Specification
Specification
Input requirements
Input requirements
Rated input voltage
Rated input current
Rated input power (W)
Rated input power (BTUs per hour)
Power supply output
Power supply output
Rated steady-state power (W)
Maximum peak power (W)
Maximum peak power
WARNING:
WARNING: To reduce the risk of electric shock or energy hazards:
This equipment must be installed by trained service personnel.
Connect the equipment to a reliably grounded secondary circuit source. A secondary circuit has no direct connection to
a primary circuit and derives its power from a transformer, converter, or equivalent isolation device.
The branch circuit overcurrent protection must be rated 27 A.
CAUTION: This equipment is designed to permit the connection of the earthed conductor of the DC supply circuit to the
CAUTION:
earthing conductor at the equipment.
If this connection is made, all of the following must be met:
This equipment must be connected directly to the DC supply system earthing electrode conductor or to a bonding
jumper from an earthing terminal bar or bus to which the DC supply system earthing electrode conductor is connected.
This equipment must be located in the same immediate area (such as adjacent cabinets) as any other equipment that
has a connection between the earthed conductor of the same DC supply circuit and the earthing conductor, and also the
point of earthing of the DC system. The DC system must be earthed elsewhere.
The DC supply source is to be located within the same premises as the equipment.
Switching or disconnecting devices must not be in the earthed circuit conductor between the DC source and the point of
connection of the earthing electrode conductor.
Websites
Websites
Value
Value
-40 VDC to -72 VDC
-48 VDC nominal input
24 A at -40 VDC input
19 A at -48 VDC input, nominal input
12.4 A at -72 VDC input
874 W at -40 VDC input
865 W at -48 VDC input, nominal input
854 W at -72 VDC input
2,983 at -40 VDC input
2,951 at -48 VDC input, nominal input
2,912 at -72 VDC input
800 W at -40 VDC to -72 VDC
800 W at -40 VDC to -72 VDC
800 W at 200 VAC to 277 VAC input
800 W at 380 VDC input