Omron NS10-TV Series Operation Manual
Omron NS10-TV Series Operation Manual

Omron NS10-TV Series Operation Manual

Programmable terminals , host connection manual: host link
Hide thumbs Also See for NS10-TV Series:

Advertisement

Cat. No. V098-E1-05
NS15-TX_, NS12-TS_,
NS10-TV_, NS8-TV_,
NS5-SQ_, NS5-TQ_, NS5-MQ_
Programmable Terminals
Host Connection Manual:
Host Link
OPERATION MANUAL

Advertisement

loading

Summary of Contents for Omron NS10-TV Series

  • Page 1 Cat. No. V098-E1-05 NS15-TX_, NS12-TS_, NS10-TV_, NS8-TV_, NS5-SQ_, NS5-TQ_, NS5-MQ_ Programmable Terminals Host Connection Manual: Host Link OPERATION MANUAL...
  • Page 3 NS-series Programmable Terminals for Host Link communications. First familiarize yourself with the contents of the manuals related to NS-series Programmable Terminals (the NS-series Setup Manual, NS-series Programming Manual, and the CX-Designer online help), and then use this manual for Host Link communications.
  • Page 5 Programmable Controller that supports Host Link communications. The NS-V1/V2 PT is connected 1:1 to the CPU Unit or a Host Link Unit of an OMRON PLC. Host Link communications are used to read and display or write the words and settings in the host PLC.
  • Page 7 This section describes the system configuration required for connecting to the host by Host Link communications. 1-2-1 NS-V1/V2 Configuration Required for Connection NS-V1/V2 Models One of the following NS-V1/V2 PTs is required to connect with the host by Host Link communications. Model NS15-TX01@-V2...
  • Page 8 Memory link (Bar-code reader input) (Temperature controller connection) (CX-Designer connection) The following table shows the communications methods that can be used in combination when serial ports A and B are used at the same time. Serial port B Host Link...
  • Page 9 The OMRON PLCs listed below can be connected as hosts using Host Link communications. The connection can be made either directly to the built-in serial port on the CPU Unit or to a Host Link Unit mounted to the PLC.
  • Page 11 1-3 Connecting to the Host The types of host that can be connected to a PT by using the serial ports on the NS-series PT and connecting to an RS-232C port at the host are described here. 1-3-1 Connecting to an RS-232C Port at the Host Compatible Host Units Some models and series of OMRON PLCs have the host link function built in.
  • Page 12 Level 1, 2, 3 Unit # Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
  • Page 13 Connecting to a C-series Host Link Unit C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Rack-mounted type: C200H-LK201-V1 Setting the Front Switches Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following. • Unit # (SW1, SW2) Set these switches to 0.
  • Page 14 Setting the Rear Switches • I/O port selection (selector switch) Set this to RS-232C. I/O port • Unit # (DIP SW1) Set SW1-1 to SW1-5 to OFF (0). Synchronization • Synchronization (selector switch) Set this to Internal. Terminator • Communications speed...
  • Page 15 A CVM1/CV series host link unit (CV500-LK201) has two connectors (communications ports 1 and 2). Either of these ports can be used for connection to an NS-series PT by the RS-232C method. However, since the connectors at these ports are of different types, a cable that matches the connector must be prepared.
  • Page 16 Set the unit number of the Serial Communications Unit by using the rotary switch located on the front panel. Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following.
  • Page 17 CJ-series Rack-mounted Type: CJ1W-SCU21/41-V1 Setting the Front Switches Set the unit number for the Serial Communications Unit using the rotary switch on the front of the Unit. Follow the procedure below use a flat-head screwdriver (−) to set the number and sign in the setting display window.
  • Page 18 ASCII 7 bits Unit # Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
  • Page 19 Connect to the CPU Unit’s built-in RS-232C port. • Connect to the CPU Unit’s built-in RS-232C port. C200HX/HG/HE(-Z)E • Connect to one of the RS-232C ports (port A or port B) on a Serial Communications Board. • Connect to the CPU Unit’s built-in RS-232C port.
  • Page 20 NS-series PT. For details, refer to 1-4 Settings for Host Link. Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer). For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.
  • Page 21 Setting the DIP Switches of a C200HX/HG/HE(-Z)E, CQM1 or CQM1H When using a C200HX/HG/HE(-Z)E, CQM1, or CQM1H the DIP switches on the front panel must be set as shown below in order to make the settings in the PLC Setup area (data memory) effective.
  • Page 22 When using the CQM1H’s built-in peripheral port, turn ON SW7. Setting the Switches of a CPM2A When using a CPM2A, the switches on the front panel must be set as shown below in order to make the PLC Setup settings effective.
  • Page 23 Host link mode, data length 7 bits, 2 stop bits, even parity 0000 Communications speed: 9600 bps. 0007 Communications speed: 19200 bps. 0000 Unit #00 Setting the Front Switches Set the CPU Unit DIP switches to 4 or 5 in accordance with the port the NS-Series PT is connected to.
  • Page 24 Communications Board. In addition, some C200HX/HG/HE(-Z)E devices have an integral CPU Unit that can be connected in the host link method by installing a Communications Board. With the CPM2A and CPM2C, an RS-422A type of 1:1 NT Link can be created through a CPM1-CIF11 RS-422A Adapter.
