Troubleshooting for Outdoor Unit
7.15 Compressor Sensor System Abnormality
H0
Error Code
Outdoor Unit LED
A j 1 i 2 i 3 h 4 h 5 h
Display
Method of Error
The system checks the power supply voltage and the DC voltage before the compressor starts.
Detection
The system checks the DC current of the compressor right after the compressor starts.
Error Decision
The power supply voltage and the DC voltage is obviously low or high.
The DC current of the compressor does not flow when the compressor starts.
Conditions
Supposed
Disconnection of reactor
Disconnection of compressor harness
Causes
Defective outdoor unit PCB
Defective compressor
212
+
Power
DC voltage
Module
–
DC current
Compressor
SiUS122226EA
PCB
(R22001)
Part 6 Service Diagnosis