• Must be posted at least 3 meters high if there are people divisions. • Detectors should not be mounted close to the walls and partitions less than 0.5 m. KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 4/15...
0,5m ≤ H 2 ≤ 7,5m 5m ≤ L 1 ≤ 100m 0,5m ≤ L 2 ≤ 7,5m 1m ≤ L 3 ≤ 15m L 4 ≤ 1m KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 5/15...
The screw is removed which is at the top of Beam Detector. While holding the latch on the top cover of the detector, the force applied to the cover the detector with 45° an angle and provides opening cover. Press and hold the latch Unscrewing Valve opening direction KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 6/15...
Alarm Resistor (470Ω) should be connected to “Alarm” terminal, 2. and 3. terminal. End of line resistor (6,8KΩ) should be connected to “Fault” terminal, 5. and 6. terminal. 470Ω and 6,8KΩ resistor values can be different depends on the conventional panel. KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 7/15...
Page 8
Zone Alarm Fault Conn3 Conn4 Conn3 Conn4 Conn3 Conn4 Fire Zone Alarm Panel Zone 24V DC 24V DC 24V DC 24V DC 24V DC 24V DC Power Supply KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 8/15...
Signal value is checked in Receiver Circuit Menu (Section 4.2 Receiver Circuit) after precise adjustment. This value should be between 86-92. If this value isn’t between 86-92, please continue alignment process. NOTE: Please be sure that cover of the transmitter should be closed. KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 10/15...
4.2.4 AL, Alarm Level Fire detector sensitivity setting. (“%25” blocking of the “25” beam) Note: %35-45 alarm level beyond the scope of EN 54-12 standard tests and are not LPCB approved. KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 11/15...
Detector alarm should be controlled for selected level. Please contact with authorized firm if the test is not successful. Alarm Level The Filter Value The Filter Value which has not an alarm which has an alarm KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 12/15...
If it occurs in a normal condition, it means detectors are dirty. Detector should be cleaned. And optical lenses and filter glass should be cleaned with soft cloth. KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 13/15...
Receiver: 60 mA Operating Temperature -10°C ~ 55°C Maximum Humidity %95 (non- condensing) Dimensions 160 x 192 x 109 mm Weight Transmitter: 800 gr. Receiver: 830 gr. Color White KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 14/15...
Beam Type Smoke Detector Light Emitting Diode ML-2170 Technical specifications: Please check KK-612.003 that is held by manufacturer. Product Code LPCB Certificate No CPR No ML-2170 926j/01 2831-CPR-F1176 KK-612.003 Rev.No:9 04.08.22 ML-2170 Beam Type Smoke Detector User Manual Page 15/15...
Page 16
COMMISSIONING, OPERATING AND MAINTENANCE MANUAL MODEL: MAXLOGIC SERIES ML-2173 SUB MODEL: CONVENTIONAL REFLECTOR BEAM TYPE SMOKE DETECTOR...
Page 17
INTRODUCTIONS 1 - GENERAL DESCRIPTION............................3 1.1 Detection Principles............................3 1.2 Utilization Fields..............................3 1.3 Manufacturer Info..............................3 1.4 Warnings................................4 2 - INSTALLATION...............................4 2.1 General Placement Rules.............................4 2.2 Placement.................................5 2.3 Pitched Roof...............................6 2.4 Ventilated Area..............................6 3 - INSTALLATION STEPS.............................7 3.1 Opening the Detectors Cover..........................7 3.2 Physically Installation and Cable Input Points......................7 3.3 Detector Connections and Settings........................8 3.3.1 Connections to the Conventional Panel......................8...
1 - GENERAL DESCRIPTION Beam type smoke detector is included with transmitter receiver module and reflector. Maximum and minimum distance should be 5-35m between transmitter receiver module and reflector. Can be expanded to 50m with 4pcs reflector. The infrared beam normally goes to reflector from the transmitter and then from the reflector goes to receiver.
1.4. Warnings The control unit contains static-sensitive high quality electronic control equipment. Do not use the panel before reading this manual. • This product should be stored as packed on indoor areas. • Storing ambient temperature should be (-30°C) to (+60°C) and relative humidity should not be exceed %95 as uncondensed. •...
2.3 Pitched Roof For detectors which are mounted on peak of the pitched ceilings. 7,5m given distance can be increased %1 for each 1° roof slope. It can be maximum %25 increase. In case of a curved roof, average slope should be used for an extended distance. Roof Angle 10°...
3 - INSTALLATION STEPS Installation of the product should be made according to the “Installation Steps”. 3.1 Opening the Detectors Cover The screw is removed which is at the top of Beam Detector. While holding the latch on the top cover of the detector, the force applied to the cover the detector with 45°...
Detector Connections and Settings 3.3.1 Connection to the conventional panel Number 2 and 3 PINs of “A” and “B” PINs should be made short circuit with jumper while installing to conventional panel. Alarm Resistor (470Ω) should be connected to “Alarm” terminal, 2. and 3. terminal. End of line resistor (6,8KΩ) should be connected to “Fault” terminal, 5.
3.3.2 Receiver Connections - Relay Output If wanted to operate with relays, “A” and “B” with number 1 and 2 switches should be made short circuit with jumper. Alarm relay; 1. NO : Normally Open 2. C : Common 3. X : There is no connection Fault relay;...
Plane Mirror “Point of view” “Looking point” A Details 3.4.1. Coarse Adjustment Looking at 10-15 cm away from the point of view of the device to the eye level in paralel, alignment is performed with alignment buttons until other device appears on the mirror. 10-15 cm 3.4.2.
4 - MENU SETTINGS 4.1 Display and Controls Button Locations button POWER FIRE FAULT Display button Down button LED Indicators; POWER : Shows the power status. FIRE : Shows the fire alarm status. FAULT : Shows the fault status. Display Indicators; Shows menu operations and measurement values.
4.2.6 rS; Signal Reading Menu Signal reading field between the receiver and transmitter. Used to align the transmitter receiver module and reflector. 4.3 Menu Structure In the following table, steps which are activated in the detector menus, and step options values, were specified. The black filler cells are default values.
6 - FAULT STATUS Yellow LED shows the fault. In this case, the transmitter receiver modules’ cover is opened, the relevant operations should be carried out according to the error code on the display. Error codes and things to do are as follows: 6.1 “E1”...
7 - DISPLAYS Receiver-Transmitter module 3 LED lights (Power, Alarm, Fault) POWER ALARM FAULT LED Position Status Green LED : Shows power, flashes in 0,5 s. Red LED : Shows the fire status, flashes continuously. Yellow LED : Shows the fault status, flashes continuously. 8 - BOX CONTENTS 1 pcs Receiver-Transmitter Module 1 pcs Reflector...