlex Sensors ® (1) Compliance Sheet (1) SD Card (1) Quick Start Guide (2) AAA Rechargeable Batteries (1) Battery Information Sheet Power & Energy Logger Model PEL 52 - User Manual...
Page 10
User Manual & ® Dataview Software Also Included: (1) Safety Sheet for the PEL (1) Compliance Sheet (1) SD Card (1) Quick Start Guide (2) AAA Rechargeable Batteries (1) Battery Information Sheet Power & Energy Logger Model PEL 52 - User Manual...
Lead rated 1000 V CAT IV 15 A, Clip rated 1000 V CAT IV 15 A, UL for PowerPad & PEL Series ......Cat. #2140.44 USB SD - card reader for PEL 102, PEL 103 & PEL 52 ... Cat. #5000.45 Order Accessories and Replacement Parts Directly Online Check our Storefront at www.aemc.com/store...
When the symbol is full and steady, the battery is fully charged. NOTE: The battery will take approximately 5 h to fully charge. Power & Energy Logger Model PEL 52 - User Manual...
Phase angle measurement ■ Calculation of aggregations of values from 1 minute to 1 hour ■ In addition to the types of measurements, the PEL 52 offers the following features: Storage of values on SD or SDHC card ■ Communication via Wi-Fi ■...
NOTE: Before connecting a current sensor, consult the sensor's corresponding safety data sheet or user manual. Also, the PEL must not be used when the SD card slot is open. Power & Energy Logger Model PEL 52 - User Manual...
SD card facing up and forward, gently push card straight into the card slot until you hear a click. SD Card Slot Screw Protective Cover Figure 6 Power & Energy Logger Model PEL 52 - User Manual...
In select mode, starts or stops a recording after the Select button is pressed. It also allows the type of Wi-Fi to be chosen. Table 1 If any button is pressed, the backlight will turn on for 3 minutes. Power & Energy Logger Model PEL 52 - User Manual...
Blinking: Wi-Fi Direct is actively transmitting. OFF: Wi-Fi Direct is disabled. 6. Wi-Fi (router connection ON (steady): Wi-Fi connection is enabled and not transmitting. Blinking: Wi-Fi is actively transmitting. OFF: Normal Wi-Fi connection is disabled. Power & Energy Logger Model PEL 52 - User Manual...
The memory symbols below when displayed indicate the approximate number of sessions stored. number of sessions ≤ 50 number of sessions > 50 number of sessions > 100 number of sessions > 150 number of sessions = 200 Power & Energy Logger Model PEL 52 - User Manual...
AP Mode: Failed to set AP mode password AP UDP SERVER FAILED AP Mode: Failed to start UDP server AP TCP SERVER FAILED AP Mode: Failed to start TCP server Power & Energy Logger Model PEL 52 - User Manual...
Page 20
WAITING FOR BOOT EVENT Waiting for the module to send a boot event message WAIT FOR HELLO MSG Waiting for module greeting WAITING FOR SYNC Waiting for module synchronization messages Power & Energy Logger Model PEL 52 - User Manual...
This is a precaution intended to prevent a recording from being unintentionally stopped by the user. To turn the PEL off: Disconnect the PEL. ■ Press and hold the ON/OFF button until the device turns off. ■ Power & Energy Logger Model PEL 52 - User Manual...
1P-2W1I: Single-phase 2-wire with a current sensor ■ 1P-3W2I: Single-phase 3-wire (2 voltages in phase) with two current sensors ■ 2P-3W2I: Split-phase 3-wires (2 voltages in opposite phases) with two ■ current sensors Power & Energy Logger Model PEL 52 - User Manual...
■ WIFI ST. PUSH ENTER FOR WIFI ST, WIFI OFF. PUSH ENTER FOR WIFI OFF or WIFI AP. PUSH ENTER FOR WIFI AP. Figure 10 Figure 11 Power & Energy Logger Model PEL 52 - User Manual...
Page 24
■ Figure 12 Start the PEL Control Panel (see § 5). ■ Go to Instrument, Add an Instrument, PEL 52, to Wifi access point. ■ When you are connected to the PEL Control Panel, you will be able to: ■...
Page 25
Your device will connect to this Wi-Fi network. The Wi-Fi access point connection will be lost. Once the PEL is connected to the network, you can find the PEL's IP address in information mode Power & Energy Logger Model PEL 52 - User Manual...
Page 26
Configuration of the DataViewSync™ connection To connect the PEL to DataViewSync™, the PEL must be in WIFI ST, ■ and the connected network must have internet access in order to access DataViewSync™. Power & Energy Logger Model PEL 52 - User Manual...
■ ■ If two current sensors are connected, they must be identical. For AmpFlex or MiniFlex sensors, press the button to select 300 A or 3000 A. ■ ® ® Power & Energy Logger Model PEL 52 - User Manual...
From the aggregation period screen, press the ▼ key to access the following ■ screen. Figure 18 To reset the device to the default Wi-Fi configuration (direct Wi-Fi, password ■ deleted), press the key. Power & Energy Logger Model PEL 52 - User Manual...
