SETTINGS
DATE & TIME
Use
arrows to enable or disable automatic Daylight Saving time adjustments. Press
Use
(+/-)
time. Press
(DST +) "Begin" - HOUR
(DST +) "Begin" - DAY
(DST +) "Begin" - MONTH
(Example: Hour=2:00, Day=2nd Sun, Month=Mar means Daylight Saving time would begin at 2:00a.m. on the 2nd
Sunday in March)
(DST -) "End" - HOUR
(DST -) "End" - DAY
(DST -) "End" - MONTH
(Example: Hour=2:00, Day=1st Sun, Month=Nov means Daylight Saving time would end at 2:00a.m. on the 1st Sunday
in November)
Timers
SETTINGS
TIMERS
Use
arrows to set preferred on delay time. Press
Note: On Delay (also known as sequential start) time, delays the starting of the motor when an automatic call to start is
received.
SETTINGS
TIMERS
Use
arrows to set desired min. run time minutes. Press
time seconds. Press
Note: Minimum Run time will begin when motor starts. If minimum run timer is set to 00:00, no run time will occur
and pump will cycle on and off via the start and stop pressure settings.
SETTINGS
TIMERS
Use
arrows to set desired restart delay time in seconds. Press
Note: The restart timer will begin when the motor stops. The motor will not start automatically until the timer expires.
The timer is intended to prevent short-cycling of the pump motor.
Pressure
SETTINGS
Use
arrows to set preferred pressure unit system (psi, bar, kPa). Press
SETTINGS
Use
arrows to set desired pump start pressure. Press
SETTINGS
Use
arrows to set desired pump stop pressure. Press
Note: Pump stop pressure must be set below the pump "churn" pressure (including minimum suction pressure), oth-
erwise the pump will run continuously once started.

DAYLIGHT SAVING

arrows to set number of minutes to adjust for at the beginning or end of Daylight Saving
to confi rm.
Use
arrows to set the hour of day that Daylight Saving time begins. Press
to confi rm.
Use
arrows to set the day of the month that Daylight Saving time begins.
Press
to confi rm.
Use
arrows to set the month of the year that Daylight Saving time begins.
Press
to confi rm.
Use
arrows to set the hour of day that Daylight Saving time ends. Press
confi rm.
Use
arrows to set the day of the month that Daylight Saving time ends.
Press
to confi rm.
Use
arrows to set the month of the year that Daylight Saving time ends.
Press
to confi rm.
ON DELAY
MIN RUN
to confi rm.
RESTART
UNITS
PRESSURE
PRESSURE

START

PRESSURE

STOP

1
1
to confi rm.
1
key and use
1
to confi rm.
1
1
to confi rm.
1
to confi rm.
8
to confi rm.
keys to set desired min. run
to confi rm.
to