Ditek ZEUS Series Installation Instructions Manual

Ditek ZEUS Series Installation Instructions Manual

Advertisement

Quick Links

ZEUS
Series Surge Protective Device (SPD)
Danger – Hazard of Electrical Shock, Explosion or Arc Flash
Only qualified licensed electricians should install or service SPDs
Verify that all power circuits are de-energized before making connections. SPDs should never be installed or serviced
when energized or during electrical storms
Follow safe electrical work practices and use appropriate safety precautions including Personal Protection Equipment
(PPE)
Confirm XO N-G bonding at upstream transformer
When used in outdoor applications, customer must seal the conduit nipple using watertight fittings (not included) to
ensure watertight connection
Read this manual in its entirety prior to installation
These installation instructions do not replace the national or local electrical codes
Failure to follow these instructions can result in death, serious injury and/or equipment damage
Caution – Ungrounded power systems are inherently unstable and can produce excessively high line-to-ground voltages
during certain fault conditions. During these fault conditions any electrical equipment, including an SPD, may be
subjected to voltages which exceed their designed ratings. This information is being provided to the user so that an
informed decision can be made before installing any electrical equipment on an ungrounded power system.
One DITEK Center 1720 Starkey Road - Largo, FL 33771
Phone: 1-800-753-2345 Direct: 727-812-5000
Technical Support: 1-888-472-6100
www.diteksurgeprotection.com
I
NSTALLATION
INT-100183-001
191620 R3
I
NSTRUCTIONS
ZEUS™ S
ERIES

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the ZEUS Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Ditek ZEUS Series

  • Page 1 This information is being provided to the user so that an informed decision can be made before installing any electrical equipment on an ungrounded power system. One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001...
  • Page 2 (SCCR), maximum continuous operating voltage (MCOV), voltage protection rating (VPR) and product options. Check that the product nameplate matches your intended application. One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...
  • Page 3 Rotate to desired position. Re- install backplane using the four screws. Insert RJ-45 communication cable into appropriate RJ-45 cord clip. Re- connect RJ-45 communication cable. One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...
  • Page 4 DITEK for assistance. If ordered with disconnect switch option “T” device will include UL98 Listed load-break disconnect switch. The One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...
  • Page 5 (0). The counter is equipped with a backup storage which will retain information indefinitely even upon power loss. One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...
  • Page 6 Re-install the two mounting screws; re-torque SPD module conductors according to table. 5. Warranty DITEK warrants ZEUS Series for a period of 10 years from SPD Module (D200M-….M / D300M…..M) the date of delivery to the purchaser to be free from defects in both workmanship and materials.
  • Page 7 D200M-277/4803YT, D300M-277/4803YT 3-Phase DELTA, 3-Wire + Ground 3-Phase DELTA, 3-Wire + Ground D200M-2403DT, D300M-2403DT D200M-2403D, D300M-2403D D200M-4803DT, D300M-4803DT D200M-4803D, D300M-4803D One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...
  • Page 8 ZEUS™ S ERIES Mechanical Drawings D200M D300M Maximum Weight = 23 lbs D200M…T D300M…T 10.00 Maximum Weight = 27 lbs One DITEK Center 1720 Starkey Road - Largo, FL 33771 INT-100183-001 Phone: 1-800-753-2345 Direct: 727-812-5000 191620 R3 Technical Support: 1-888-472-6100 www.diteksurgeprotection.com...