Troubleshooting
48
8.3
Confirming messages
Depending on the settings for the ALARM DISPL. TIME and ACK. ALARM MODE parameters, the
following measures should be taken to clear a message:
1)
Settings
– ALARM DISPL. TIME = 0 s
– ACK. ALARM MODE = off
– ALARM DISPL. TIME > 0 s
– ACK. ALARM MODE = off
– ALARM DISPL. TIME = 0 s
– ACK. ALARM MODE = on
– ALARM DISPL. TIME > 0 s
– ACK. ALARM MODE = on
1)
Menu path for ALARM DISPL. TIME and ACK. ALARM MODE: (GROUP SELECTION
→
→
DIAGNOSTICS
MESSAGES
If the onsite display displays a message, you can suppress it with the F key.
If there are several messages, the onsite display shows the message which has the highest priority
(→ ä 39). Once you have suppressed this message using the F key, the message with the next
highest priority is displayed. You can use the F key to suppress each message, one after the other.
The ALARM STATUS parameter continues to display all the messages present.
Cerabar S PMP71 with 4 to 20 mA HART
Measures
– Rectify cause of the message (→ ä 39).
– Rectify cause of the message (→ ä 39).
– Wait for the alarm display time to elapse.
– Rectify cause of the message (→ ä 39).
– Confirm message using ACK. ALARM parameter.
– Rectify cause of the message (→ ä 39).
– Confirm message using ACK. ALARM parameter.
– Wait for the alarm display time to elapse. If a message appears and the alarm
display time elapses before the message has been acknowledged, the message
will be cleared once it has been acknowledged.
→
] OPERATING MENU
Endress+Hauser