Roller shutter switch n 523/03 4 x 230 v ac / 6 a (4 pages)
Summary of Contents for Siemens SIPROTEC 5 V9.70
Page 1
Preface Table of Contents Overview of the Function SIPROTEC 5 Structure and Interfaces of the Function Point-On-Wave Switching General Functionality CB Opening Stage V9.70 and higher CB Closing Stage Manual Sequence of Functions Recording and Logging Requirements for Device and External Equipment Technical Data Appendix...
Page 2
Document version: C53000-H5040-C082-5.02 Trademarks Edition: 02.2024 SIPROTEC, DIGSI, SIGRA, SIGUARD, SIMEAS, SICAM, Insights Version of the product described: V9.70 and higher Hub, and OT Companion are trademarks of Siemens. Any unauthorized use is prohibited.
Preface Purpose of the Manual This manual provides supplementary information about the Point-On-Wave Switching function in addition to SIPROTEC 5 device manuals. For other protection, automation, control, and monitoring functions of a specific SIPROTEC 5 device, the corresponding device manual applies. Target Audience Protection system engineers, commissioning engineers, persons entrusted with the setting, testing and maintenance of automation, selective protection and control equipment, and operational crew in electrical...
Page 4
EN 60255-26 (for EMC directive), the standard EN IEC 63000 (for RoHS directive), and with the product standard EN 60255-27 (for Low Voltage Directive) by Siemens. The device is designed and manufactured for application in an industrial environment.
Page 5
You can find the product with the UL File Number E194016. IND. CONT. EQ. 69CA Additional Support For questions about the system, contact your Siemens sales partner. Customer Support Center Our Customer Support Center provides a 24-hour service. Siemens Electrification & Automation...
Page 6
Preface CAUTION CAUTION means that medium-severe or slight injuries can occur if the specified measures are not taken. Comply with all instructions, in order to avoid moderate or minor injuries. ² NOTICE NOTICE means that property damage can result if the measures specified are not taken. Comply with all instructions, in order to avoid property damage.
Table of Contents Preface................................3 Overview of the Function..........................9 Introduction........................10 Subfunctions........................11 Influencing Factors on Desired Closing and Opening Instants..........12 1.3.1 Capacitive and Inductive Loads..................12 1.3.2 System Grounding....................... 12 Properties of the Circuit Breaker..................15 1.4.1 Definitions of Circuit-Breaker Properties............... 15 1.4.2 Compensation of the Mechanical Operating Times............
Page 8
Table of Contents 3.1.6.4 Supervision-Error Reaction..................51 3.1.7 Determination of the Point-on-Wave Switching Availability...........52 Application and Setting Notes................... 54 Settings..........................57 Information List........................ 59 CB Opening Stage............................61 Description........................62 4.1.1 Overview and General Description................62 4.1.2 Opening Time Stamp Calculation and Circuit-Breaker Opening Process......64 4.1.3 Compensation......................
Overview of the Function Introduction Subfunctions Influencing Factors on Desired Closing and Opening Instants Properties of the Circuit Breaker Application Environment and Equipment Applications Possible Device Types and Device Applications Point-On-Wave Switching Processing SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
Overview of the Function 1.1 Introduction Introduction The Point-on-wave switching function in SIPROTEC 5 is used to reduce increased electrodynamic and dielec- tric loads, which are caused by non-optimal switching of circuit breakers in the network. In extreme cases, these loads reduce the reliability and life of the equipment installed in the network or lead to unnecessary opening operations by the protection device.
Overview of the Function 1.2 Subfunctions Subfunctions Control of the Closing and Opening Instants The desired closing or opening instant is always related to a voltage zero crossing. Depending on the load type, the Point-on-wave switching function forwards the received switching command to the trip coil of the circuit breaker with an appropriate delay, taking the phase situation into consideration.
