SiUS122226EA

7.18 Electrical Box Temperature Rise

L3
Error Code
Outdoor Unit LED
A j 1 i 2 i 3 h 4 i 5 h
Display
Method of Error
An electrical box temperature rise is detected by checking the radiation fin thermistor with the
Detection
compressor off.
Error Decision
 With the compressor off, the radiation fin temperature is above A.
Conditions
 The error is cleared when the temperature drops below B.
 To cool the electrical components, the outdoor fan starts when the radiation fin temperature
A
B
C
Supposed
 Defective outdoor fan motor
Causes
 Short circuit
 Defective radiation fin thermistor
 Disconnection of connector
 Defective outdoor unit PCB
Troubleshooting
Part 6 Service Diagnosis
rises above C and stops when the radiation fin temperature drops below B.
2/3/4MXS
°C
°F
100
212
70
158
85
185
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Turn off the power. Then, turn on
the power to restart the system.
Error again or
outdoor fan activated?
NO
Check No. 19
Check the outdoor fan.
OK
Radiation fin
dirty?
YES
5MXS
2/3MXL(H)
°C
°F
°C
70
158
100
60
140
70
70
158
85
YES
Check the radiation fin
temperature.
Above A?
YES
NG
NO
Troubleshooting for Outdoor Unit
4MXL(H)
°F
°C
°F
212
70
158
158
60
140
185
70
158
NO
Replace the outdoor unit
PCB (main PCB).
Replace the outdoor fan
motor.
Correct the connectors
and fan motor lead wire.
Replace the outdoor unit
PCB (main PCB).
Check the installation
condition.
Go to Check No. 17.
Clean up the radiation fin.
R6000426
219