Filter - Beckhoff EP4378-1022 Manual

Ethercat box with 4 analog inputs, 4 analog outputs, 8 digital inputs/ outputs
Table of Contents

Advertisement

Commissioning and configuration
5.2.4

Filter

The measured value of each analog input can be filtered with a digital filter.
5.2.4.1
Enable filter
Measured value jumps when enabling or disabling filters
When filters are enabled or disabled, short-term measured value jumps can occur in the process data that
do not correspond to the physical values.
You can enable the filter individually for each input. All filters are disabled in the factory setting.
Enable the filter by setting the following CoE parameters to TRUE:
Connection
X01
X02
X05
X06
The enabling of filters also affects the synchronization mode:
• If all filters are disabled, the device runs in the synchronization mode "Synchron with SM event"
• If one or more filters are enabled, the device runs in the synchronization mode "Free Run".
Example
Fig. 17: "Enable filter" CoE parameter for the analog input at connection X01
48
NOTICE
CoE object
8100
AI Settings Ch.1
hex
8110
AI Settings Ch.2
hex
8120
AI Settings Ch.3
hex
8130
AI Settings Ch.4
hex
Version: 1.4
Parameter
06
Enable Filter
06
Enable Filter
06
Enable Filter
06
Enable Filter
EP4378-1022