7.4. Function setting

• FUNCTION SETTING can be performed with the wired or wireless remote controller.
(The remote controller is optional equipment)
• Refer to the wired or wireless remote controller manual for detailed setting information.
(Set IU AD, REF AD SW to 0)
• Refer to "7.1. Setting the address" for indoor unit address and refrigerant circuit address
settings.
• Turn the power of the indoor unit ON before starting the setting.
* Turning on the power to the indoor units initializes EEV, so make sure the pip-
ing air tight test and vacuuming have been conducted before turning on the
power.
* Also check again to make sure no wiring mistakes were made before turning
on the power.
Function details
Function
Function
Setting number
number
00
Standard
Filter
01
Longer
indicator
11
interval
02
Shorter
00
Enable
01
Disable
Filter
indicator
13
Display only
action
on central
02
remote
controller
00
Standard
Cool air
temperature
30
01
Adjust (1)
trigger
02
Adjust (2)
00
Standard
01
Adjust (1)
Heat air
temperature
31
02
Adjust (2)
trigger
03
Adjust (3)
00
Enable
Auto restart
40
01
Disable
00
Super low
Cool Air
Follow the
43
Prevention
setting on
01
the remote
controller
00
Start/Stop
Emergency
External
01
46
control
02
Forced stop
00
Display only
Error report
47
on central
target
01
remote
controller
Follow the
setting on
Fan set-
00
the remote
ting when
controller
cooling
49
thermostat
OFF
01
Details
Default
Adjust the fi lter cleaning
interval notifi cation. If the
notifi cation is too early,
change to setting 01. If the
notifi cation is too late, change
to setting 02.
Enable or disable the fi lter
indicator. Setting 02 is for
use with a central remote
controller.
Adjust the cool air trigger
temperature. To lower the
trigger temperature, use
setting 01. To raise the trigger
temperature, use setting 02.
Adjust the heat air trigger
temperature. To lower the
trigger temperature by 6
degrees C, use setting 01. To
lower the trigger temperature
by 4 degrees C, use setting
02. To raise the trigger tem-
perature, use setting 03.
Enable or disable automatic
system restart after a power
outage.
Restrain the cold airfl ow
with making the airfl ow
lower when starting heating
operation. To correspond to
the ventilation, set to 01.
Allow an external controller to
start or stop the system, or to
perform an emergency stop.
* If an emergency stop is
performed from an external
controller, all refrigerant
stop
systems will be disabled.
* If forced stop is set, indoor
unit stops by the input to
the external input terminals,
and Start/Stop by a remote
controller is restricted.
All
Change the target for report-
ing errors. Errors can either
be reported in all locations, or
only on the wired remote.
When set to 01, the fan stops
when the thermostat is OFF
in cooling operation. Con-
nection of the wired remote
controller (2-wire type or
3-wire type) and switching its
Stop
thermistor are necessary.
Function
Function
Setting number
number
00
Mode 0
01
Mode 1
Switching
02
Mode 2
functions
03
Mode 3
for external
04
Mode 4
inputs and
60
external
05
Mode 5
outputs
06
Mode 6
terminals
07
Mode 7
08
Mode 8
Auxiliary
00
heater con-
Auxiliary
01
heater con-
Heat pump
02
prohibition
Control
control
switching
61
Heater
of external
selection
heaters
03
control using
outdoor tem-
perature 1
Heater
selection
04
control using
outdoor tem-
perature 2
00
Setting 0
01
Setting 1
Operating
temperature
02
Setting 2
switching
62
03
Setting 3
of external
heaters
04
Setting 4
05
Setting 5
Temperature conditions when the external heater is ON
Temperature (t) when the external heater is ON= Room temperature - set temperature
00
00
t < -5.4°F (-3°C)
01
t < -3.6°F (-2°C)
02
t < -3.6°F (-2°C)
03
t < -5.4°F (-3°C)
04
t < -7.2°F (-4°C)
05
t < -9.0°F (-5°C)
Details
Default
• Set this function when
connecting the VRF system
to a ventilator, economizer,
humidifi er, or other external
device.
• The connection terminal
functions can be changed
depending on the type of
external device. For details
of the connection terminal
functions, see the Design &
Technical Manual.
trol 1
trol 2
Sets the control method for
the external heater being
used. For details of the con-
trol method, see the Design &
Technical Manual.
• Sets the temperature condi-
tions when the external
heater is ON.
• For the temperature
conditions, see "Tempera-
ture conditions when the
external heater is ON". For
a more detailed explanation,
see the Design & Technical
Manual.
Set value of function: 61
01
02
03
t ≤ -0.9°F (-0.5°C)
t ≤ -1.8°F (-1°C)
t ≤ -3.6°F (-2°C)
t ≤ -5.4°F (-3°C)
t ≤ -7.2°F (-4°C)
t ≤ -9.0°F (-5°C)
04
En-16