Overview of the Function 1.3 Influencing Factors on Desired Closing and Opening Instants Influencing Factors on Desired Closing and Opening Instants The desired closing and opening instants depend on the load type. The most important influencing factors are described below. Capacitive and Inductive Loads 1.3.1 The influences of the load type on the desired closing and opening instants are described using the closing...
Page 13
Overview of the Function 1.3 Influencing Factors on Desired Closing and Opening Instants Closing a Grounded Capacitor Bank For each phase, the voltage across the contact gap of the circuit breaker is decisive for the selection of the correct closing instant. Each closing of a phase causes a current to flow via the earth. The target instant is the voltage zero crossing in each phase, where a time offset of the three phases is required due to the phase displacement of their zero crossings.
Page 14
Overview of the Function 1.3 Influencing Factors on Desired Closing and Opening Instants [dw_Closing instants for isolated capacitor bank, 3, en_US] Figure 1-4 Closing Instants for an Isolated Capacitor Bank (3-Phase, 50 Hz) Zero crossing of the reference voltage Closing instant for phases B and C Closing instant for phase A SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
As shown in the preceding figure, the actual time of mechanical contact is obtained via reference contacts of the circuit breaker. Reference contacts can be either specific precise sensors (for example, Hall-effect sensors of Siemens CBs) or the CB auxiliary contacts. [fo_Closing time, 2, en_US]...
As shown in the preceding figure, the actual time of mechanical separation is obtained via reference contacts of the circuit breaker. Reference contacts can be either specific precise sensors (for example, Hall-effect sensors of Siemens CBs) or the CB auxiliary contacts. [fo_Break time, 2, en_US] Compensation of the Mechanical Operating Times 1.4.2...
Application Environment of the SIPROTEC 5 Device with the Point-On-Wave Switching Function As reference contacts for third-party circuit breakers As reference contacts for Siemens circuit breakers The application can comprise the following primary, secondary, and auxiliary equipment, some of which is optional: •...
Page 18
Hall-effect Sensors (only for Siemens Circuit-Breaker, as Reference Contacts) In case of Siemens circuit breakers, the mechanical make/break time is detected via Hall-effect sensors with high precision. The Hall-effect sensors are connected to the device via fast measuring-transducer inputs.
Overview of the Function 1.6 Applications Applications Reactance Coil 1.6.1 Closing Closing a reactance coil can result in large current asymmetry between phases and overvoltage, which might cause the maloperation of protection devices. To avoid this problem in grounded systems, for example, the Point-on-wave switching function can energize the reactance coil at the current zero crossing, that is, at the maximum reference voltage.
Overview of the Function 1.6 Applications [dw_Shunt reactor,1-phase VM, 2, en_US] Figure 1-9 Reactance Coil, 1-Phase Voltage Measurement for Reference Signal For switching-accuracy supervision Reference Voltage Connection A reference voltage must be connected to the Point-on-wave switching function for detecting the zero crossing of the power-system voltage.
Overview of the Function 1.6 Applications be used as the reference voltage. For more information about the reference voltage connection via the measuring point V-3ph or V-1ph, refer to 3.1.3 Reference Signal. Switching-Accuracy Supervision For capacitor banks, the 3-phase feeder current of the circuit breaker is used for the switching-accuracy supervision in the Open CB and Close CB stages.
Overview of the Function 1.6 Applications 1-phase busbar voltage as reference signal For switching-accuracy supervision of the Open CB stage and for recording the inrush current Reference Voltage Connection A reference voltage must be connected to the Point-on-wave switching function for detecting the zero crossing of the power-system voltage.
Page 23
Overview of the Function 1.6 Applications VA or VAB as reference signal For switching-accuracy supervision Reference Voltage Connection A reference voltage must be connected to the Point-on-wave switching function for detecting the zero crossing of the power-system voltage. For the transmission line, a 3-phase busbar voltage is used as the reference voltage.
