2) Motor 150%-overload time limit
The motor 150%-overload time limit parameter
the motor trips under a load of 150% (overload trip
Operation frequency
0.01 [Hz](*1)
Motor overload
withstanding time [s]
Motor 150%-overload
time limit
0
×0.6×1.1
Title
3) Inverter overload characteristic
This function is provided to protect the inverter itself and it cannot be changed or
disabled by changing any parameter setting.
If the inverter overload trip function () is activated frequently, this condition can be
improved by changing the setting of the stall prevention level parameter to a
lower level or increasing the acceleration time or the deceleration time .
Inverter overload
withstanding time
Operation frequency
no less than
×1.1
Function
Motor 150%-overload time limit
[s]
60
0
* If the load applied to the inverter exceeds 120% of its rated load or the
operation frequency is less than 0.1Hz, the inverter may trip in a shorter time.
Inverter's overload protective characteristic
is used to set the time elapsed before
) within a range of 10 to 2400 seconds.
[Example: setting of ]
Monitored output
current [%]
=
=
68
34
70
35
80
40
90
45
100
50
112
56
120
60
130
65
140
70
150
75
200
100
Monitored output current [%]
×1.5
to [s]
Output
current
[%]
106
110
115
120
120
140
150
180
105%
120%
100%: Inverter's rated output current
E-27
Motor overload withstanding time [s]
(Outline data)
=
≦
[Hz]
7200
−
−
3600
1000
−
600
−
420
−
12000
310
6000
2400
270
1200
1200
230
600
800
190
400
600
170
300
270
110
135
(*1) Except for the cases of
=, [Hz]
Adjustment range
Default setting
Inverter overload withstanding time
[s] (Outline data)
200V:18.5∼55kW
200V:75∼110kW
400V:18.5∼75kW
400V:90∼315kW
900
180
90
60
6.8
3.4
2.3
0.5
Monitored output current [%]
=
≦
[Hz]
3600
−
−
1800
500
−
300
−
210
−
155
135
115
95
85
55
900
180
90
60
6
3
0.3
ー