Frigidaire FHWW144TF1 Use & Care Manual page 8

Table of Contents

Advertisement

8
IMPORTANT SAFETY INSTRUCTIONS
searching for or detection of refrigerant
leaks. A halide torch (or any other
detector using a naked flame) shall not be
used.
The following leak detection methods are
deemed
acceptable
containing
flammable
Electronic leak detectors shall be used to
detect flammable refrigerants, but the
sensitivity may not be adequate, or may
need
re-calibration.
equipment
shall
refrigerant-free area). Ensure that the
detector is not a potential source of
ignition and is suitable for the refrigerant
used. Leak detection equipment shall be
set at a percentage of the LFL of the
refrigerant and shall be calibrated to the
refrigerant employed and the appropriate
percentage of gas (25 % maximum) is
confirmed. Leak detection fluids are
suitable for use with most refrigerants but
the use of detergents containing chlorine
shall be avoided as the chlorine may react
with the refrigerant and corrode the
copper pipe-work. If a leak is suspected,
all
naked
removed/extinguished. If a leakage of
refrigerant
is
brazing, all of the refrigerant shall be
recovered from the system, or isolated
(by means of shut off valves) in a part of
the
system
remote
Removal of refrigerant shall be according
to Removal and evacuation.
11. Removal and evacuation
When breaking into the refrigerant circuit
to make repairs – or for any other
purpose–conventional procedures shall
be
used.
However,
refrigerants it is important that best
practice be followed, since flammability is
a consideration. The following procedure
shall be adhered to:
a) Safely remove refrigerant following
local and national regulations;
b) Evacuate;
c) Purge
the
(optional for A2L);
d) Evacuate (optional for A2L);
for
systems
refrigerants.
(Detection
be
calibrated
flames
shall
found
which
requires
from
the
for
flammable
circuit
with
inert
e) continuously flush or purge with inert
gas when using flame to open circuit;
and;
f) open the circuit.
The refrigerant charge shall be recovered
into the correct recovery cylinders if
venting is not allowed by local and
national codes. For appliances containing
flammable refrigerants, the system shall
be purged with oxygen-free nitrogen to
render the appliance safe for flammable
in
a
refrigerants. This process might need to
be repeated several times. Compressed
air or oxygen shall not be used for
purging
appliances
refrigerants, refrigerants purging shall be
achieved by breaking the vacuum in the
system with oxygen-free nitrogen and
continuing
pressure is achieved, then venting to
atmosphere, and finally pulling down to a
vacuum (optional for A2L). This process
shall be repeated until no refrigerant is
within the system (optional for A2L).
When the final oxygen-free nitrogen
be
charge is used, the system shall be vented
down to atmospheric pressure to enable
work to take place. Ensure that the outlet
for the vacuum pump is not close to any
potential
ventilation is available.
leak.
12. Charging procedures
In addition to conventional charging
procedures, the following requirements
shall
contamination of different refrigerants
does not occur when using charging
equipment. Hoses or lines shall be as
short as possible to minimise the amount
of
refrigerant
Cylinders shall be kept in an appropriate
position according to the instructions.
Ensure that the refrigeration system is
earthed prior to charging the system with
refrigerant.
charging is complete (if not already).
Extreme care shall be taken not to overfill
gas
the
refrigeration
recharging the system it shall be pressure
refrigerant
systems.
containing
to
fill
until
ignition
sources
be
followed.
contained
Label
the
system.
For
flammable
the
working
and
that
Ensure
that
in
them.
system
when
Prior
to

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the FHWW144TF1 and is the answer not in the manual?

Table of Contents