Overview of the Function 1.7 Possible Device Types and Device Applications Possible Device Types and Device Applications The Point-on-wave switching function can be applied in the following SIPROTEC 5 device types: 6MD86, 7SJ85, 7SA87, 7SD87, 7SL87, 7VK87, 7UT85, 7UT86, 7UT87, 6MU85, 7UM85. Three different device applications are possible: •...
Overview of the Function 1.8 Point-On-Wave Switching Processing Point-On-Wave Switching Processing The Point-on-wave switching function calculates the switching times for the binary outputs of the device for each phase based on the relevant settings and on the compensated operating time. The switching procedures are described below using the example of closing and opening a grounded reac- tance coil.
Overview of the Function 1.8 Point-On-Wave Switching Processing [dw_Closing instants for grounded shunt reactor, 2, en_US] Figure 1-13 Closing Instants for a Grounded Reactance Coil (3-Phase, 50 Hz) Controlled closing of an earthed reactance coil reduces inrush currents for an optimized closing operation, compared with a non-optimized closing operation (see the figure below).
Page 27
Overview of the Function 1.8 Point-On-Wave Switching Processing • With opening the open trip coil, the circuit-breaker opening time starts. • The mechanical separation occurs after the opening time has passed and the current still flows because of the arcing. •...
Structure and Interfaces of the Function Structure and Interface Overview Interaction with the Control and Circuit-Breaker Functionality Interaction with Other Functions SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
Structure and Interfaces of the Function 2.1 Structure and Interface Overview Structure and Interface Overview The Point-on-wave switching function can be used in the Circuit breaker function group for 1-pole and 3‑pole switching. The function comes factory-set with one Open CB stage and one Close CB stage. A maximum of 1 Open CB stage and 1 Close CB stage can be operated simultaneously in the function.
Page 31
Structure and Interfaces of the Function 2.1 Structure and Interface Overview The Point-on-wave switching function has interfaces to: • Measuring points The Point-on-wave switching function obtains the busbar voltage as a reference voltage for zero- crossing detection via the Vsync interface of the connected measuring point. For more information, refer 3.1.3 Reference Signal.
Structure and Interfaces of the Function 2.2 Interaction with the Control and Circuit-Breaker Functionality Interaction with the Control and Circuit-Breaker Functionality [dw_Control function blocks PoW, 2, en_US] Figure 2-3 Interaction with the Control and Circuit-Breaker Functionality When processing a switching command, the Point-on-wave switching function can be in 2 states: •...
Structure and Interfaces of the Function 2.2 Interaction with the Control and Circuit-Breaker Functionality Application and Setting Notes 2.2.1 To ensure the accuracy of the switching times, the following signals of the FB Circuit breaker must be routed to high-speed outputs: •...
Structure and Interfaces of the Function 2.3 Interaction with Other Functions Interaction with Other Functions Automatic reclosing The Automatic reclosing function does not cooperate with the Point-on-wave switching function. This means that the Point-on-wave switching function does not process the close command of the Automatic reclosing function.
Page 35
Structure and Interfaces of the Function 2.3 Interaction with Other Functions Circuit-Breaker Restrike Protection In the plausibility-release logic of the Circuit-Breaker Restrike Protection function, the following phase- segregated trip commands of the Point-on-wave switching function trigger the logic of the trip command: •...
General Functionality Description Application and Setting Notes Settings Information List SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
General Functionality 3.1 Description Description Overview and General Description 3.1.1 Overview The general functionality provides the following functions: • Determination of switching angles • Zero-crossing detection based on the reference signal • Measuring-transducer configuration for the acquisition of the process and environmental data •...
General Functionality 3.1 Description Logic [lo_PoW FB General, 3, en_US] Figure 3-1 Logic Diagram of the General Functionality 3.1.2 Determination of Switching Angles The optimum switching instants depend on the switching application (load type) and the switching direction. A further criterion for selecting the correct switching instant is whether the system is grounded or isolated. For the calculation of the phase switching times, the voltage of phase A is the internally used reference phase.