■ menu (see § 3.4). The following screen will be displayed: Figure 19 NOTE: Refreshing the display is not automatic. You need to refresh regularly. Power & Energy Logger Model PEL 52 - User Manual...
Page 30
On the second tab, measurements can be viewed: Figure 20 On the third tab, the device information is displayed: Figure 21 Power & Energy Logger Model PEL 52 - User Manual...
To enter Information mode, press the ◄ or ► buttons until the symbol is ■ selected. Using the ▲ and ▼ keys, scroll through the device information: ■ ■ Type of network Power & Energy Logger Model PEL 52 - User Manual...
Page 32
Year, month, day ■ Time Hour, minute, second ■ IP address (scrolling) ■ Firmware version and scrolling serial number After configuration is complete, the instrument is ready for use. Power & Energy Logger Model PEL 52 - User Manual...
Connect the V1 measuring lead to the L1 phase conductor. ■ Connect the I1 current sensor to the L1 phase conductor. ■ 600 V 600 V CAT III Figure 23 Power & Energy Logger Model PEL 52 - User Manual...
Connect the I1 current sensor to the L1 phase conductor. ■ Connect the I2 current sensor to the L2 phase conductor. ■ 600 V 600 V CAT III Figure 25 Power & Energy Logger Model PEL 52 - User Manual...
The displays can be accessed as soon as the PEL is turned on but the values will be zero. The values will update when voltage or current is present at the inputs. Power & Energy Logger Model PEL 52 - User Manual...
Single-phase 2-wire (1P-2W1I)v φ (I If the current sensor is not detected, all the quantities that depend on the current (current, angle, powers, PF) are undefined (displays Power & Energy Logger Model PEL 52 - User Manual...
Page 37
Sum of powers on L1 and L2. If a current sensor is not detected, all the quantities that depend on this current (current, angle, powers, PF) are undefined (displays Power & Energy Logger Model PEL 52 - User Manual...
Es+: Total apparent energy consumed (by the load) in VAh. ■ Es-: Total apparent energy supplied (by the source) in VAh. ■ NOTE: The device does not display the h symbol. Therefore, you will see W for Wh. Power & Energy Logger Model PEL 52 - User Manual...
Single-phase 2-wire (1P-2W1I) Power & Energy Logger Model PEL 52 - User Manual...
Page 40
Single-phase 3-wire 2-currents (1P-3W2I) and split-phase 3-wire (2P-3W2I) Sum of powers on the load on L1 and L2. Power & Energy Logger Model PEL 52 - User Manual...
Page 41
Sum of powers on the source on L1 and L2. Power & Energy Logger Model PEL 52 - User Manual...
Adobe Reader. This links to the Adobe ® web site where you can download the latest version of Reader. This program is recommended to view DataView.pdf documents. Power & Energy Logger Model PEL 52 - User Manual...
Page 43
French, or Spanish) then click Next. (By default, the language selected in step 3 is highlighted.) Figure 27 5. You are now prompted to select the software you want to install. Figure 28 Power & Energy Logger Model PEL 52 - User Manual...
Page 44
Panel(s) that you have installed. 10. A warning message similar to the one below will appear. Click OK. There is no USB connection on the PEL 52, therefore ignore this automatic message that applies to other devices in the PEL range.
For further information about using the PEL Control Panel, consult the Help system that comes with the product. To access Help, click the option Help in the PEL Control Panel’s menu bar at the top of the screen. Power & Energy Logger Model PEL 52 - User Manual...
2. To open the PEL Control Panel, double click on the PEL Control Panel icon 3. Select Instrument from the menu, then Add an Instrument. 4. Go through the process of adding the PEL 51 or PEL 52 instrument. Reference the PEL HELP file if assistance is needed.
You can also choose which data to record. Recorded data is stored on the PEL instrument, where it can subsequently be downloaded to a PC and analyzed in detail using DataView. Power & Energy Logger Model PEL 52 - User Manual...
Page 48
The app is provided with a complete online Help system, which can be viewed independently at http://www.pel100.us/help-en/index.html. Consult this Help system for a complete description of the PEL app and all its capabilities. Power & Energy Logger Model PEL 52 - User Manual...
100 mA at 90 V and 500 mA at 600 V. Sustained overload: 660 V. Above 690 V, the device will display the OL symbol. Power & Energy Logger Model PEL 52 - User Manual...
Active power PF = [0.5 inductive; 0.8 capacitive] V = [100 V; 600 V] ± 0.7 % R ± 0.007 % P I = [5 % I ; 120 % I Power & Energy Logger Model PEL 52 - User Manual...
Page 51
Active energy , Ep , Ep PF = [0.5 inductive; 0.8 capacitive] V = [100 V; 600 V] ± 0.6 % R I = [5 % I ; 120 % I Power & Energy Logger Model PEL 52 - User Manual...
The choice of the current sensor to use depends on the current to be measured and the diameter of the cables. When installing current sensors, point the arrow on the sensor towards the load. When a current sensor is not connected, the device displays Power & Energy Logger Model PEL 52 - User Manual...
