EN54-4 CERTIFIED POWER SUPPLY UNITS AES24V USER MANUAL AES24V MS40 AES24V MS150 POWER SUPPLY UNITS User manual Manual to download in PDF format on www.majorcom.fr 5 6 , c h e m i n d e l a F l a m b è r e • 3 1 3 0 0 To u l o u s e • F R A N C E • T é l . 3 3 ( 0 ) 5 6 1 3 1 8 6 8 7...
AES24V EN54-4 CERTIFIED POWER SUPPLY UNITS EN54-4 CERTIFIED POWER SUPPLY UNITS AES24V INTRODUCTION TABLE OF CONTENTS This manual includes instructions for the installation, commissioning and maintenance of this equipment. In order for the equipment to work properly, we recommend to carefully follow these instructions. 1.
In emergency operating mode : the total operating current is provided by the battery, including the current of the PA/VA amplifiers not exceeding ‘Imax b mains not present’ depending on the size of the battery. Model AES24V MS40 AES24V MS150 Imax b...
2. INSTALLATION OF YOUR EQUIPMENT 3. CONNECTION 2.1 MOUNTING 3.1 CONNECTION DIAGRAM AES24V MS40 rear panel Note : When installing the module in the rack, the protection rating must comply with fire safety standards EN 54-4/ A2: IP30. AES24V MS40 2.2 BATTERIES...
AES24V EN54-4 CERTIFIED POWER SUPPLY UNITS EN54-4 CERTIFIED POWER SUPPLY UNITS AES24V 3.2 CONNECTION SPECIFICATIONS 4. COMMISSIONING Model AES24V MS40 AES24V MS150 Mains 2.5mm² Battery 16mm² 50mm² Connect the battery wires to the terminal strip, but do not connect the battery terminals.
A battery voltage compensation system maintains the charge characteristics within the limits specified by the battery manufacturer across the entire operational temperature range. Battery low voltage cut-out : The cut-out threshold is : AES24V MS40 AES24V MS150 21.6V ±3 % 1.8 V/cell ±3 % The element causing the cut-out will be in the + position.
In order to ensure maximal and durable service, we strongly recommend that your product be maintained clean and ensure that it is installed in a dry and ventilated location. We shall in no case be liable for damages associated with improper use or incorrect maintenance of the equipment. AES24V MS40 AES24V MS150 F1 MOTHER BOARD (MAINS): RATING WARNING BREAKING CAPACITY –...
AES24V 8. TROUBLESHOOTING PROCEDURE 9. TECHNICAL SPECIFICATIONS If the Power supply does not deliver voltage : Model AES24V MS40 AES24V MS150 • Check mains presence on the mains terminal strip Dimensions (W x D x H) 483 x 395 x 89mm •...
Page 9
AES24V MS40 AES24V MS150 POWER SUPPLY UNITS User manual 5 6 , c h e m i n d e l a F l a m b è r e • 3 1 3 0 0 To u l o u s e • F R A N C E • T é l . 3 3 ( 0 ) 5 6 1 3 1 8 6 8 7...