General Functionality 3.1 Description The following applications can be selected: • Capacitive load • Transmission line • Reactance coil • Transformer (YNd, Yd) • User-defined The following table provides the switching angles of different applications or loads. Each angle in the table means an offset angle to the zero-crossing point of the phase A voltage.
General Functionality 3.1 Description [sc_MP V1ph routing, 2, en_US] Figure 3-2 Routing of Measuring Point V-1ph The reference voltage must be connected to the voltage interface Vsync1 of FG Circuit breaker. Conse- quently, you must connect the measuring point that represents the reference voltage to the Vsync1 interface, as shown in the following figure.
General Functionality 3.1 Description [dw_Zero crossing detection, 2, en_US] Figure 3-4 Zero-Crossing Determination The zero-crossing time t is determined accurately with a linear interpolation with one sample before the zero crossing (V at t ) and one sample after the zero crossing (V at t [fo_Zero crossing determination, 2, en_US] The Zero crossing direction can be rising (V...
Page 43
Supervision. NOTE To acquire circuit breaker reference contacts from Siemens, you must select fast measuring transducer inputs (available on the I/O module IO218). All available measuring transducers in the scope of hardware are visible in the function group Analog units.
Page 44
General Functionality 3.1 Description Parameter Setting Value Fast voltage inputs for measuring the control voltage Top limiting value of the control voltage in V Upper limit Lowest limiting value of the control voltage in V Lower limit Sensor The calculated measured value if the input current or the voltage corre- Upper limit - Sensor sponds to the value set in the Upper limit parameter.
MT Configuration Control Voltage, Page In the configuration, Siemens recommends the value 0.02 for the Upper limit - Sensor parameter and the value 0.00 for the Lower limit - Sensor parameter (with the unit A).
Page 46
General Functionality 3.1 Description Zero-Crossing Supervision of the Reference Phase Figure 3-8 shows the zero-crossing supervision of the reference phase. [lo_PoW_Supervision_zero crossing, 2, en_US] Figure 3-8 Logic of the Zero-Crossing Supervision of the Reference Phase Error zero crossing signal is generated if at least one of the following conditions is met: •...
General Functionality 3.1 Description 3.1.6.2 Supervision of the Circuit-Breaker Switch Position Unless otherwise specified, this supervision function is active if the Mode parameter for at least one of the stages Close CB and Open CB is set to on or test. Figure 3-9 shows the possible states of the circuit-breaker poles when the circuit-breaker switch position is determined via 2 circuit-breaker auxiliary contacts.
Page 48
General Functionality 3.1 Description Table 3-3 Process and Environmental Data Acquired from the Input and Output Module IO218 Data Data Acquisition Supervision Control voltage of the closing circuit Data quality is valid; for example, no overflow or wire break was detected and the voltage is in the allowed Control voltage of the opening circuit range.
Page 49
General Functionality 3.1 Description Hydraulic Pressure [lo_PoW_Supervision_hydraulic_pressure, 2, en_US] Figure 3-14 Logic of the Pressure Supervision Control voltage of the opening circuit [lo_PoW_Supervision_V open, 2, en_US] Figure 3-15 Logic of the Control Voltage Supervision of the Opening Circuit SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
Page 50
General Functionality 3.1 Description Control voltage of the closing circuit [lo_PoW_Supervision_V close, 2, en_US] Figure 3-16 Logic of the Control Voltage Supervision of the Closing Circuit Reference Contact Inputs [lo_PoW_Supervision_ref input, 2, en_US] Figure 3-17 Logic of the Reference Contact Inputs Group Indication: Defect sensor Each defect of a sensor leads to a group fault indication Defect sensor .
General Functionality 3.1 Description [lo_PoW_Supervision_sensor_defect, 2, en_US] Figure 3-18 Logic of the Message Defect sensor 3.1.6.4 Supervision-Error Reaction When device errors occur and the corresponding supervision functions pick up, this is displayed on the device and also indicated. Device errors can lead to corruption of data and signals. These data items and signals are marked and tagged as invalid, so that affected functions automatically transition to a secure state.
