Omron SYSDRIVE 3G3JV Setup Manual page 56

Compact simplified inverters
Hide thumbs Also See for SYSDRIVE 3G3JV:
Table of Contents

Advertisement

List of Parameters
Param-
Name
eter
No.
(Regis-
ter No.
(Hex))
n62
UP/DOWN
command
(013E)
frequency
memory
n63
Torque
compensa-
(013F)
tion gain
n64
Motor
rated slip
(0140)
n65
Motor no-
load cur-
(0141)
rent
n66
Slip com-
pensation
(0142)
gain
n67
Slip com-
pensation
(0143)
time
constant
3-16
Description
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
Used to store the adjusted frequency refer-
ence with the UP/DOWN function.
0: Frequency not stored
1: Frequency stored
The frequency must be on hold for 5 s or
more.
Used to set the gain of the torque compensa-
tion function.
The default setting does not need any
changes in normal operation.
Used to set the rated slip value of the motor in
use.
Note Used as the constant of the slip com-
pensation function.
Used to set the no-load current of the motor in
use based on the rated motor current as
100%.
Note Used as the constant of the slip com-
pensation function.
Used to set the gain of the slip compensation
function.
Note The slip compensation function is dis-
abled with n66 set to 0.0.
Used for the response speed of the slip com-
pensation function.
Note The default setting does not need any
changes in normal operation.
Chapter 3
Set-
Default
Changes
ting
setting
during
range
opera-
tion
0, 1
0
No
0.0 to
1.0
Yes
2.5
0.0 to
Varies
Yes
20.0
with the
capac-
ity.
0 to
Varies
No
99
with the
capac-
ity.
0.0 to
0.0
Yes
2.5
0.0 to
2.0
No
25.5
Memo