Characteristics:
General Description:
The single channel DIN Rail Relay Output D1093S is a relay module suitable for the
switching of safety related circuits, up to SIL 3 level according to IEC61508, for high risk
industries. It provides isolation between the input and output contact.
D1093S provides 1 DPST contact for normally energized loads and
1 SPST contact for normally de-energized loads.
Diagnostic:
Line breakage detection for NE and ND load conditions.
Provides 1 SPST normally energized relay contact (closed) for fault indication.
It de-energizes (open contact) in case of load or line fault.
Function:
1 relay for safety related circuits, provides isolation between input/output/fault.
D1093S provides 1 DPST for NE loads and 1 SPST for ND loads.
SIL 3 Safety Function for NE load (de-energized in safe state) is available at
Terminal Blocks 5-6;
in this case, the safety function is met when the relay is de-energized (open contact).
SIL 3 Safety Function for ND load (energized in safe state) is available at
Terminal Blocks 7-8;
in this case, the safety function is met when the relay is energized (closed contact).
Signalling LEDs:
Power supply indication (green), relay status (yellow), line fault (red).
EMC:
Fully compliant with CE marking applicable requirements.
Front Panel and Features:
1
2
3
4
• SIL 3 according to IEC 61508
for Tproof = 10 years (10 % of total SIF)
with NE Load.
5
6
7
8
• SIL 3 according to IEC 61508
for Tproof = 7 / 10 years (10 / 20 % of total SIF)
with ND Load.
• PFDavg (1 year) 7.01 E-06, SFF 99.19 %
with NE Load.
• PFDavg (1 year) 1.14 E-05, SFF 98.14 %
with ND Load.
• Installation in Zone 2, Division 2.
PWR ON
• Line and Load open diagnostic
STATUS
in NE and ND conditions.
FAULT
• 1 DPST contact for NE load and
1 SPST contact for ND load.
• Three port isolation, Input/Output/Supply.
D1093
• EMC Compatibility to EN61000-6-2, EN61000-6-4.
• ATEX, FM & FM-C Certifications.
9 10 11 12
• TUV Certification for SIL.
• High Reliability, SMD components.
13
14
15
16
• Simplified installation using standard
DIN Rail and plug-in terminal blocks.
Ordering Information:
Model:
D1093S
Power Bus enclosure
G.M. International DTS0242-8 Page 1/4
D1093
/B
SIL 3 Relay Output Module with
Line and Load diagnostics DIN-Rail
Model D1093S
Technical Data:
Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected,
ripple within voltage limits ≤ 5 Vpp.
Current consumption @ 24 V: 25 mA typical.
Power dissipation: 0.6 W with 24 V supply voltage and fault relay energized, typical.
Max. power consumption: at 30 V supply voltage and fault relay energized, 0.9 W.
Isolation (Test Voltage):
Output/Input 2.5 KV; Output/Supply 2.5 KV; Output/Fault Output 2.5 KV;
Input/Supply 500 V; Input/Fault Output 500 V; Fault Output/Supply 500 V.
Input: 24 Vdc nom (20.4 to 27.6 Vdc) reverse polarity protected.
Current consumption @ 24 V: 50 mA with relay energized, typical.
Power dissipation: 1.2 W with 24 V input voltage and relay energized, typical.
Max. power consumption: at 27.6 V input voltage and relay energized, 1.5 W.
Output: voltage free relay contact, normally open.
Contact material: Ag Alloy (Cd free).
Contact rating: 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
DC Load breaking capacity:
V (V)
200
125
100
50
40
30
20
10
0.1
0.2
0.3
0.4 0.5
Mechanical / Electrical life: 50 * 10
Operate / Release time: 5 / 3 ms typical.
Bounce time NO / NC contact: 3 ms.
Frequency response: 10 Hz maximum.
Fault detection:
De-energized fault signal: ≤ 150 µA continuous.
De-energized open output detection: load current ≤ 50 µA.
Energized open output detection: load current ≤ 10 mA.
Fault signalling: voltage free NE SPST relay contact
(output de-energized in fault condition).
Contact rating: 3 A 250 Vac 750 VA, 3 A 125 Vdc 120 W (resistive load).
Response time: 200 ms typical.
Compatibility:
CE mark compliant, conforms to 94/9/EC Atex Directive and to
2004/108/CE EMC Directive.
Environmental conditions:
Operating: temperature limits –20 to + 60 °C,
relative humidity max 90 % non condensing, up to 35 °C.
Storage: temperature limits - 45 to + 80 °C.
Safety Description:
II 3G Ex nAC IIC T4 non-incendive electrical apparatus.
-20 °C ≤ Ta ≤ 60 °C.
Approvals: IMQ 09 ATEX 013 X conforms to EN60079-0, EN60079-15,
FM & FM-C No. 3024643, 3029921C, conforms to Class 3600, 3611, 3810 and
C22.2 No.142, C22.2 No.213, E60079-0, E60079-15.
TUV Certificate No. C-IS-183645-01, SIL 3 according to IEC 61508.
Please refer to Functional Safety Manual for SIL applications.
Proof Test Interval: 10 years for SIL3 application with NE load or 7 years with ND load
or 10 years with ND load (20 % of SIF).
Mounting: T35 DIN Rail according to EN50022.
Weight: about 160 g.
Connection: by polarized plug-in disconnect screw terminal blocks to accomodate
terminations up to 2.5 mm
.
2
Location: Safe Area/Non Hazardous Locations or Zone 2, Group IIC T4,
Class I, Division 2, Groups A, B, C, D Temperature Code T4 and
Class I, Zone 2, Group IIC, IIB, IIA T4 installation.
Protection class: IP 20.
Dimensions: Width 22.5 mm, Depth 99 mm, Height 114.5 mm.
Resistive
Load
I (A)
1
2
3
/ 1 * 10
operation, typical.
6
5
www.gmintsrl.com

Advertisement

loading
Need help?

Need help?

Do you have a question about the D1093S and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for GMI D1093S

  • Page 1 General Description: Supply: 24 Vdc nom (20 to 30 Vdc) reverse polarity protected, The single channel DIN Rail Relay Output D1093S is a relay module suitable for the ripple within voltage limits ≤ 5 Vpp. switching of safety related circuits, up to SIL 3 level according to IEC61508, for high risk Current consumption @ 24 V: 25 mA typical.
  • Page 2 Function Diagram: SAFE AREA, ZONE 2 GROUP IIC T4, NON HAZARDOUS LOCATIONS, CLASS I, DIVISION 2, GROUPS A, B, C, D T-Code T4, CLASS I, ZONE 2, GROUP IIC T4 MODEL D1093S Load Power DC/AC max. 125 Vdc, 250 Vrms...
  • Page 3 Applications: Application for D1093S - Normally Energized Condition (NE) Contacts 1-5 and 2-6: SIL 3 Function is met when contacts are in open state. + / AC Contacts 3-7: Opening of contacts can be used for monitoring Contacts 1-5 and 2-6. No SIL Function.
  • Page 4 Applications: Application for D1093S - Normally De-Energized Condition (ND) Contacts 1-5 and 2-6: Closing of contacts can be used for monitoring + / AC Contacts 3-7. No SIL Function. Contacts 3-7: SIL 3 Function is met when contacts are in closed state.