General Functionality 3.1 Description Error Class Type 1 Type 2 Type 3 Type 4 States of the FB Open CB and the FB FB inactive FB active FB active FB inactive Close CB Health = Health = Health = Ok Health = Ok Alarm Warning...
Page 53
General Functionality 3.1 Description [lo_PoW Closing possible, 2, en_US] Figure 3-20 Logic of Issuing the Internal Signal PoW closing possible [lo_PoW Capability, 2, en_US] Figure 3-21 Logic of the Determination of the Availability of the Point-on-wave switching Function SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
(rising or falling). Minimizing peak inrush currents on frequently switched transformers will extend transformer life. For all other applications, Siemens recommends using the preset value both for a quick determination of the zero crossing point.
Page 55
= 50 Hz rated With these parameters, you define the limits of the frequency at which the function operates. Siemens recommends using the default settings of these parameters. Parameter: ΔT zero crossing min., ΔT zero crossing max., Min. reference voltage, Zero-crossing sup.
Page 56
• Default setting (_:2311:119) MT for ref. contact phsC = None These settings are only applicable for Siemens circuit breakers with mechanical contact detection via Hall‑effect sensors. To acquire Siemens circuit breaker reference contacts, you must select fast measuring transducer inputs (available on the I/O module IO218).
Page 58
General Functionality 3.3 Settings Addr. Parameter Setting Options Default Setting _:2311:135 General:Zero-crossing 0.00 s to 60.00 s 0.10 s sup. T-hold _:2311:136 General:CB interm.pos. 0.00 s to 300.00 s 5.00 s max. time _:2311:104 General:MT for tempera- Setting options depend on ture configuration _:2311:106...
General Functionality 3.4 Information List Information List Information Data Class Type (Type) General _:2311:500 General:>CB closed phsA _:2311:501 General:>CB closed phsB _:2311:502 General:>CB closed phsC _:2311:81 General:>Ref. signal connected _:2311:82 General:>Block ref. signal sup. _:2311:316 General:Defect sensor _:2311:332 General:Defect V open.cir.sens _:2311:333 General:Defect V clos.cir.sens _:2311:308...
CB Opening Stage 4.1 Description Description Overview and General Description 4.1.1 Overview The Open CB stage provides the following subfunctions: • General Stage Control • Start of the Switching Operation • Calculation of the opening time stamps and circuit-breaker opening process •...
Page 63
CB Opening Stage 4.1 Description In the following conditions, the 3-pole switching allowed parameter does not affect the normal 3-pole switching: • The stage is configured but switched off (Mode is off). • The stage is configured and switched on (Mode is on or test) but blocked by the input signal >Block function .
CB Opening Stage 4.1 Description Start of the Switching Operation The switching operation can be started via either of the following options: • Via the trip command from the function block Control • Via the binary input signal >Open CB When the stage is tripped via >Open CB , the stage checks the circuit-breaker switch position.
Page 65
CB Opening Stage 4.1 Description [fo_Full compensation per phase, 2, en_US] With: • is specified by the CB opening time phsA parameter. Open setting, A • With the parameter CB correction time phsA, you specify t . The automatically calculated corr, A optimum opening time can be adjusted with this correction time (in ms) in order to compensate for deviations detected during operation (during commissioning).
CB Opening Stage 4.1 Description Compensation 4.1.3 4.1.3.1 Compensation of the Ambient Temperature Influence By measuring the ambient temperature, the Point-on-wave switching function can compensate the influence of the ambient temperature on the circuit breaker switching time. With the parameter Temperature compensat., you can select one of the following methods for compen- sation: •...
CB Opening Stage 4.1 Description [sc_Curve setting, 2, en_US] Figure 4-6 Setting Example of the Parameter Temper.-compens. curve In this compensation, the compensation time t is calculated as follows: Comp(temp) – t Comp(temp) Actual With: • is the opening time at the reference temperature (T ) specified by the Reference temperature parameter.
