4585 COM-LOOP REPEATER - FIRE ALARM SOLUTIONS TECHNICAL DESCRIPTION
9. TECHNICAL DATA
All current consumptions are valid by nominal voltage and by 25 °C.
Voltage:
Allowed
Normal
Current:
Max
min (internal)
COM loop voltage:
Allowed
Normal
COM loop current:
SUB-loop:
Voltage
Current
Max outtake
Address range
Address setting
Short circuit isolator
Internal battery
Ambient temperature:
Operating
Storage
Ambient humidity
Size:
H x W x D
Weight (including batteries):
The 4585 unit is power supplied from the 4466.
16 – 30.0V DC
24V DC
640 mA
10 mA
12 - 30V DC
24V DC
< 6 mA
22.0V - 24.0V
350 mA
001-253
Automatic
No
No
-5 to +40 °C
-20 to +70 °C
Maximum 95 % RH (Non condensing)
108 x 114 x 15 mm (the p.c.b. incl. components)
55 g