TRMS 3-phase voltage and frequency
monitoring relay
DPC02
Connections
(*) F
Connect the 3-phase power supply and the
neutral (if present) taking care of the sequence.
Connect the relay output according to the rat-
ings.
Keep power OFF while connecting!
DPC02
Terminals
L1, L2, L3, N Power supply
15, 16, 18
Relay 1 output
25, 26, 28
Relay 2 output
Each terminal can accept up to 2 x 2.5 mm
Tightening
torque
Adjustment
V
= Overvoltage
0 1
4 1
6
18
V
= Undervoltage
2
22%
V
-14
-10
50
70
Hz = Frequency tolerance
-18
-6
30
90
2
DELAY 1 and 2 = Delay time
-22
-2%
10
110%
V
Hz
1
3
1
3
1
and
= Yellow LEDs
0.3
10
0.3
10
1
2
AL
0. 1
30s
0. 1
30s
AL /
= Red LED / Green LED
DELAY 1
DELAY 2
When the frequency runs out of the set window, for more than the set delay time, the "frequency" output relay (terminals 25, 26, 28) and the related yellow LED turn OFF, red LED (flashing 2 Hz during
the delay time) turns ON. If the phase sequence is wrong, or one phase is lost, the output relays release immediately (only 200 ms delay occurs). This failure is indicated by the red LED which flashes
5 Hz as long as the alarm condition is occurring.
Mounting
Hang the device to the DIN-Rail being sure that the spring closes. Use a screwdriver to remove the
product.
Installation instructions
Code 8022339/170624 INSTRUCTION SHEET
DPC02 V4
www.gavazziautomation.com
Settings
Do not open the DIP switches cover if
the Power Supply is ON!
Setting only for DPC02DM44
SW1: System frequency
ON: 60 Hz
OFF: 50 Hz
wires
2
SW2: Setpoint range
ON: 2 Hz
OFF: 15 Hz
Ensure the input voltage range is correct. Adjust upper (
frequency window ( Hz
) on relative scale by turning the upper right dial. Turn the lower dials to set the delay times (0.1 to 30 s).
Turn power ON. The bi-colour bottom LED turns ON (green or red colour).
DPC02 operates when all 3 phases are present at the same time in the proper turning sequence, the voltage value is within the upper and lower set limits
and the frequency value is within a symmetrical window around the nominal frequency.
When one or more phases exceed the upper level, or drops below the lower level, for more than the set delay time, the "voltage" output relay (terminals
15, 16, 18) and related yellow LED turn OFF, red LED (flashing 2 Hz during the delay time) turns ON.
Scan to read me in your language!
Scannen Sie, um mich in Ihrer Sprache
zu lesen!
Scanne pour me lire dans ta langue !
SW1: Output configuration
ON: 2 x SPDT (relays operate independently
each connected to a single set point)
OFF: 1 x DPDT (relays operate together)
SW2: Mains type
ON: 3P+N
OFF: 3P
SW1: Output configuration
ON: 2 x SPDT (relays operate independently
each connected to a single set point)
OFF: 1 x DPDT (relays operate together)
Nominal
208 V 220 V 230 V 240 V 380 V 400 V 415 V 440 V 480 V 600 V 690 V
voltages
SW3
ON
ON
ON
SW4
ON
ON
ON
SW5
ON
ON
OFF
SW6
ON
OFF
ON
) and lower (
) voltage levels by turning the upper left and the middle left dials. Adjust the
Packaging
The packing material should be kept for redeliv-
ery in case of replacement or repair.
¡Escanea para leerme en tu idioma!
Scansiona per leggermi nella tua lingua!
Scan for at læse mig på dit sprog!
扫码后选择相关语言进行阅读!
SW3
SW4 Nominal voltages
Models M23
M48
ON
ON
208 V
380 V
ON
OFF
220 V
400 V
OFF
ON
230 V
415 V
OFF
OFF
240 V
480 V
SW5: System frequency
SW6: Setpoint range
ON: 60 Hz
ON: 2 Hz
OFF: 50 Hz
OFF: 15 Hz
SW2: Mains type
ON: 3P+N
OFF: 3P
ON
ON
ON
ON
ON
ON
OFF
OFF
OFF
OFF
OFF
ON
ON
OFF
OFF
OFF
ON
OFF
ON
OFF
CE-marking and approvals
M49
M69
440 V
600 V
440 V
600 V
480 V
690 V
480 V
690 V
OFF
OFF
OFF
ON
ON
ON
ON
ON
OFF
ON
OFF
ON
Need help?
Do you have a question about the DPC02 and is the answer not in the manual?
Questions and answers