CB Opening Stage 4.1 Description Linear Compensation In the linear compensation, the compensation time t is calculated as follows: Comp(volt) = (V – V ) ⋅ K Comp(volt) Actual Comp(volt) With: • is the currently measured voltage (actual value). Actual •...
Measured Opening and Break Time • The actual opening time is measured either via the fast measuring transducer input (Hall-effect sensor measuring transducer, only for Siemens circuit breakers) or via the binary inputs >CB closed phsx connected to the CB-closed auxiliary contacts.
Page 70
CB Opening Stage 4.1 Description Calculated Time Differences The Switching-accuracy supervision function determines the following time differences: • Time difference between the calculated and the measured opening time per phase • Time difference between the calculated and the measured break time per phase Calculated, measured, and delta times are also available as functional values.
CB Opening Stage 4.2 Application and Setting Notes Application and Setting Notes Start of the Switching Operation If the bay controller and the Point-on-wave switching function are in the same device, the switching opera- tion can be started via the trip command from the FB Control. If the bay controller and the Point-on-wave switching function are in different devices, the switching opera- tion can be started via the input signal >Open CB .
Page 72
Supervision). The type of reference contact depends on the circuit-breaker manufacturer: • Siemens circuit breakers: Siemens circuit breakers contain a measuring transducer for a CB-integrated Hall‑effect sensor. In this case, 3 fast measuring transducer inputs are required. To configure the measuring transducer reference contacts, follow the instructions under 3.1.5 Measuring Transducer Configuration for the...
Page 73
0.05 A for example. If no special requirements exist, Siemens recommends using the setting value of 0.10 A. Signal: Ref.cont.duration phsA, Ref.cont.duration phsB, Ref.cont.duration phsC These signals are available only when the parameters MT for ref.
CB Opening Stage 4.3 Settings Settings Addr. Parameter Setting Options Default Setting General • _:20671:1 Opening:Mode • • test • _:20671:102 Opening:3-pole switching allowed • CB data _:20671:105 Opening:CB opening 0.0 ms to 200.0 ms 0.0 ms time phsA _:20671:106 Opening:CB opening 0.0 ms to 200.0 ms 0.0 ms...
CB Opening Stage 4.4 Information List Information List Information Data Class Type (Type) Opening _:20671:82 Opening:>Block function _:20671:501 Opening:>Open CB _:20671:54 Opening:Inactive _:20671:52 Opening:Behavior _:20671:53 Opening:Health _:20671:55 Opening:Start _:20671:338 Opening:CB position wrong _:20671:310 Opening:Mech.ref.contact phsA _:20671:311 Opening:Mech.ref.contact phsB _:20671:312 Opening:Mech.ref.contact phsC _:20671:301 Opening:Max.
CB Closing Stage 5.1 Description Description Overview and General Description 5.1.1 Overview The CB closing stage provides the following subfunctions: • General Stage Control • Start of the Switching Operation • Calculation of the closing time stamps and circuit-breaker closing process •...
Page 79
CB Closing Stage 5.1 Description In the following conditions, the 3-pole switching allowed parameter does not affect the normal 3-pole switching: • The stage is configured but switched off (Mode is off). • The stage is configured and switched on (Mode is on or test) but blocked by the input signal >Block function .
CB Closing Stage 5.1 Description Start of the Switching Operation The switching operation can be started via either of the following options: • Via the close command from the FB Control • Via the binary input signal >Close CB When the stage is tripped via >Close CB , the stage checks the circuit-breaker switch position.
Page 81
CB Closing Stage 5.1 Description [fo_Full compensation per phase_close, 2, en_US] With: • is specified by the CB closing time phsA parameter. Close setting, A • With the parameter CB correction time phsA, you specify t . The automatically calculated corr, A optimum closing time can be adjusted with this correction time (in ms) in order to compensate for deviations detected during operation (during commissioning).
