Summary of Contents for Temper Koban KMPC-01-50A

  • Page 1 KMPC-01-50A (0769711)
  • Page 3: Table Of Contents

    CONTENT 1. Introduction ..................1 2. Performance Feature ................ 1 2.1. Large touch LCD is clear and obvious, easy to operate....1 3. Ttechnical breakthrough ..............2 4. Technology Specification ..............2 5. Operation Procedure & Function Description ........3 5.1. Measurement principle & testing wiring diagram .......3 5.2.
  • Page 4: Introduction

    1. Introduction Large Grounding Grid Earth Resistance Tester is a multi-purpose model to test the grounding impedance, grounding resistance and soil resistivity of substation ground network(4Ω), water and fire power plant, microwave station(10Ω), lightning arrester(10Ω), communication base station and other large ground network, The instrument adopts the new frequency type conversion AC power supply, microcomputer processing control and signal processing measures, which solves the anti-interference problem in the test process, simplifies the test operation process, improves the accuracy of the test results, and greatly reduces the labor intensity and test cost of the test...
  • Page 5: Ttechnical Breakthrough

    2.9.Measure earth voltage, step voltage, voltage gradient and others characteristic parameters. 2.10.Measure soil resistivity. 2.11.Pylon measurement function( 2.7. With RS232 and USB interface *PS.: RS232 and USB interface only for secondary development or improvement, can supply the Serial Protocol, not provide the background software. 3.
  • Page 6: Operation Procedure & Function Description

    Data Storage 100 groups Computer Interface (Only For Secondard RS232 and USB Development) Printer Working Temperature & -10℃~40℃;80%rh below Humidity Storage Temperature & -20℃~60℃;70%rh below Humidity Insulation Resistance Above 20MΩ (between the circuit and shell 500V) Withstand Voltage AC 3700V/rms(between the circuit and shell) 5.
  • Page 7 1.Current electrode(C1) 2.Voltage electrode(P1) 3.Voltage electrode(P2) 4.Grounding grid(C2) 5.Current electrode(external C1) 6.Voltage electrode(external P1) 7.Voltage electrode(external P2) 8.Grounding grid(external C2) 9.External + 10.External - 11.Power supply 12.Power switch 13.Printer 14.RS-232 port 15.USB port 16.Ground port 17.LCD Measurement wire connecting diagram as follow:...
  • Page 8: Operation Steps

    Note: voltage electrode2(P2), grounding grip(C2) two line must connect to the instrument, and then according the measurement operation steps to testing. 5.2. Operation Steps 5.2.1. First of all, check whether the current line, voltage line and grounding network line used for the test are open circuit situation or not (can be measured with multimeter), whether the rust on the grounding pile is cleared, and whether the buried depth is appropriate (>0.5 meters).
  • Page 9 5.3.1. Frequency can select Variable Vrequency(VF) and Fixed Frequency(FF); (a).Variable Vrequency(VF) select option as follow: (b).Fixed Frequency(FF) select option as foolow: 5.3.2. Test mode can select different mode as G.Grid(Grounding Grid), C. Spk(Current Spike), V. Spk(Voltage Spike), Step.V(Step Voltage), G. Cont( Grounding Continuity), Soil R( Soil...
  • Page 10 Resistivity), Tch. V( Touch Voltage). 5.3.4. Test current can select 1A-5A gears inuput current, click the up and down allow to select differnt input current. 5.3.5. After finish the selection of frequecy, test mode and the input current gear, can press the Start key to start the testing, the testing interface as follow: When finidh the testing, will display the tester result, and can click “SAVE”...
  • Page 11: Test Menu Detail Description

    5.3.7. In the function selection interface, click “time set” key to set the time. 5.4.Test Menu Detail Description 5.4.1. Test mode: the instrument can select 7 test modes, which are ”G.Grid ”, “C.Spk”,, “V.Spk”, “Stp.V”, “G.Cont”, “Soil R”, “Tch.V”, The function of “G. Grid”, “C.Spk”, “V.Spk” modes are to measure the impedance of the grounding grid, the current spike and the voltage spike.
  • Page 12: Attentions

    and the "current pole" ground spike or too few ground piles, the ground pile should be increased to reduce the loop resistance. The depth of the ground spike shall not be less than 0.5m. Current spike resistance should be less than 200 Ω. 5.5.2.
  • Page 13: Measurement Grounding Impedance Of The Grounding Grid

    7.2. Measurement Grounding Impedance Of The Grounding Grid 7.2.1. Inclined angle method In general, the measurement of grounding impedance of large grounding devices adopts the mode of the included Angle arrangement of the current and voltage line. Generally, the distance between current pile C and the tested grounding device edge d should be 4~5 times of the diagonal length of the grounding grid.
  • Page 14 7.2.3. Soil resistivity measurement of 4-pole equidistant method The four grounding piles are arranged in a straight line, and the distance between the grounding piles are equal to a. The depth of the ground pile driven into the ground h is not more than one twentieth of a.
  • Page 15: Attention

    It can put in a human body simulation resistance Rm inside the frequency selective voltmeter. (Note: the frequency selective voltmeter need to purchase extra.) Test mode selection: Stp.V/Tch.V VF 1A 7.2.6. The instrument verification During instrument verification, a resistance of more than 20 ohms must be connected at the output end of C1 to simulate the resistance of field current pile, otherwise may cause the measurement data error too large, or cause the instrument may be directly protected.
  • Page 16: Wiring Connection Reference

    9.2.Starting the host power souce and enter the main interface, press “External Power” key to seltect external power mode 9.3.Starting the 50A external power souce instrument. 9.4.Enter into test current adjustment interface, at the same time, set the external power souce to reqeust current, and then press “TEST” key of the earth tester, then the tester will measurement with external power.
  • Page 17 Note: The measurement line is equiped by the user according to the size of the grounding grid Please do not disassemble the instrument, including the panel.It may break the connection wire inside of the instrument and cause the instrument malfunction! The com p an y is not res p onsible for other losses caused b y use.