3.2. Installation dimensions
• Provide the space around the unit as shown in the following fi gure.
6 (150) or more
16 (400) or
more
1 16 in. (400 mm) or more when drain from drain pipe.
• Provide a service hole for inspection purposes.
• Do not place any wiring or illumination in the service space, as they will impede service.
• When an air fi lter is installed on the air inlet, provide enough service space to replace
the fi lter.
Air
12 (300) or
Service hole
more
Control box
20 (500) or more
Air
12 (300) or
Service space
more
Control box
62 in. (1,550) or more
] 1
3.3. Installation the unit
Install the air conditioner in a location which can withstand a load of at least 5 times
the weight of the main unit and which will not amplify sound or vibration. If the
installation location is not strong enough, the indoor unit may fall and cause injuries.
If the job is done with the panel frame only, there is a risk that the unit will come loose.
Please take care.
Unit: in. (mm)
1
Unit: in. (mm)
Air
Intake panel
Air
Unit: in. (mm)
WARNING
3.3.1. Installing the hangers
Hanging bolt installation diagram.
(Top side)
29-1/8 (740)
18-3/4 (477)
(Right side)
When fastening the hangers, make the bolt positions uniform.
The distance of
is adjustable according to the place of the hanging bolts.
(MAX. : 21-5/8 in. (550 mm), MIN. : 16-1/8 in. (410 mm))
Slide the unit in the arrow direction and fasten it.
Hanging bolt M10
(Field supply)
Bolt Strength
Fasten the unit securely with special nuts A and B.
3.3.2. Leveling
Base vertical direction leveling on the unit (right and left).
Level meter
(Right side)
Unit: in. (mm)
Unit: in. (mm)
WARNING
Special nut A (Accessories)
Washer (Field supply)
Special nut B (Accessories)
Hanger (Accessories)
86.8 to 130.2 lbf·in. (9.81 to 14.71 N·m)
WARNING
En-4