Heat management process

DocuTech 61xx Installation Planning Guide
Use the following table to find the appropriate system and
venting configuration in the column labeled: Replaced system.
Read across that row to find the Heat output for that system.
Record this value on the Heat Management Worksheet.
Table 4-7. Copier heat output
Replaced system
9900 Vented
9900 Unvented
5090 Vented
5090 Unvented
9700 Vented
9700 Unvented
9500 Vented
9500 Unvented
1090 Unvented
EK235â Unvented
EK250â Unvented
EK300â Unvented
NOTE: Vented heat output values assume a vented airflow of
200 CFMs.
The procedure that follows describes the heat management
assessment process.
1. Assess current conditions: Consider the following items when
assessing the current conditions:
Maximum heat load in the room with existing equipment.
High outside temperatures.
Properly functioning HVAC.
2. Determine acceptable maximum temperature: Consider the
following items when determining the maximum acceptable
temperature:
Operator comfort and safety.
Select and prepare an installation site
Heat output (BTU per
hr.)
17,000
25,000
19,000
27,000
24,000
31,000
17,000
24,000
12,000
14,000
22,000
22,000
4-17