Cabling Requirements - Xerox 4050 Installation Planning

Laser printing systems
Hide thumbs Also See for 4050:
Table of Contents

Advertisement

4090/4650

Cabling requirements

XEROX 4050/4090/4450/4650 LPS INSTALLATION PLANNING
The environmental and electrical requirements for the 4090 and
4650 LPS are listed in tables 1-17 and 1-18
Table 1-17.
Operating temperature
Humidity
Heat dissipation, online
Heat dissipation, offline
Table 1-18.
System controller
Printer
Agency certification
The printer and the system controller can be separated by up to
25 ft/7.6 m. The system controller is delivered with a 50 ft/
15.5 m interface cable and a 14 ft/4.3 m, 220 VAC power cable.
The printer is delivered with a 10 ft/3 m, 220 VAC power cable.
The power cable for the terminal is 15 ft/4.7 m long. The
terminal must sit within 15 ft/4.7 m of the system controller, if
not directly on it. The power source (wall or beneath flooring)
for the terminal must be within the maximum 15 ft/4.7 m length
of the power cable.
Environmental requirements
Normal: 68° F to 76° F/20° C to 24° C
Minimum: 60° F/16° C
Maximum: 80° F/27° C
Normal: 45 +/- 10%
Minimum: 30%
Maximum: 60%
Operating:
15,000 BTU per hour
Standby:
7,500 BTU per hour
Operating:
15,500 BTU per hour
Standby:
8,000 BTU per hour
Electrical requirements
120/208 or 120/240 VAC; 50/60 Hz,
20 amp service, NEMA L14-20R
1.8 KVA both in standby mode and when
operating
Note: Magnetic tape unit assumed
(maximum draw)
U.S./Canada, 60 Hz: 120/208 or 120/240
VAC; 20 amp service, NEMA 14-30R
.875 KVA in standby, 3.1 when operating
International, 50 Hz:
220/240 VAC or 380 VAC
UL, CSA, IEC