In the case of inflow control, the valve is controlled by relay K3. The relay K1 de-energizes when the level falls below the electrode E1. The relay K4 de-energizes when the level rises above the electrode E4. connection plan: flow control: inflow control: Function: NS43V 11880-0703-00 Page 4 / 12 www.ziehl.de...
Page 5
The relay K1 de-energizes when the level falls below the electrode E1. The relay K4 de-energizes when the level rises above the electrode E4. connection plan: Function: NS43V 11880-0703-00 Page 5 / 12 www.ziehl.de...
Page 6
The outflow valve is controlled by relay K1 between the electrodes E1 and E2. The inflow valve is controlled by relay K2 between the electrodes E2 and E3. The relays K3 and K4 de-energize when the level rises above the electrode E4. connection plan: Function: NS43V 11880-0703-00 Page 6 / 12 www.ziehl.de...
Page 7
When not submerged, the relays are de-energized. When an electrode is immersed, the associated relay energizes after the d delay has elapsed. The adjustable time d delays the relays when energizing relay relay and when de-energizing. connection plan: Function: NS43V 11880-0703-00 Page 7 / 12 www.ziehl.de...
Page 8
Pr 6: Swimming pool controller for overflow pool connection plan: Function: a) Filter release b) Filter forced shutdown c) Hydraulic shut off valve EIN d) Fresh water inflow EI NS43V 11880-0703-00 Page 8 / 12 www.ziehl.de...
• Commissioning first with setting for maximum resistance (Poti R on right stop) liquid • in case of malfunctions due to excessive cable lengths (cable capacity) or wetting with foam, reduce resistance (turn Poti R to the left) liquid NS43V 11880-0703-00 Page 9 / 12 www.ziehl.de...
If all four relay LEDs (K1 - K4) and two red LEDs (E1, E4) flash, no valid program is selected. Check the switch position of the DIP switches. → In the case of other errors, send in the device with error information for review. NS43V 11880-0703-00 Page 10 / 12 www.ziehl.de...
Connection cross-section – solid-core 1x0.14mm² to 1.5mm² each fine wire with ferrules Degree of protection (EN60529) Housing / IP 30 /IP 20 Terminals Fitting position app. 250 g Weight Subject to technical changes NS43V 11880-0703-00 Page 11 / 12 www.ziehl.de...
12 Disposal Disposal should be carried out properly and in an environmentally friendly manner in accordance with legal provisions. ZIEHL is registered with the EAR Foundation under WEEE no.: DE 49 698 543. NS43V 11880-0703-00 Page 12 / 12...