CB Closing Stage 5.1 Description [dw_CB closing_voltage, 2, en_US] Figure 5-5 Circuit-Breaker Closing Process for the Application Type of the Transformer The descriptions of Legends 1, 2, and 3 in this figure are the same as those in the preceding figure. Compensation 5.1.3 5.1.3.1...
Page 83
CB Closing Stage 5.1 Description [dw_Opening time acc. temp, 2, en_US] Figure 5-6 Compensation Characteristics The slope of the line in the figure is specified by the Temperature comp. factor parameter, which is usually a negative value. Compensation by User-Defined Characteristic Curve With the user-defined characteristic curve of the temperature, you can define the characteristic curve point by point, using up to 30 value pairs of temperature and time.
CB Closing Stage 5.1 Description [dw_Operate time by temp, 2, en_US] Figure 5-8 Compensation Characteristics Compensation of the Control Voltage Magnitude Influence 5.1.3.2 By measuring the control voltage, the Point-on-wave switching function can compensate the influence of the control voltage on the circuit breaker switching time. With the parameter Clos.circuit volt.compens., you can select one of the following methods for compensation: •...
CB Closing Stage 5.1 Description 5.1.3.3 Compensation of the Hydraulic-Pressure Influence By measuring the phase-selective hydraulic pressure, the Point-on-wave switching function can compensate the influence of the hydraulic pressure on the circuit breaker switching time per phase. With the Hydr. pressure compens. parameter, you can select whether or not you want to perform linear compensation of the hydraulic pressure.
Measured Closing and Make Time • The actual closing time is measured either via the fast measuring transducer input (Hall-effect sensor measuring transducer, only for Siemens circuit breakers) or via the binary inputs >CB closed phsx connected to the CB-closed auxiliary contacts.
Page 87
Only in the case that the reference contact information is obtained via fast measuring transducer inputs (with Siemens circuit breakers), the signals Ref.cont.duration phsA , Ref.cont.duration phsB , and Ref.cont.duration phsC show the measured (pulse) duration of the reference contacts, from the rising edge to the falling edge.
CB Closing Stage 5.2 Application and Setting Notes Application and Setting Notes Start of the Switching Operation If the bay controller and the Point-on-wave switching function are in the same device, the switching opera- tion can be started via the close command from the FB Control. If the bay controller and the Point-on-wave switching function are in different devices, the switching opera- tion can be started via the input signal >Close CB .
Page 89
Supervision). The type of reference contact depends on the circuit-breaker manufacturer: • Siemens circuit breakers: Siemens circuit breakers contain a measuring transducer for a CB-integrated Hall‑effect sensor. In this case, 3 fast measuring transducer inputs are required. To configure the measuring transducer reference contacts, follow the instructions under 3.1.5 Measuring Transducer Configuration for the...
Page 90
81.6 V since harmonics can occur even with good circuits. Siemens recommends setting this parameter according to the evaluation of the first switching operations. The default setting can be applied until that point.
Page 91
Threshold: I too high setting, the closing operation is considered as inaccu- rate. Siemens recommends setting this parameter according to the evaluation of the first switching operations. The default setting can be applied until that point.
CB Closing Stage 5.3 Settings Settings Addr. Parameter Setting Options Default Setting General • _:20641:1 Closing:Mode • • test • _:20641:102 Closing:3-pole switching allowed • CB data _:20641:105 Closing:CB closing time 0.0 ms to 200.0 ms 0.0 ms phsA _:20641:106 Closing:CB closing time 0.0 ms to 200.0 ms 0.0 ms...
CB Closing Stage 5.4 Information List Information List Information Data Class Type (Type) General _:2311:500 General:>CB closed phsA _:2311:501 General:>CB closed phsB _:2311:502 General:>CB closed phsC _:2311:81 General:>Ref. signal connected _:2311:82 General:>Block ref. signal sup. _:2311:316 General:Defect sensor _:2311:332 General:Defect V open.cir.sens _:2311:333 General:Defect V clos.cir.sens _:2311:308...
