5
Specifications
Power factor improving effect
Power specifications
Surrounding air
temperature
Ambient humidity
Storage temperature -20°C to + 65°C (non-freezing)
Atmosphere
Altitude/vibration
The power factor is calculated on the assumption that the power impedance is 1%. The value
changes according to the power supply capacity and power impedance. The load is
calculated using the fundamental current specified in JEM-TR201 as 100%.
The value is 92.3% when calculated with 1 power factor for the fundamental wave according
to the Architectural Standard Specifications (Electrical Installation) (2013 revision) supervised
by the Ministry of Land, Infrastructure, Transport and Tourism of Japan.
For a motor of less than 0.4kW, the power factor improving effect will be slightly lower.
For single-phase power input, the power factor improving effect will be slightly lower.
For the installation at an altitude above 1000 m up to 3000 m, consider a 3% reduction in
the rated current per 500 m increase in altitude.
2
2.9m/s
or less for the H185K or higher.
Power supply power factor approx. 88% (92.3%)
(at 100% load)
200V class Three-phase 200 to 240VAC 50Hz/60Hz
55K or
lower
400V class
75K or
higher
-10°C to + 50°C (non-freezing)
90%RH or less (non-condensing)
Indoors (free from corrosive gas, flammable gas, oil
mist, dust and dirt)
Max. 3000m/ 5.9m/s
Z directions
Specifications
Three-phase 380 to 480VAC
50Hz/60Hz
Three-phase 380 to 500VAC
50Hz/60Hz
2
*2*3 at 10 to 55 Hz in X, Y, and
8