Stall Prevention Level during Acceleration (n56)
Set the operation level of a function to stop the acceleration of
the motor automatically for stall prevention during acceleration.
Set this value in percentage based on the rated output current of
the Inverter as 100%.
Value
Name
n56
Stall Prevention Level
during Acceleration
Stall Prevention during Acceleration
Output
current
Output
frequency
Stall Prevention Level during Operation (n57)
Select the operation level of a function to reduce the output fre-
quency of the Inverter automatically for stall prevention during
operation. Set this value in percentage based on the rated output
current of the Inverter as 100%.
Value
Name
n57
Stall Prevention Level
during Operation
Stall Prevention during Operation
Output
current
Output
frequency
Frequency Detection Level (n58)
Set the frequency to be detected.
Note: When frequency detection 1 and 2 are to be output, n40
(multi-function output) must be set.
Value
Name
n58
Frequency Detection
Level
Function of Each Parameter
Setting
Unit of
Default
range
setting
settings
30 to 200
1%
170
n56
Time
The output frequency is
controlled so that the
Inverter will not stall.
Time
Setting
Unit of
Default
range
setting
settings
30 to 200
1%
160
n57
Time
The output frequency is
controlled so that the
Inverter will not stall.
Time
Setting
Unit of
Default
range
setting
settings
0.0 to 400
0.1 Hz
0.0
Overtorque Detection Function Selection
(n59 to n61)
Set n59 to enable or disable overtorque detection and select the
processing to be performed after overtorque detection.
Value
0
Inverter does not monitor overtorque.
1
Inverter monitors overtorque only when speed is matched.
It continues operation (issues warning) even after overtorque is
detected.
2
Inverter monitors overtorque only when speed is matched.
It discontinues operation (through protective function) when
overtorque is detected.
3
Inverter always monitors overtorque during operation.
It continues operation (issues warning) even after overtorque is
detected.
4
Inverter always monitors overtorque during operation.
It discontinues operation (through protective function) when
overtorque is detected.
Set the overtorque detection level in n60 and the overtorque
detection time in n61.
Value
Name
n60
Overtorque Detection
Level
n61
Overtorque Detection
Time
Note: 1. In n60, set the overtorque detection level in percentage
based on the rated output current of the Inverter as 100%.
2. In n61, set the overtorque detection time in 0.1-s increments.
Overtorque Detection
Output
current
Overtorque
detection
(NO)
Note: Overtorque detection will be canceled if the out-
put current decreases from the detection level by
approximately 5% of the Inverter rated current.
Description
Setting
Unit of
range
setting
30 to 200
1%
0.1 to 10.0
0.1 s
See note.
n60
n61
Default
set-
tings
160
0.1
Time
Time
19