8. Dip switch setting

Operate according to the following setting as necessary after refrigerant piping construction and electrical wiring
construction are finished.
1. Code setting for the address of wired control and the capacity of connection kit:
1 is ON, 0 is OFF
SW3_1
Wired Indoor
~
Address
SW3_4
SW3_5
AHU
~
Capacity
SW3_8
2. Code setting for the postal address of the connection kit:
SW2 is used for AH devices address setting, 1 is ON, 0 is OFF
Manner of set
SW2_1
address
The
SW2_2
communication
~
address of first
SW2_8
indoor unit
address
[1]
[2]
[3]
[4]
0
0
0
0
0
0
0
1
0
0
1
0
...
...
...
...
1
1
1
1
[5]
[6]
[7]
[8]
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
1
1
0
1
1
1
1
0
1
1
1
1
0
Set the address with automatism (default)
1
[2] [3] [4] [5] [6] [7] [8]
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
0
0
0
0
1
Wired Indoor Adress
0# Slave Unit (Default)
1# Slave Unit
2# Slave Unit
......
15# Slave Unit
AHU Capacity
AH1-070B
AH1-140B
AH1-280B
AH1-560B/AH1-730B
Set the address with dip switch
Communication
address
0
0
0#(default)
0
1
1#
1
0
2#
1
1
3#
0
0
4#
0
1
5#
1
0
6#
1
1
7#
30
/
/
/
/
/
/
/
/
/
/
/
/
Center controller
address
0#(default)
1#
2#
3#
4#
5#
6#
7#