• INSTALLATION INSTRUCTIONS (For Outdoor Unit) for 85264189993002 and 85264190214003
MODEL
G The illustration in "5-5. Wiring Instructions for the Outdoor Unit (Fig. 31)"
in the installation instructions (For Outdoor Unit) was corrected as shown below.
Indoor unit A
A is the indoor unit with
refrigerant tubing that is
connected to service valve
A (bottom) of the outdoor unit.
Terminal board
Indoor unit B
B is the indoor unit with
refrigerant tubing that is
connected to service valve B
(second from the bottom) of
the outdoor unit.
Terminal board
Be sure to perform grounding.
Attach a ground wire to either the
outdoor unit or indoor unit.
If there is a grounding terminal
inside the room, use the grounding
screw inside the indoor unit.
Page 25
Correction Notice
CMH1972
CMH2472
CMH3172
1 2 3 4 5 6 7 8 9 10 11 12
Inter Unit
(conduit)
1 2 3
Label A
A
Inter-unit cables
#14 (not provided)
1 2 3
Inter-unit cables
#14 (not provided)
Label B
B
CM1972
CM2472
CM3172
Outdoor unit
Terminal board
1
2
Inter Unit
(conduit)
Inter-unit cables
#14 (not provided)
Inter-unit cables
#14 (not provided)
Be sure to apply the provided labels to both
ends of the inter-unit cables to prevent mis-
wiring. The units will not function if the wiring
connections are incorrect.
# ... AWG (American Wire Gauge)
Fig. 31
CLM1972
CLM2472
CLM3172
Power supply
(conduit)
Power:
Single-phase,
230/208VAC 60HZ
Power breaker
(not provided)
Ground
Power cable (not provided)
(#12: Less than 85 ft.)
Indoor unit D
D is the indoor unit with
refrigerant tubing that is
1 2 3
connected to service valve
D (top) of the outdoor unit.
Terminal board
Label D
D
Indoor unit C
C is the indoor unit with
refrigerant tubing that is
1 2 3
connected to service valve
C (third from the bottom)
of the outdoor unit.
Label C
Terminal board
C
492
85264190
000

Advertisement

loading