  • Page 25 Check the model and series of the PLC and the type of the installed Board or Unit before making a connection. The PLC Units that provide an RS-422A Host Link interface and that can be connected to an NS-series PT port to which an RS-232C/RS422A Link Adaptor (NS-AL002) is connected are listed in the following table.
  • Page 26 Level 1, 2, 3 Unit # Note 1: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
  • Page 27 Connecting to a C Series Host Link Unit C200H/C200HS/C200HE(-Z)E/C200HG(-Z)E/C200HX(-Z)E Rack-mounted Type: C200H-LK202-V1 Setting the Front Switches Set each switch with a flat blade screwdriver so that the values or symbols in the setting value window agree with the following: • Unit # (SW1, SW2) Set these switches to 0.
  • Page 28 • I/O port selection (selector switch) Set this to RS-422A. I/O port • Unit # (DIP SW1) Synchronization Set SW1-1 to SW1-5 to OFF (0). • Synchronization (selector switch) Terminator Set this to Internal. • Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19200 bps.
  • Page 29 Set SW1-1 to SW1-5 to OFF (0). * Parity is fixed at Even Parity. Transfer code is fixed at ASCII 7 data bits and 2 stop bits. • Communications speed (DIP SW2-1 to SW2-4) Set these switches to 0010 to select 19200 bps.
  • Page 30 A CVM1/CV series host link unit (CV500-LK201) has two connectors (communications ports 1 and 2). To use the RS-422A type host link method, set communications port 2 to RS-422A. Communications port 2 is a 9-pin connector which allows selection of the RS-232C or RS-422A method.
  • Page 31 ASCII 7 bits Unit # Note: Set the Host Link communications speed (baud rate) to 9600 bps or 19200 bps with the Communications Setting menu item in the CX-Designer and the System Menu for the NS-series PT. For details, refer to 1-4 Settings for Host Link.
  • Page 32 Set this switch to ON. (Set terminator ON.) C-series C200HX/HG/HE(-Z)E, CPM1, CPM2A, CPM2C, CQM1H, CPU Unit or SRM1 The connection method depends upon the model of PLC being used, as shown in the following table. PLC model Connection method • Connect to the RS-422A port (port A) on a Communications Board.
  • Page 33 NS-series PT. For details, refer to 1-4 Settings for Host Link. Set the PLC Setup area settings directly from a Programming Device (e.g. CX-Programmer). For details on operations relating to the PLC Setup area, refer to the manual for the PLC which is used.
  • Page 34 Unit # 00 Connecting to a CPM2C The CPM2C PLCs do not have the same kind of port connectors found on CS-series PLCs. The CPM2C’s communications port handles both RS-232C and peripheral port connections which are divided internally. Therefore, when using the CPM2C, it is necessary to select RS-232C or peripheral port connections, according to the kind of cable and port (on the cable) used, as shown in the following table.
  • Page 35 Settings are written from the Programming Device (a Programming Console or CX-Programmer) directly into the allocation DM area (system setting area) of the CPU Unit. After the settings are written, they become effective by turning the power ON, restarting the unit, restarting the communications port, or executing the STUP command.
  • Page 36 Setting the Front-panel Switches Set the unit number for the Serial Communications Unit using the rotary switch on the front panel of the Unit. Use a flat-head screwdriver to set the unit number in the setting display window. Set the terminator switch to ON (right side).
  • Page 37 Use the CX-Designer to create the screen data. First, select Communication Setting from the PT Menu to display the Communication Setting Dialog Box. Select Serial Port A or Serial Port B. Then set the serial port to PLC and the protocol to Host Link.
  • Page 38 (1) Press the Comm. Tab in the System Menu to display the Communications Setup Screen. (For the NS5 PT, press the Comm. Button in the System Menu to display the screen, and then press the ← and → Screen Switching Buttons to display the screen for page (2/3).
  • Page 39 1-4-4 Connecting to the Host Connect in the same way as for a 1:1 NT Link, and use the same cables that are used for a 1:1 NT Link connection. If cables must be prepared, refer to the relevant manuals for the PLC or Host Link Unit, and...
  • Page 41 1-5 PLC Areas That Can Be Used for Communications OMRON C-series PLCs PLC model C200HS 00000 00000 00000 00000 00000 00000 C200HE/HG/HX(-Z) 00000 00511 00099 00027 00063 00511 06655 07000 06143 09999 C500 00000 00000 00000 00000 00000 00063 00031...
  • Page 42 09999 CVM1-CPU21-V @ Note 1: The HR Area is included in the CIO Area. To use the HR Area, specify the CIO Area. 2: Do not use this area for creating screens. It cannot be used with Host Link communications.
  • Page 43 To use a project of version 5.x or earlier, first use CX-Designer to convert the project to version 6.0 or later before transferring it to the NS-V1/V2 PT. Applicable Serial Ports Either NS-V1/V2 serial port A or B can be used to connect to the host by means of Host Link communications. Applicable NS Models Only NS-series PT models with a -V1/V2 suffix can be used to connect to the host by means of Host Link communications.
  • Page 44 Revision History The following table outlines the changes made to the manual during each revision. Page numbers refer to the previous version. V098-E1-05 Cat. No. Revision Code Revision code Date Revised content July 2004 Original production July 2006 Revisions made for the release of the CX-Designer.