Using The Stop Valve And Service Port - Daikin RXP25N5V1B Installer's Reference Manual

Hide thumbs Also See for RXP25N5V1B:
Table of Contents

Advertisement

7.2.6 Using the stop valve and service port

To handle the stop valve
RXP20~35N5V1B+ARXP20~35N5V1B
R32 split series
4P519439-22V – 2022.10
4 Flare the pipe. Set exactly at the position as shown in the following figure.
A
Flare tool for R32
(clutch type)
A
0~0.5 mm
5 Check that the flaring is properly made.
a
a Flare's inner surface MUST be flawless.
b The pipe end MUST be evenly flared in a perfect circle.
c Make sure the flare nut is fitted.
CAUTION
Do NOT open the valves before flaring is complete. This would cause refrigerant gas
leakage.
Take the following guidelines into account:
The stop valves are factory closed.
The following figure shows the stop valve parts required when handling the
valve.
a
b
c
d
a Service port and service port cap
b Valve stem
c Field piping connection
d Stem cap
Keep both stop valves open during operation.
Do NOT apply excessive force to the valve stem. Doing so may break the valve
body.
ALWAYS make sure to secure the stop valve with a spanner, then loosen or
tighten the flare nut with a torque wrench. Do NOT place the spanner on the
stem cap, as this could cause a refrigerant leak.
a
b
Conventional flare tool
Clutch type
(Ridgid-type)
1.0~1.5 mm
b
c
7
Piping installation
|
Wing nut type
(Imperial-type)
1.5~2.0 mm
Installer reference guide
37

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Rxp20n5v1bRxp35n5v1bArxp20n5v1bArxp25n5v1bArxp35n5v1b

Table of Contents