Page 5
If it does not light up, verify the 24 VAC is connected to the The A2L Controller will remain in the alarm state for five minutes controller, the wiring connections are tight, and they are wired for after the sensor is cleared before returning to normal operation.
Page 6
OMRON G5Q-1 DC12V 5A30VDC CHINA 10A250VAC ~ 4.40 OMRON G5Q-1 DC12V 5A30VDC CHINA 10A250VAC ~ OMRON G5Q-1 DC12V 5A30VDC CHINA 10A250VAC ~ 2019WXX Note: All Dimensions are in inches. Figure 1: A2L Mitigation Controller Components A2L Mitigation Controller Technical Guide...
Page 7
*VA Load is dependent on sensor configuration. Table 1: Voltage and Environment Requirements Wiring The A2L Mitigation Controller and expansion modules must be connected to a 24 VAC power source of the proper size for the calculated VA load requirements. All transformer sizing should be...
Page 8
Alarm - Normal condition held closed Signal Out VAV - Normal condition held open COMM Common Table 2: Analog Inputs Wiring VAV - Normal condition held closed Table 4: Relay Inputs Wiring Figure 2: Analog Input Pin Diagram A2L Mitigation Controller Technical Guide...
Page 9
24 VAC NOTE: When two A2L Mitigation Controllers are used, wire the compressor relay in series. Figure 3: A2L Mitigation Controller Wiring Diagram - Air Flow NOTE: The Sensor Bypass Plug is Sensor 1 only used if a sensor is not installed.
Page 10
VCCX-454 5A30VDC CHINA 10A250VAC ~ Fan Proof of Flow Signal Common OMRON G5Q-1 DC12V Signal 5A30VDC CHINA 10A250VAC ~ Field 2019WXX Connection 24 VAC Figure 5: A2L Mitigation Controller Wiring - Connected to VCCX-454 A2L Mitigation Controller Technical Guide...
Page 12
A2L Mitigation Controller LEDs The three red Sensor LEDs indicates the attached sensor detects a fault or the sensor is not connected. The A2L Mitigation Controller is equipped with LEDs that can be Binary LEDs used to verify operation and perform troubleshooting.
Page 13
TROUBLESHOOTING A2L Gas Sensor Wiring The A2L gas sensor is wired as shown on Figure 8, this page. LED Lights When the sensor is powered up, an LED will indicate the sensor status. While the sensor is mounted, the LED will backlight the sensor and be visible by reflection from the mounting service.
Need help?
Do you have a question about the A2L and is the answer not in the manual?
Questions and answers