Ventilation Into a Room For Combustion Air is an Essential Requirement.
Any apertures provided for this purpose must not be restricted or blocked.
Flues Without a Flue Draft Stabiliser 2.5kW-5kW Output
When installing without a flue draft stabiliser into houses built before 2008, no
additional permanent ventilation will be required.* Houses built after this date will
require additional means of permanent ventilation direct to outside of at least 4400
2
mm
.
* Note: Installers must verify adequate draw and install ventilation if required. See Appendix F of
Building Regulations Approved Document J.
5kW-8kW Output - If you are intending to burn the stove above the independently
tested 5kW output, then a permanently open air vent into the room where the stove is
situated will be required. For house built before 2008, the vent must have a free area of
2
at least 1650mm
. For house built after 2008, the vent must have a free area of at least
2
4400mm
.
Flues With a Flue Draft Stabiliser 2.5kW-5kW Output
When installing with a flue draft stabiliser into houses built before 2008, at least
2
1500mm
additional means of permanent ventilation direct to outside is required.
Houses built after this date will require additional means of permanent ventilation direct
to outside of at least 6800 mm
5kW-8kW Output - If you are intending to burn the stove above the independently
tested 5kW output, then a permanently open air vent into the room where the stove is
situated will be required. For house built before 2008, the vent must have a free area of
2
at least 4050mm
. For house built after 2008, the vent must have a free area of at least
2
6800mm
.
Top or Rear Flue
Remove the collar and accessory pack from the stove. The
stove will arrive with the blanking plate fitted to the rear.
This can be removed if required allowing the collar to be
fitted for rear flue installations. The circular cut out in the
rear heat shield must be removed to enable this style of
connection – see image.
Remove the panel from the stove by unscrewing the four
screws and then remove the circular cut out for rear flue
installations. Replace the rear heat shield. Remember to fit
the blanking plate to the unused flue position if it has been
removed.
9
2
.
SCREWS

Advertisement

loading

Related Products for GALLERY ECO Series

This manual is also suitable for:

Firefox 8 ecoClassic 8 eco