2, 600 V CAT IV, 1000 V CAT III Table 6 NOTE: Currents < 0.4 A for the 300 A range and < 2 A for the 3000 A range are set to zero. Power & Energy Logger Model PEL 52 - User Manual...
Page 54
2, 600 V CAT IV, 1000 V CAT III Table 7 NOTE: Currents < 0.4 A for the 300 A range and < 2 A for the 3000 A range are set to zero. Power & Energy Logger Model PEL 52 - User Manual...
Page 55
AC current IEC/EN 61010-2-032 or BS EN 61010-2-032, Safety pollution degree 2, 300 V CAT IV, 600 V CAT III Table 9 NOTE: Currents < 0.1 A are set to zero. Power & Energy Logger Model PEL 52 - User Manual...
Page 56
AC current IEC/EN 61010-2-032 or BS EN 61010-2-032, Safety pollution degree 2, 300 V CAT IV, 600 V CAT III Table 11 NOTE: Currents < 50 mA are set to zero. Power & Energy Logger Model PEL 52 - User Manual...
Rejection: > 60 dB 6.3.5 Frequency Range of influence: (45 to 65) Hz, - 60 ° ≤ φ ≤ +60 ° Quantities influenced: V1, V2, I1, I2, P1, P2 Influence: 0.1 %/Hz Power & Energy Logger Model PEL 52 - User Manual...
MiniFlex MA193 or MA194 < 3 % ® Table 15 Bridge rectifiers have a waveform that is not supported by the PEL 52. 6.4 POWER SUPPLY Power supply (between terminals V1 and N) Operating range: (100 to 600) V ■...
2.4 G Hz IEEE 802.11 b/g band ■ Tx (b) power: +17.3 dBm Tx (g) power: +14 dBm Rx sensitivity: -98 dBm Security: open / WPA2 Power & Energy Logger Model PEL 52 - User Manual...
0.5 % of full scale with a maximum of 5 A. 6.10 RADIO EMISSION The devices comply with the RED Directive 2014/53/EU and FCC regulations. FCC certification number for the Wi-Fi: FCC QOQWF121 Power & Energy Logger Model PEL 52 - User Manual...
Charge the device only at temperatures between (50 and 104) °F (10 and 40) °C. ■ Comply with the conditions for use. ■ Comply with the conditions for storage. ■ Power & Energy Logger Model PEL 52 - User Manual...
(Or contact your authorized distributor.) Contact us for the costs for repair, standard calibration, and calibration traceable to N.I.S.T. NOTE: You must obtain a CSA# before returning any instrument. Power & Energy Logger Model PEL 52 - User Manual...
AEMC Instruments will repair or replace the faulty material ® at our discretion. REGISTER ONLINE AT: www.aemc.com/warranty.html Power & Energy Logger Model PEL 52 - User Manual...
Fax: (603) 742-2346 E-mail: repair@aemc.com Caution: To protect yourself against in-transit loss, we recommend that you insure your returned material. NOTE: You must obtain a CSA# before returning any instrument. Power & Energy Logger Model PEL 52 - User Manual...
Aggregation of values for aggregated trends . ■ Determination of minimum and maximum values for the values of aggregated ■ trends. All 1 s quantities can be recorded on the SD card during the recording session. Power & Energy Logger Model PEL 52 - User Manual...
N = number of samples L = I1 or I2 incremental sample Active power (PL) N = number of samples [1 s]= P [1 s] + P [1 s] Table 16 Power & Energy Logger Model PEL 52 - User Manual...
Table 17 N is the number of 1 s values for the aggregation period considered (1, 2, 3, 4, 5, 6, 10, 12, 15, 20, 30, or 60 minutes). Power & Energy Logger Model PEL 52 - User Manual...
Split-phase (split-phase single phase 3-wire) Reference Abbreviation Comments diagram Voltage is measured between L1, L2, and N. 2P-3W2I see § 4.1.3 Current is measured on conductors L1 and L2. Table 18 Power & Energy Logger Model PEL 52 - User Manual...
Fundamental ● ○ ○ reactive power on the load ● ○ ○ ○ Apparent power Apparent power ● ○ on the source Apparent power ● ○ on the load Power & Energy Logger Model PEL 52 - User Manual...
Page 72
Reactive energy ● ○ on quadrant 3 Reactive energy ● ○ on quadrant 4 Apparent energy ● ○ on the source Apparent energy ● ○ on the load ● Φ (I Power & Energy Logger Model PEL 52 - User Manual...
Cosine of the phase shift of the voltage with respect to the current DC component (current or voltage) DataViewSync™ Internet Relay system that relays data between the recorder and a PC Power & Energy Logger Model PEL 52 - User Manual...
Page 74
Phase-neutral voltage or Volt (unit of voltage) Unit of apparent power (Volt x Ampere) Unit of reactive power varh Unit of reactive energy Unit of active power (Watt). W·h Unit of active energy (Watt x hours) Power & Energy Logger Model PEL 52 - User Manual...
Need help?
Do you have a question about the PEL 52 and is the answer not in the manual?
Questions and answers