ELECTRICAL HAZARD
Failure to follow this warning
could result in personal injury
or death.
WAIT TWO (2) MINUTES
after disconnecting power prior
to touching electrical
components as they may hold
a dangerous charge of
400VDC, then verify DC
Voltage is less than 42 VDC at
inverter test points labeled
+DC and -DC before servicing
board.
Approved Combinations for Variable Speed Units running in
American Standard Link mode
UX360 Smart Thermostat
SC360 System Controller
Approved System Accessories
TAMX
S8V2xxxxxxVC
Note: See AHRI directory for approved indoor and outdoor model
combinations. Only Trane / American Standard coils and air
handlers are approved for use with variable speed outdoor unit.
Table 1. Operating Range
Cooling
Heating
11-BC47D1-1A-EN
WARNING
400 VOLTS
DC-
DC+
45° F to 120° F
-10° F to 66° F
Important: Use caution when cleaning outdoor coil to ensure no
water enters the electrical control compartment. When
cleaning coil from inside the compressor compartment,
take special care not to spray water towards the top rows
of the coil near the control panel. Water may enter the
control compartment and drive damaging the
electronics. Disconnect all electric power, including
remote disconnects before servicing.