Page 95
CB Closing Stage 5.4 Information List Information Data Class Type (Type) _:20671:302 Opening:Switching inaccurate _:20671:303 Opening:Deviation break time _:20671:304 Opening:Deviation opening time _:20671:307 Opening:Break time phsA calc. _:20671:308 Opening:Break time phsB calc. _:20671:309 Opening:Break time phsC calc. _:20671:320 Opening:Break time phsA meas. _:20671:321 Opening:Break time phsB meas.
Page 96
CB Closing Stage 5.4 Information List Information Data Class Type (Type) _:20641:321 Closing:Make time phsB meas. _:20641:322 Closing:Make time phsC meas. _:20641:323 Closing:Clos. time phsA calc. _:20641:324 Closing:Clos. time phsB calc. _:20641:325 Closing:Clos. time phsC calc. _:20641:326 Closing:Clos. time phsA meas. _:20641:327 Closing:Clos.
Sequence of Functions 6.1 Description Description The functional sequence of the stages Close CB and Open CB of the Point-on-wave switching function is similar. The following describes the sequence of the Open CB stage as an example: • The Open CB stage is triggered via a trip command or the binary input signal >Open CB .
The maximum duration is specified by a settable parameter Maximum record time. For more information about this parameter, refer to Fault Recording in the SIPROTEC 5 device manuals. Siemens recommends setting this parameter to 250 ms. Message Logging The message logs of the Point-on-wave switching function are saved in the fault logs of the device.
Requirements for Device and External Equipment 8.1 Required Device Hardware Required Device Hardware For an overview of the required physical components, refer to 1.5 Application Environment and Equipment. The following describes the details about the required secondary equipment components. The following figure provides an example of the device view in DIGSI 5 for using the Point-on-wave switching function.
Page 103
Point-on-wave switching function. If you do not require an IO218 module to detect the Siemens circuit breaker reference contacts, you can also collect the process and environmental data via an ANAI plug-in module. One ANAI plug-in module provides 4 normal measuring transducer inputs.
Requirements for Device and External Equipment 8.2 Application Template and Related Device Hardware Application Template and Related Device Hardware The bay controller 6MD86 provides the Point-on-wave switching application template. The device hardware described below supports the prerouting of this application template. The following sections describe an example of suitable device hardware.
Page 105
Requirements for Device and External Equipment 8.2 Application Template and Related Device Hardware [dw_Standard variants PoW, 4, en_US] Figure 8-2 Sequence of Modules and Terminal Overview of the Device Hardware for the Application Template SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
Technical Data General Device Data For more information about the general device data, refer to Technical Data in the Hardware Manual. Setting Values for the General Functionality Phase shift opening phs 0° to 720° Increments of 1° Phase shift closing phs V open.
Page 108
Technical Data Open. time: allowed diff. 0.0 ms to 20.0 ms; ∞ Increments of 0.1 ms Break time: allowed diff. Clos. time: allowed diff. Make time: allowed diff. Make-time detec. V> phs 0.300 V to 340.000 V Increments of 0.001 V Threshold: V too high Threshold: I too high 1 A @ 100 Irated...
Page 109
Technical Data Phase-selective reference-contact duration 125 μs Phase-selective maximum current or voltage 1.5 % of the measured value SIPROTEC 5, Point-On-Wave Switching, Manual C53000-H5040-C082-5, Edition 02.2024...
Ordering a Device with the Point-on-Wave Switching Function To order a device with the Point-on-wave switching function, proceed as follows: Open the SIPROTEC 5 order configurator under https://w3.siemens.com/smartgrid/global/en/products- ² systems-solutions/Protection/Pages/protection-relay-configurator.aspx. In the order configurator, access the order page of the device.
Need help?
Do you have a question about the SIPROTEC 5 V9.70 and is the answer not in the manual?
Questions and answers